Plan Review Details - Permit 16020383
Plan Review Stops For Permit 16020383
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-22 Cont ID  
Sent By vperez Date 2016-02-22 Time 15:23 Rev Time 0.00
Received By vperez Date 2016-02-22 Time 15:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By vperez Date 2016-02-12 Time 09:29 Rev Time 0.00
Received By vperez Date 2016-02-12 Time 09:29 Sent To  
Notes
2016-02-12 09:30:07INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE NOTE THAT THE ELECTRICAL CONTRACTOR QUALIFIER
 MUST SIGN DRAWINGS SUBMITTED NOT THE PROJECT MANAGER AS
 SHOWN. PER FBC 105.3.1.2 (FLORIDA STATUE 417.003 2H
 2. PROVIDE A NOTE TO INDICATE THE CARD READERS AND
 DATA/PHONES TO BE ON SEPARATE PERMIT. A NOTE WILL
 SUFFICE. FBC 107.
 3. PROVIDE A NOTE TO MAINTAIN FIRE RATING ON DEMISING
 WALLS. NEC 300.21
 4. IDENTIFY ROOM NAME AND NUMBER WHERE THE TEMPORARY
 OUTLETS WILL BE INSTALLED WITHIN HOSPITAL.
 5. CLARIFY ON PANEL SCHEDULE AND INDICATE BRANCH SYSTEM
 SERVING THE RECEPTACLES, EXAMPLE: CRITICAL/LIFE SAFETY,
 NORMAL. FBC 107
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-22 Cont ID  
Sent By vperez Date 2016-02-22 Time 15:23 Rev Time 0.00
Received By vperez Date 2016-02-22 Time 15:23 Sent To  
Notes
2016-02-22 15:23:49TO CAROLINE
2016-02-22 14:32:03VPEREZ DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-12 Cont ID  
Sent By vperez Date 2016-02-12 Time 09:30 Rev Time 0.00
Received By vperez Date 2016-02-12 Time 09:30 Sent To  
Notes
2016-02-12 09:30:31TO LAURA
2016-02-11 09:30:27ELEC <5K