Plan Review Details - Permit 16020366
Plan Review Stops For Permit 16020366
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2016-03-15 Time 09:31 Sent To  
Notes
2016-03-15 15:56:51BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020366
 ADD: 1401 ELIZABETH AVE.
 CONT: TBD
 TEL: 561-662-7322
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MARCH 15/ 2016
 ACTION: DENIED
  
 1) PLEASE NOTE 2 SETS OF PLANS WERE SUBMITTED WITH JOHN
 HOLT P. E. THE DESIGNER OF RECORD. PLEASE NOTE ONLY (1)
 SET OF PLANS WERE SIGNED AND SEALED.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 2) NOTE THIS PERMIT IS FOR A CHANGE IN OCCUPANCY FROM
 LIGHT MANUFACTURING F1 TO A GYMNASIUM A-3 (WITHOUT
 SPECTATORS). THE PROJECT DATA SHEET A-2 INDICATES THIS
 IS A LEVEL II ALTERATION. PLEASE NOTE WITH THIS PERMIT
 BEING A CHANGE OF OCCUPANCY LEVEL 3 AND CHAPTER 10 OF
 THE 2014 FBC-EXISTING BUILDING WILL BE APPLICABLE.
 2014 EXIST. BUILD. CODE 1001.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 1002
 THROUGH 1012 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 3) EXIST. BUILD. CODE 1001.3 CHANGE OF OCCUPANCY
 CLASSIFICATION. WHERE THE OCCUPANCY CLASSIFICATION OF A
 BUILDING CHANGES, THE PROVISIONS OF SECTIONS 1002
 THROUGH 1012 SHALL APPLY. THIS INCLUDES A CHANGE OF
 OCCUPANCY CLASSIFICATION WITHIN A GROUP AS WELL AS A
 CHANGE OF OCCUPANCY CLASSIFICATION FROM ONE GROUP TO A
 DIFFERENT GROUP.
  
 3A) EXIST. BUILD. CODE 1012.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING, SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2014 FBC-B [F] 903.2.1.3 GROUP A-3. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-3
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS: 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 300 OR
 MORE;
 PLEASE NOTE THE DESIGNER OF RECORD HAS TAKEN THE
 OCCUPANT LOAD @ 50 SQ. FT. FOR THE GYM. THIS CAN ONLY
 BE TAKEN WHEN GYM EQUIPMENT IS SHOWN OTHERWISE THE
 OCCUPANT LOAD IS TAKEN AT 15 SQ. FT./ OCCUPANT PUTTING
 THE OCCUPANT LOAD OVER 300, REQUIRING FIRE SPRINKLERS.
  
 3B)EXISTING BUILDING CODE 1012.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS THAT REQUIRES A FIRE ALARM AND
 DETECTION SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS. EXISTING ALARM NOTIFICATION APPLIANCES SHALL BE
 AUTOMATICALLY ACTIVATED THROUGHOUT THE BUILDING. WHERE
 THE BUILDING IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM,
 ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
 2014 FBC-B 907.2.1 GROUP A.
 A MANUAL FIRE ALARM SYSTEM THAT ACTIVATES THE OCCUPANT
 NOTIFICATION SYSTEM IN ACCORDANCE WITH SECTION 907.5
 SHALL BE INSTALLED IN GROUP A OCCUPANCIES WHERE THE
 OCCUPANT LOAD DUE TO THE ASSEMBLY OCCUPANCY IS 300 OR
 MORE.
 PLEASE NOTE THE DESIGNER OF RECORD HAS TAKEN THE
 OCCUPANT LOAD @ 50 SQ. FT. FOR THE GYM. THIS CAN ONLY
 BE TAKEN WHEN GYM EQUIPMENT IS SHOWN OTHERWISE THE
 OCCUPANT LOAD IS TAKEN AT 15 SQ. FT./ OCCUPANT PUTTING
 THE OCCUPANT LOAD OVER 300, REQUIRING FIRE ALARM
 SYSTEM.
  
 4) EXISTING BUILDING CODE 1012.4.1 MEANS OF EGRESS FOR
 CHANGE TO HIGHER HAZARD CATEGORY. WHEN A CHANGE OF
 OCCUPANCY CLASSIFICATION IS MADE TO A HIGHER HAZARD
 CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE 1012.4, THE
 MEANS OF EGRESS SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 10 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 4A) PLEASE PROVIDE A SITE PLAN FOR HOW THE EXIT
 DISCHARGE OF THE EXITS WILL OCCUR. PLEASE NOTE WITH THE
 BUILDING BEING NON-SPRINKLERED THE EXIT DOORS ARE
 REQUIRED TO BE ? THE OVERALL DIAGONAL DISTANCE APART.
 EITHER OF THE FRONT DOORS CAN BE USED AS PART OF THE ?
 THE DIAGONAL DISTANCE APART BUT THE 2ND EXIT WILL BE
 REQUIRED TO BE THE BACK EXIT. PLEASE SHOW HOW
 COMPLIANCE WITH SECTION 1027 OF THE FBC-B AND DEPENDING
 ON THE LOCATION OF THE PROPERTY LINE 1027.4. EGRESS
 COURTS.
  
 4B) THE EXTERIOR DOOR THAT LEADS INTO THE LOBBY WILL
 NEED A NEW EXTERIOR SWING DOOR. AS PART OF A MEANS OF
 EGRESS THIS DOOR WITH AN OCCUPANT LOAD OF 50 OR GREATER
 IS REQUIRED TO SWING IN THE DIRECTION OF TRAVEL. 2014
 FBC-B 1008.1.2.
  
 4B)(1) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 4B)(2)107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY
 DCA RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING
 BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4C) THE DOOR FROM THE OPEN EXERCISE AREA THAT LEADS
 INTO THE LOBBY AREA WILL ALSO NEED TO SWING IN THE
 DIRECTION OF EGRESS TRAVEL. 2014 FBC-B 1008.1.2.
  
 5) 2014 FBC-EXISTING BUILDING CODE. 1007.1 GRAVITY
 LOADS. BUILDINGS OR PORTIONS THEREOF SUBJECT TO A
 CHANGE OF OCCUPANCY WHERE SUCH CHANGE IN THE NATURE OF
 OCCUPANCY RESULTS IN HIGHER UNIFORM OR CONCENTRATED
 LOADS BASED ON THE FLORIDA BUILDING CODE, BUILDING
 TABLE 1607.1 SHALL COMPLY WITH THE GRAVITY LOAD
 PROVISIONS OF THE FLORIDA BUILDING CODE, BUILDING.
 PLEASE NOTE THERE WAS AN ORIGINAL CORE OFFICE AND
 MEZZANINE LEVEL THAT WAS BUILT WITH THE ORIGINAL SHELL
 OF THE BUILDING. THEPALM BEACH COUNTY PROPERTY
 APPRAISERS INDICATES A 1ST FLOOR OFFICE SPACE OF 920
 SQUARE FEET AND A MEZZANINE LEVEL OF 392 SQ. FT. OF
 OFFICE SPACE. IN 1992 THERE WAS A FOUNDATION PERMIT
 ISSUED FOR INCREASING THE SIZE OF THE MEZZANINE, PERMIT
 NUMBER 92A01923 FOR A FOUNDATION PERMIT ONLY! THERE HAS
 BEEN NO OTHER BUILDING (STRUCTURAL) PERMITS PULLED
 SINCE.
 CREATION OR EXTENSION OF NONCONFORMITY RENOVATION, OR
 ALTERATION SHALL NOT CREATE OR EXTEND ANY NONCONFORMITY
 IN THE EXISTING BUILDING BEING MADE WITH REGARD TO
 ACCESSIBILITY, STRUCTURAL STRENGTH, FIRE SAFETY, MEANS
 OF EGRESS, OR THE CAPACITY OF MECHANICAL, PLUMBING, OR
 ELECTRICAL SYSTEMS. THERE HAS BEEN WORK PREFORMED
 WITHOUT THE BENEFIT OF A PERMIT AND INSPECTIONS.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 110.1 GENERAL. CONSTRUCTION OR WORK FOR
 WHICH A PERMIT IS REQUIRED SHALL BE SUBJECT TO
 INSPECTION BY THE BUILDING OFFICIAL AND SUCH
 CONSTRUCTION OR WORK SHALL REMAIN ACCESSIBLE AND
 EXPOSED FOR INSPECTION PURPOSES UNTIL APPROVED.
 APPROVAL AS A RESULT OF AN INSPECTION SHALL NOT BE
 CONSTRUED TO BE AN APPROVAL OF A VIOLATION OF THE
 PROVISIONS OF THIS CODE OR OF OTHER ORDINANCES OF THE
 JURISDICTION. INSPECTIONS PRESUMING TO GIVE AUTHORITY
 TO VIOLATE OR CANCEL THE PROVISIONS OF THIS CODE OR OF
 OTHER ORDINANCES OF THE JURISDICTION SHALL NOT BE
 VALID. IT SHALL BE THE DUTY OF THE PERMIT APPLICANT TO
 CAUSE THE WORK TO REMAIN ACCESSIBLE AND EXPOSED FOR
 INSPECTION PURPOSES.
  
 THE ADDITIONAL SQUARE FOOTAGE OF THE 1ST FLOOR OFFICE,
 MEZZANINE LEVEL AND NEW STAIRWAY, HANDRAIL & GUARDRAIL
 SYSTEMS AND RELOCATED STAIRWAY WILL NEED TO BE SHOWN ON
 PLANS AND VALUATION OF THIS WORK ADDED TO THE SCOPE OF
 THIS PERMIT. EXPLORATORY OPENINGS INTO CEILINGS, WALLS
 AND OR STAIR STRINGERS FOR VERIFYING CODE COMPLIANCE,
 CODE VIOLATIONS WILL NEED TO BE CORRECTED .
  
 6) 2014 EXISTING BUILDING CODE 1012.7.2 STAIRWAYS. WHEN
 A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY AS SHOWN IN TABLE 1012.4,
 INTERIOR STAIRWAYS SHALL BE ENCLOSED AS REQUIRED BY THE
 FLORIDA BUILDING CODE, BUILDING.
  
 7) 2014 EXISTING BUILDING CODE. 1012.8 ACCESSIBILITY.
 EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE
 PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY.
 2014 FBC-ACCESSIBILITY CODE 202.4.1 DISPROPORTIONATE
 COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 8) EXISTING BUILDING CODE. SECTION 1013 ENERGY
 CONSERVATION SEE THE FLORIDA BUILDING CODE, ENERGY
 CONSERVATION.
  
 9) PLEASE PROVIDE A SITE PLAN. 107.3.5.1.1 MINIMUM PLAN
 REVIEW CRITERIA FOR COMMERCIAL BUILDINGS BUILDINGS.
 1. SITE REQUIREMENTS:
 PARKING
 FIRE ACCESS
 VEHICLE LOADING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 LOCATION OF WATER LINES AND SEWER LINES
  
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-17 Cont ID  
Sent By vperez Date 2016-03-17 Time 06:42 Rev Time 0.00
Received By vperez Date 2016-03-17 Time 06:42 Sent To  
Notes
2016-03-17 06:45:51INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1.PLEASE PROVIDE COMPLETE ELECTRICAL INFORMATION FOR
 THE CHANGE OF OCCUPANCY CONTEMPLATED.
 2.FURTHER COMMENTS TO FOLLOW UPON RESUBMITTAL.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-22 Cont ID  
Sent By pleduc Date 2016-02-22 Time   Rev Time 0.00
Received By pleduc Date 2016-02-22 Time 14:35 Sent To B
Notes
2016-02-22 14:54:14THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THE EQUIPMENT PLAN SHALL BE PROVIDED TO THE FIRE
 INSPECTOR FOR APPROVAL.
  
 2. THE OCCUPANCY LOAD SIGN SHALL BE POSTED.
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-16 Cont ID  
Sent By ccole Date 2016-03-17 Time 06:47 Rev Time 0.00
Received By vperez Date 2016-03-17 Time 06:47 Sent To Z
Notes
2016-03-17 06:48:103/17 TO CAROLINE FOR COMPLETION
2016-03-09 09:13:32B16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 09:31 Rev Time 0.00
Received By jwitmer Date 2016-03-15 Time 09:31 Sent To  
Notes
2016-03-15 09:31:51IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-16 Cont ID  
Sent By ccole Date 2016-03-16 Time 14:29 Rev Time 0.00
Received By ccole Date 2016-03-16 Time 14:29 Sent To  
Notes
2016-03-16 15:10:311ST REVIEW: FBC 2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION
 PERMIT #16020366
 3/16/16
  
 1) REFER TO SECTION C101.4.4 FBC-14 ENERGY CONSERVATION
 AND SUBMIT ENERGY CALCULATIONS FOR THE PROPOSED CHANGE
 OF OCCUPANCY- SEE SECTION C101.5.1 FOR COMPLIANCE
 MATERIALS, AND C401.2 FOR COMPLIANCE METHODS AND
 REQUIREMENTS.
 2) REFER TO SECTION 1009.1 FBC-14 EXISTING BUILDING AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR EACH
 OCCUPIABLE ROOM OR SPACE-IN ACCORDANCE WITH TABLE 404.3
 FBC-14 MECHANICAL. PROVIDE A VENTILATION SCHEDULE ON
 THE PLAN INDICATING THE REQUIRED AND PROVIDED AMOUNT OF
 OUTDOOR AIR CFM'S. COMPLIANCE FOR NATURAL VENTILATION
 CAN BE FOUND IN SECTION 402.
 3) NO MECHANICAL PLANS HAVE BEEN SUBMITTED FOR THE
 PROPOSED PROJECT, HOWEVER THE PLANS INDICATE AN
 AIR-HANDLER ON THE 1ST FLOOR ARCHITECTURAL PLANS.
 PLEASE PROVIDE COMPLETE AC PLANS AND SPECIFICATIONS
 INCLUDING: A) AC COOLING AND HEATING CALCULATIONS. B)
 AN AC DUCT LAYOUT PLAN AND EQUIPMENT SCHEDULE. C) AIR
 HANDLER AND CONDENSER INSTALLATION DETAILS. D) OUTSIDE
 AIR DETAILS INCLUDING LOCATION OF THE AIR INTAKE, TYPE
 AND SIZE OF O/A INTAKE AND CFM CAPACITY. E) CONDENSATE
 DISPOSAL DETAILS. E) TOILET ROOM EXHAUST VENTILATION
 PLANS AND DETAILS.
 4) THE OPEN AREA HAS BEEN DESIGNATED AS THE EXERCISE
 AREA WHICH IS CLASSIFIED AS "OCCUPIABLE SPACE" AND
 THEREFORE MUST BE PROVIDED WITH HEAT AND VENTILATION.
 PLEASE REFER TO COMMENT #2 ABOVE, AND ALSO SECTION
 309.1 FBC-14 MECHANICAL AND SHOW COMPLIANCE.
 5) BASED ON THE SCOPE OF WORK FOR THE PROPOSED PROJECT,
 THE $800.00 JOB VALUE LISTED ON THE PERMIT APPLICATIONS
 APPEARS EXTREMELY LOW. PLEASE PROVIDE AN ACCURATE VALUE
 FOR ALL WORK EITHER UNPERMITTED OR PROPSED THAT
 INCLUDES LABOR, MATERIALS, AND EQUIPMENT FOR ALL PHASES
 OF CONSTRUCTION INCLUDING BUILDING, MEP, SITE WORK,
 DESIGN FEES, OVEHEAD AND PROFIT- SEE SECTION 109.3 WPB
 AMENDMENTS TO THE FBC-10 BUILDING CODE. PLEASE NOTE
 FURTHER COMMENTS MAY FOLLOW AFTER MORE COMPREHENSIVE
 PLANS AND SPECIFCATIONS HAVE BEEN SUBMITTED FOR REVIEW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-03-11 Cont ID  
Sent By gjohnson Date 2016-03-11 Time 17:53 Rev Time 0.00
Received By gjohnson Date 2016-03-11 Time 17:53 Sent To  
Notes
2016-03-11 18:09:481ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. BOTH SETS OF PLANS SHALL BE SIGNED AND SEALED ONE IS
 NOT.
 PER FLORIDA ADMINISTRATIVE CODE 61G15-23.000
 2.SHT. A3.0 DETAIL NOTED AS EXISTING OFFICE FIRST FLOOR
 PLAN.
 (A) SHOULD BE DESIGNATED 2ND FLOOR.
 (B) ALL THE WORK ON THE SECOND FLOOR APPEARS TO BE NEW,
 THE EXISTING PLANS ON RECORD INDICATE IT AS AN OPEN
 LOFT. CLARIFY
 PER WPB AMEND TO FBC SEC. 107.2.1
 3. PROVIDE FULL SET OF PLANS WORK DONE ON SECOND FLOOR
 AND A WATER AND SANITARY RISER DIAGRAM FOR NEW
 BATHROOM.
 PER WPB AMEND TO FBC SEC.107.3.5.1.3(13)
 4. NEW BATHROOM ON SECOND FLOOR SHALL COMPLY WITH FBC
 ACC. SEC. 603 AND 604
 5. DUE TO INCREASE IN OCCUPANT LOAD A SERVICE SINK AND
 WATER FOUNTAIN ARE REQUIRED PER FBC ACC. TABLE 403.1
 6.THE GYMNASIUM AREA OCCUPANT LOAD CAN ONLY BE
 CALCULATED AT 50 GROSS IF EXERCISE EQUIPMENT IS IN THE
 ROOM, PROVIDE EQUIPMENT LAYOUT PLAN. IF THE GYMNASIUM
 DOES NOT HAVE EQUIPMENT IT IT SHALL BE CALCULATED AT 15
 GROSS, WHICH WILL INCREASE THE PLUMBING FIXTURE COUNT.\
 7. PROVIDE BREAK DOWN ON OCCUPANT LOAD FOR FIRST FLOOR
 AND SECOND FLOOR OFFICES.
 PER WPB AMEND TO FBC SEC. 107.2.1
 8. PROVIDE COST BREAK DOWN TO SHOW COMPLIANCE WITHFBC
 ACC. SEC. 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date   Cont ID  
Sent By vperez Date 2016-03-17 Time 06:47 Rev Time 0.00
Received By llouie Date 2016-02-17 Time 17:44 Sent To FIRE
Notes
2016-02-19 08:56:41CHANGE OF OCCUPANCY TO A GYM. GYMNASIUMS (INDOOR
 RECREATION) PERMITTED IN THE INDUSTRIAL (I) ZONING
 DISTRICT.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved