Plan Review Details - Permit 16020515
Plan Review Stops For Permit 16020515
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-05-09 Cont ID  
Sent By rmcdouga Date 2016-05-09 Time 09:19 Rev Time 0.00
Received By rmcdouga Date 2016-05-09 Time 09:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By rmcdouga Date 2016-02-18 Time 07:46 Rev Time 0.00
Received By rmcdouga Date 2016-02-18 Time 06:43 Sent To  
Notes
2016-02-18 09:54:21PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN THE 2014 FBC RESIDENTIAL CODE PRIVATE SWIMMING
 POOLS HAVE BEEN MOVED TO CHAPTER 45. PLEASE UPDATE THE
 CODE REFERENCES IN THE PLANS THAT WERE SUBMITTED. SEE
 SHEETS P-1 AND N-1.
  
 2) THE POOL BARRIER NOTE ON P-1 REFERENCES THE 2010
 FBC. UPDATE NOTE TO THE 2014 FBC AND THE CORRECT
 SECTIONS.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-05-09 Cont ID  
Sent By rmcdouga Date 2016-05-09 Time 10:05 Rev Time 0.00
Received By rmcdouga Date 2016-05-09 Time 09:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By rmcdouga Date 2016-02-18 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2016-02-18 Time 08:21 Sent To  
Notes
2016-02-18 09:49:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014) / 2011 NEC
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) IN THE 2014 FBC RESIDENTIAL CODE THE PRIVATE
 SWIMMING POOL ELECTRICAL PROVISIONS HAVE BEEN INSERTED
 IN CHAPTER 42. PLEASE UPDATE THE CODE REFERENCES.
  
 2) NOTE 2 UNDER APPLICABLE CODES ON SHEET C-1,
 INCORRECTLY REFERENCES THE 2014 NEC. ELECTRICAL NOTE 1
 ON SHEET N-1, ALSO INCORRECTLY REFERENCES THE 2014 NEC.
 THE CURRENT REFERENCED EDITION IS THE 2011 NEC.
  
 3) THE SITE PLAN SHOWS AN OVERHEAD ELECTRICAL SERVICE
 DROP DIRECTLY OVER THE PROPOSED POOL. SHOW HOW
 COMPLIANCE WITH FBCR-E4203.6 FOR OVERHEAD CONDUCTOR
 CLEARANCES AND E4203.7 FOR UNDERGROUND WIRING.
  
 4) SHOW COMPLIANCE WITH FBCR-E4203.1.2 FOR REQUIRED
 GFCI PROTECTED RECEPTACLE LOCATED A MINIMUM OF 6 FEET
 FROM AND NOT MORE THAN 20 FEET FROM THE INSIDE POOL
 WALL.
  
 5) SHOW COMPLIANCE WITH FBCR-E4204.3 FOR THE BONDING OF
 THE POOL WATER.
  
 6) THE EQUIPOTENTIAL BONDING NOTE ON SHEET P-3
 REFERENCES THE 2008 NEC AND THE 2010 FBC. CITE THE
 CURRENT EDITIONS OF NEC AND FBC.
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-02-18 Cont ID  
Sent By rmcdouga Date 2016-02-18 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2016-02-18 Time 07:47 Sent To  
Notes
2016-02-18 08:45:43NO GAS WAS INDICATED ON THE PLANS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-09 Cont ID  
Sent By rmcdouga Date 2016-05-09 Time 10:05 Rev Time 0.00
Received By rmcdouga Date 2016-05-03 Time 13:50 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-18 Cont ID  
Sent By rmcdouga Date 2016-02-18 Time 08:22 Rev Time 0.00
Received By rmcdouga Date 2016-02-16 Time 11:02 Sent To  
Notes
2016-02-16 11:02:54ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-05-09 Cont ID  
Sent By rmcdouga Date 2016-05-09 Time 09:49 Rev Time 0.00
Received By rmcdouga Date 2016-05-09 Time 09:19 Sent To  
Notes
2016-05-09 09:48:59APPROVED WITH EXCEPTION
 SUBMIT REVISED FLOW CALCULATIONS USING THE CORRECT PUMP
 CURVE. THE PLANS SPECIFY THE JANDY FLO PRO FHPM 1.0-2
 POOL PUMP. THIS IS THE 2 SPEED 1 HP MODEL PUMP. ON
 SHEET P-2 THE PUMP CURVE FOR THE FHPM .75 HP WAS USED
 TO DETERMINE THE FLOW RATE IN GPM. THE CALCULATIONS
 WILL NEED TO BE REDONE USING THE HIGHER SPEED PUMP
 CURVE. FBCR 4501.6.3

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By rmcdouga Date 2016-02-18 Time 08:08 Rev Time 0.00
Received By rmcdouga Date 2016-02-18 Time 08:08 Sent To  
Notes
2016-02-18 09:46:45PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS SPECIFY THE JANDY FLO PRO FHPM 1.0-2 POOL
 PUMP. THIS IS THE 2 SPEED 1 HP MODEL PUMP. ON SHEET P-2
 THE PUMP CURVE FOR THE FHPM .75 HP WAS USED TO
 DETERMINE THE FLOW RATE IN GPM. THE CALCULATIONS WILL
 NEED TO BE REDONE USING THE HIGHER SPEED PUMP CURVE.
 FBCR 4501.6.3
  
 2) PLUMBING NOTE 3 ON N-1 INCORRECTLY CITES SECTION
 605.21 FOR THE REQUIRED PURPLE PRIMER. THE CORRECT
 SECTION IS 605.22.2.
  
 3) NOTE 1 AND NOTE 11 CITE SECTIONS R4101. IN THE 2014
 FBC RESIDENTIAL CODE PRIVATE SWIMMING POOLS HAVE BEEN
 MOVED TO CHAPTER 45. PLEASE UPDATE THE CODE REFERENCES.
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By rmcdouga Date 2016-05-09 Time 10:05 Rev Time 0.00
Received By llouie Date 2016-05-06 Time   Sent To B
Notes
2016-05-06 09:17:43ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) OVERHEAD WIRE CLEARANCE PER 2014 FBC SHALL BE MET
 PRIOR TO FINAL INSPECTION.
  
 2.) COMPLIANCE WITH POOL BARRIER PER ZLDR SECTION
 94-304(D)(2)(C) REQUIRED.
  
 REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL
 COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458
 IF THERE ARE QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By llouie Date 2016-02-17 Time 17:12 Rev Time 0.00
Received By llouie Date 2016-02-17 Time 17:12 Sent To P
Notes
2016-02-17 17:19:00** FAILED **
  
 1.) ACCORDING TO THE SURVEY, THERE SEEMS TO BE OVERHEAD
 WIRES RUNNING ACROSS THE PROPOSED LOCATION OF THE
 SWIMMING POOL. A MINIMUM DISTANCE CLEARANCE IS REQUIRED
 FROM OVERHEAD LINES. PLEASE CONTACT THE BUILDING
 DEPARTMENT (561) 805-6700 FOR THE DISTANCE CLEARANACE
 FROM OVERHEAD WIRES, OTHERWISE, PROVIDE
 INFORMATION/EVIDENCE THAT OTHER ALTERNATIVES ARE
 PLANNED TO RELOCATE THE WIRES.
  
 2.) ILLUSTRATE THE LOCATION OF THE POOL EQUIPMENT,
 INCLUDING SETBACK FROM THE PROPERTY LINE IN THE SITE
 PLAN.
  
 CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.