Plan Review Stops For Permit 16020515 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
P |
Date |
2016-05-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
09:19 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-05-09 |
Time |
09:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-02-18 |
Time |
07:46 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-02-18 |
Time |
06:43 |
Sent To |
|
|
Notes |
2016-02-18 09:54:21 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) IN THE 2014 FBC RESIDENTIAL CODE PRIVATE SWIMMING | | POOLS HAVE BEEN MOVED TO CHAPTER 45. PLEASE UPDATE THE | | CODE REFERENCES IN THE PLANS THAT WERE SUBMITTED. SEE | | SHEETS P-1 AND N-1. | | | | 2) THE POOL BARRIER NOTE ON P-1 REFERENCES THE 2010 | | FBC. UPDATE NOTE TO THE 2014 FBC AND THE CORRECT | | SECTIONS. | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
P |
Date |
2016-05-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-05-09 |
Time |
09:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-02-18 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-02-18 |
Time |
08:21 |
Sent To |
|
|
Notes |
2016-02-18 09:49:14 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) / 2011 NEC | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY ELECTRICAL | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) IN THE 2014 FBC RESIDENTIAL CODE THE PRIVATE | | SWIMMING POOL ELECTRICAL PROVISIONS HAVE BEEN INSERTED | | IN CHAPTER 42. PLEASE UPDATE THE CODE REFERENCES. | | | | 2) NOTE 2 UNDER APPLICABLE CODES ON SHEET C-1, | | INCORRECTLY REFERENCES THE 2014 NEC. ELECTRICAL NOTE 1 | | ON SHEET N-1, ALSO INCORRECTLY REFERENCES THE 2014 NEC. | | THE CURRENT REFERENCED EDITION IS THE 2011 NEC. | | | | 3) THE SITE PLAN SHOWS AN OVERHEAD ELECTRICAL SERVICE | | DROP DIRECTLY OVER THE PROPOSED POOL. SHOW HOW | | COMPLIANCE WITH FBCR-E4203.6 FOR OVERHEAD CONDUCTOR | | CLEARANCES AND E4203.7 FOR UNDERGROUND WIRING. | | | | 4) SHOW COMPLIANCE WITH FBCR-E4203.1.2 FOR REQUIRED | | GFCI PROTECTED RECEPTACLE LOCATED A MINIMUM OF 6 FEET | | FROM AND NOT MORE THAN 20 FEET FROM THE INSIDE POOL | | WALL. | | | | 5) SHOW COMPLIANCE WITH FBCR-E4204.3 FOR THE BONDING OF | | THE POOL WATER. | | | | 6) THE EQUIPOTENTIAL BONDING NOTE ON SHEET P-3 | | REFERENCES THE 2008 NEC AND THE 2010 FBC. CITE THE | | CURRENT EDITIONS OF NEC AND FBC. | | |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
N |
Date |
2016-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-02-18 |
Time |
07:47 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-02-18 |
Time |
07:47 |
Sent To |
|
|
Notes |
2016-02-18 08:45:43 | NO GAS WAS INDICATED ON THE PLANS. |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-05-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-05-03 |
Time |
13:50 |
Sent To |
Z |
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-02-18 |
Time |
08:22 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-02-16 |
Time |
11:02 |
Sent To |
|
|
Notes |
2016-02-16 11:02:54 | ROUTED TO ZONING |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2016-05-09 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
09:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-05-09 |
Time |
09:19 |
Sent To |
|
|
Notes |
2016-05-09 09:48:59 | APPROVED WITH EXCEPTION | | SUBMIT REVISED FLOW CALCULATIONS USING THE CORRECT PUMP | | CURVE. THE PLANS SPECIFY THE JANDY FLO PRO FHPM 1.0-2 | | POOL PUMP. THIS IS THE 2 SPEED 1 HP MODEL PUMP. ON | | SHEET P-2 THE PUMP CURVE FOR THE FHPM .75 HP WAS USED | | TO DETERMINE THE FLOW RATE IN GPM. THE CALCULATIONS | | WILL NEED TO BE REDONE USING THE HIGHER SPEED PUMP | | CURVE. FBCR 4501.6.3 |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-02-18 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-02-18 |
Time |
08:08 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-02-18 |
Time |
08:08 |
Sent To |
|
|
Notes |
2016-02-18 09:46:45 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY PLUMBING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PLANS SPECIFY THE JANDY FLO PRO FHPM 1.0-2 POOL | | PUMP. THIS IS THE 2 SPEED 1 HP MODEL PUMP. ON SHEET P-2 | | THE PUMP CURVE FOR THE FHPM .75 HP WAS USED TO | | DETERMINE THE FLOW RATE IN GPM. THE CALCULATIONS WILL | | NEED TO BE REDONE USING THE HIGHER SPEED PUMP CURVE. | | FBCR 4501.6.3 | | | | 2) PLUMBING NOTE 3 ON N-1 INCORRECTLY CITES SECTION | | 605.21 FOR THE REQUIRED PURPLE PRIMER. THE CORRECT | | SECTION IS 605.22.2. | | | | 3) NOTE 1 AND NOTE 11 CITE SECTIONS R4101. IN THE 2014 | | FBC RESIDENTIAL CODE PRIVATE SWIMMING POOLS HAVE BEEN | | MOVED TO CHAPTER 45. PLEASE UPDATE THE CODE REFERENCES. | | | | |
|
|
Review Stop |
Z |
ZONING |
Rev No |
2 |
Status |
P |
Date |
2016-05-06 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-05-09 |
Time |
10:05 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2016-05-06 |
Time |
|
Sent To |
B |
|
Notes |
2016-05-06 09:17:43 | ZONING APPROVED WITH THE FOLLOWING PROVISOS: | | | | 1.) OVERHEAD WIRE CLEARANCE PER 2014 FBC SHALL BE MET | | PRIOR TO FINAL INSPECTION. | | | | 2.) COMPLIANCE WITH POOL BARRIER PER ZLDR SECTION | | 94-304(D)(2)(C) REQUIRED. | | | | REVISIONS TO THE PLANS MAY RESULT IN ADDITIONAL | | COMMENTS. PLEASE CONTACT LINDA LOUIE @ (561) 822-1458 | | IF THERE ARE QUESTIONS. |
|
|
Review Stop |
Z |
ZONING |
Rev No |
1 |
Status |
F |
Date |
2016-02-17 |
|
|
Cont ID |
|
Sent By |
llouie |
Date |
2016-02-17 |
Time |
17:12 |
Rev Time |
0.00 |
Received By |
llouie |
Date |
2016-02-17 |
Time |
17:12 |
Sent To |
P |
|
Notes |
2016-02-17 17:19:00 | ** FAILED ** | | | | 1.) ACCORDING TO THE SURVEY, THERE SEEMS TO BE OVERHEAD | | WIRES RUNNING ACROSS THE PROPOSED LOCATION OF THE | | SWIMMING POOL. A MINIMUM DISTANCE CLEARANCE IS REQUIRED | | FROM OVERHEAD LINES. PLEASE CONTACT THE BUILDING | | DEPARTMENT (561) 805-6700 FOR THE DISTANCE CLEARANACE | | FROM OVERHEAD WIRES, OTHERWISE, PROVIDE | | INFORMATION/EVIDENCE THAT OTHER ALTERNATIVES ARE | | PLANNED TO RELOCATE THE WIRES. | | | | 2.) ILLUSTRATE THE LOCATION OF THE POOL EQUIPMENT, | | INCLUDING SETBACK FROM THE PROPERTY LINE IN THE SITE | | PLAN. | | | | CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | QUESTIONS. |
|
|