Plan Review Details - Permit 16020521
Plan Review Stops For Permit 16020521 |
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-02-25 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-02-25 |
Time |
11:23 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-25 |
Time |
09:35 |
Sent To |
I |
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-02-19 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-02-19 |
Time |
10:14 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-19 |
Time |
09:34 |
Sent To |
I |
|
Notes |
2016-02-19 11:59:05 | 1ST ELECTRICAL REVIEW NOTES: | | REVIEWED FOR COMPLIANCE WITH: | | FBC 5TH EDITION 2014 | | NFPA 70 2011 (NEC) | | | | CORRECTIONS REQUIRED: | | 1. THE PLAN SET IS INCOMPLETE. ACCORDING TO THE SHEET | | INDEX THERE IS A SHEET E-300 THAT IS MISSING. THE | | SUBMITTED PLANS WERE REVIEWED AS PRESENTED AND WOULD | | OTHERWISE BEEN APPROVED. REVISE THE SHEET INDEX OR | | PROVIDE THE MISSING PAGE. | | | | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR | | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER | | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER | | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID | | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR | | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE | | GREATLY APPRECIATED. | | | | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO | | CONTACT ME DIRECTLY. | | | | THANK YOU, | | MIKE ALBARRAN | | ELECTRICAL PLANS EXAMINER | | PH: 561-805-6746 | | EMAIL: [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-02-25 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-02-25 |
Time |
11:25 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-23 |
Time |
15:20 |
Sent To |
|
|
Notes |
2016-02-25 11:25:21 | 2/25/16 PASSED ELECTRICAL REVIEW. CONTRACTOR NOTIFIED | | VIA CELL PHONE (561) 350-7538. SENT FILE TO SMALL READY | | BIN "B". MA | 2016-02-23 15:20:26 | REVISION ROUTED TO MALBARRAN |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-02-19 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-02-19 |
Time |
10:20 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-16 |
Time |
15:04 |
Sent To |
|
|
Notes |
2016-02-19 12:05:06 | 2/19/16 FAILED ELECTRICAL REVIEW FOR INCOMPLETE PLANS. | | SPOKE W/MARK FURMAN. SENT FILE TO SMALL DENIED BIN "B". | | MA | 2016-02-16 15:05:04 | REVISION ROUTED TO MALBARRAN |
|
|
|