Plan Review Details - Permit 16020329
Plan Review Stops For Permit 16020329
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-19 Cont ID  
Sent By jgomez Date 2016-02-18 Time 18:54 Rev Time 0.00
Received By jgomez Date 2016-02-18 Time 18:54 Sent To  
Notes
2016-02-18 18:57:20 
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By jgomez Date 2016-02-10 Time 17:02 Rev Time 0.00
Received By jgomez Date 2016-02-10 Time 12:33 Sent To HIST
Notes
2016-02-10 17:03:34RESIDENTIAL (R3) STRUCTURAL REVISION, BUILDING REVIEW
 COMMENTS.
 CODE; FBC 5TH EDITION (2014).
  
 1- STRUCTURAL PLANS SUBMITTING ARE MISSING CONNECTORS
 SPECIFICATIONS. CLEARLY SPECIFY THE CONNECTORS AT ALL
 FRAMING MEMBERS. SPECIFY THE CONNECTORS AT BOTH ENDS OF
 COLUMNS, WALL STUDS, BEAMS AND FLOOR JOISTS. SEC.
 R501.2 AND SEC. R601.2 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 2- ENGINEER TO PROVIDE COMPLETE DETAILS/SPECIFICATIONS
 SHOWING COMPLIANCE WITH THE PROTECTION OF THE WOOD
 FRAMING MEMBERS SHOWN ON FRAMING PLANS AND DETAILS
 SUBMITTED. SEE SEC. R317 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014) AND PROVIDE SUCH SPECIFICATIONS.
  
 3- ENGINEER TO SPECIFY HOW MUCH EMBEDMENT IS REQUIRED
 FOR ALL BOLTS SPECIFIED ON DETAILS PROVIDED. SEC. R301
 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 4- FOOTING DETAIL B/MF1:
 A) SPECIFY THE MINIMUM FOOTING DEPTH BELOW GRADE AS
 REQUIRED BY SEC. R403.1.4 OF FBC-RESIDENTIAL, 5TH
 EDITION (2014) AND THE NUTTING ENGINEERS GEOTECHNICAL
 EXPLORATION REPORT SUBMITTED.
  
 B) SPECIFY THE MINIMUM CLEARANCE REQUIRED BETWEEN THE
 FINAL GRADE AND EXTERIOR WALL COVERING AS REQUIRED BY
 SEC. R318.7 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 5- PROVIDE COMPLETE WALL SECTION: PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE WALL SHEATHING
 ATTACHMENT, FINISH MATERIALS ON BOTH SIDES (INTERIOR
 AND EXTERIOR), INSULATION, ETC. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- PROVIDE THE SIGNED AND SEALED SHORING DRAWINGS AND
 STEEL SHOP DRAWINGS FOR CONNECTORS AS SPECIFIED BY THE
 ENGINEER ON PLANS SUBMITTED. SUBMITTALS TO BE
 REVIEWED/APPROVED BY THE ENGINEER OF RECORD PRIOR TO
 SUBMITTAL TO THIS OFFICE. SEC. 107.3.4.2 CITY
 AMENDMENTS.
  
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. NOTE: PROVIDE THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 ENGINEER TO LIST THE FLORIDA PRODUCT APPROVAL NEXT TO
 EACH SPECIFIED CONNECTOR.
  
 NOTE: PRODUCT APPROVALS FOR DOORS AND WINDOWS WILL BE
 REQUESTED WHEN-THE ARCHITECTURAL PLANS ARE SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2016-02-11 Cont ID  
Sent By fmittner Date 2016-02-11 Time 10:10 Rev Time 0.00
Received By fmittner Date 2016-02-11 Time 10:10 Sent To  
Notes
2016-02-11 10:11:01APPROVED FOR STRUCTURAL PURPOSES ONLY. ARCHITECTURAL
 PLANS TO FOLLOW AND WILL REQUIRE HSITORIC REVIEW.
 QUESTIONS, CONTACT FRIEDERIKE MITTNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-19 Cont ID  
Sent By jgomez Date 2016-02-19 Time 07:27 Rev Time 0.00
Received By jgomez Date 2016-02-17 Time 10:46 Sent To  
Notes
2016-02-18 10:46:50RESUB ROUTED TO JGOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-10 Cont ID  
Sent By jgomez Date 2016-02-10 Time 12:34 Rev Time 0.00
Received By jgomez Date 2016-02-09 Time 09:30 Sent To  
Notes
2016-02-10 09:31:27JGOMEZ'S DESK


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved