2016-02-18 06:53:20 | 1) IDENTIFY THE PIPE MATERIAL ON THE PLAN FOR THE GAS |
| DRYER AND THE WATER HEATER.2014 FBC SEC. 107.2.1. |
| 2) SUBMIT MANUF. SPECIFICATIONS FOR THE NEW GAS |
| APPLIANCES. APPLIANCES SHALL BE LISTED AND LABELED IN |
| ACCORDANCE WITH 2014 FGC SEC. 301.3. |
| 3) SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER |
| OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS |
| SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3. |
| 4) SIZE THE NEW GAS LINES TO THE WATER HEATER AND THE |
| GAS DRYER. |
| 5) SIZE THE EXISTING GAS LINE IN ITS ENTIRETY TO ENSURE |
| THE EXISTING GAS LINE IS ADEQUATE TO CARRY THE ADDED |
| BTU LOAD. 2014 FBC SEC. 107.2.1. |
| 6) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE |
| WATER HEATER AND THE DRYER. SUBMIT COMBUSTION AIR |
| CALCULATIONS FOR THE DRRYER AND THE WATER HEATER. 2014 |
| FGC SEC.304.1. |
| 7) INDICATE ON THE PLAN IF ANY OF THE GAS PIPE WILL BE |
| INSTALLED BELOW GROUND .FGC 107.2.1. |
| 8) IS THERE A CRAWL SPACE BELOW THIS STRUCTURE? IF SO, |
| INDICATE ON THE PLAN IF THE GAS PIPE WILL BE INSTALLED |
| WITHIN THE CRAWL SPACE AND SHOW THE TYPE OF PIPING TO |
| BE INSTALLED WITHIN THE CRAWL SPACE. NOTE - P.E. PIPE |
| CAN ONLY BE INSTALLED OUTSIDE UNDERGROUND IN ACCORDANCE |
| WITH 2014 FBC SEC.404.17.1. P.E. PIPE CANNOT BE |
| INSTALLED ABOVE GROUND IN A CRAWL SPACE. |
| |