Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2017-07-26 Cont ID  
Sent By jgomez Date 2017-07-26 Time 17:07 Rev Time 0.00
Received By jgomez Date 2017-07-26 Time 15:18 Sent To  
Notes
2017-07-26 15:38:00BUILDING REVIEW APPROVED WITH PROVISO:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE.
 B) OUTSWING EXTERIOR DOORS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
 C) SINGLE HUNG WINDOWS THAT MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD. NOTE: ORIGINALLY
 NOA 13-0430.09 WAS SUBMITTED FOR SINGLE HUNG WINDOWS.
 THIS NOA WAS ALREADY APPROVED. IF USING ANOTHER PRODUCT
 APPROVAL THEN, REVISION FEES APPLY.
 D) CASEMENT EGRESS WINDOWS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS.
  
  
  
 CONSIDERATIONS FROM THE HISTORIC:
  
 05/18/2017 08:38AM.
 GOOD MORNING JULIO,
 ALTHOUGH THIS BUILDING IS CLASSIFIED AS NONCONTRIBUTING
 BECAUSE OF ALTERATIONS, IT WOULD BE CONTRIBUTING DUE TO
 ITS AGE IF SOMEONE RESTORED IT. THE EARLIER FRAME
 VERNACULAR HOUSES THAT PREDATE THE MIDCENTURY INFILL
 ARE PARTICULARLY VALUABLE IN THIS AREA. I JUST WANTED
 TO SHARE THAT DISTINCTION.
 DES
 DESIREE ESTABROOK, CNU-A
 HISTORIC PRESERVATION PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT
 PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
 P: 561.822.1428 F: 561.822.1460 E: [email protected]
 W: WPB.ORG
  
  
 05/18/2017 11;25AM
 JUST TO CLARIFY - THE CONTRIBUTING/NONCONTRIBUTING
 STATUS IS SOMETHING CHANGED BY ORDINANCE, AND THIS
 CHANGE WILL ONLY BE PICKED UP DURING OUR NEXT
 NEIGHBORHOOD SURVEY. SO FOR THE SAKE OF PERMIT REVIEW,
 IT WILL REMAIN NONCONTRIBUTING. WE JUST WOULD ENCOURAGE
 THE APPLICANT TO MAKE HISTORICALLY-APPROPRIATE CHANGES
 TO THE BUILDING RATHER THAN IT DEGRADING FURTHER. PER
 FRIEDERIKE'S COMMENTS ON THE PERMIT, THE APPLICANT HAD
 ISSUES OF CONSISTENCY WITH THE PLAN AND ELEVATIONS, AND
 THE USE OF VINYL HORIZONTAL SLIDER WINDOWS.
  
 DES
 DESIREE ESTABROOK, CNU-A
 HISTORIC PRESERVATION PLANNER
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2017-01-09 Cont ID  
Sent By jgomez Date 2017-01-06 Time 18:01 Rev Time 0.00
Received By jgomez Date 2017-01-05 Time 17:06 Sent To  
Notes
2017-01-05 15:41:49RESIDENTIAL (R3) ALTERATION, FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 NEW COMMENT:
 1- ENERGY CALCULATIONS SUBMITTED NOW REVISED THE ATTIC
 VENTILATION RATIO FROM 1/150 TO 1/300. ENGINEER OF
 RECORD TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW THE HOUSE COMPLIES WITH THE 1/300
 VENTILATION RATIO. SEE THE EXCEPTION ON SEC. R806.2 FOR
 THE MINIMUM CRITERIA REQUIRED TO COMPLY WITH THE 1/300
 VENTILATION RATIO AND PROVIDE DETAILS AND
 SPECIFICATIONS. SEC. R103.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014). NOTE: COORDINATE WITH THE PERSON
 PREPARING THE ENERGY CALCULATIONS.
  
 2- SHEET A-2/2:
 A) NORTH ELEVATION SHOWS TWO DIFFERENT KIND OF WINDOWS
 ON THE SECOND FLOOR. REVISE AS REQUIRED TO MATCH
 SPECIFICATIONS ON FLOOR PLAN ON SHEET A-1/3. SEC.
 107.2.1 CITY AMENDMENTS.
  
 B) WEST ELEVATION SHOWS TWO DIFFERENT TYPES OF SIDING:
 HARDIE BOARD SIDING AND CEDAR SIDING. REVISE AS
 REQUIRED. SPECIFY ONLY ONE TYPE OF SIDING. SEC. 107.2.1
 CITY AMENDMENTS.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) NEED THE OWNER'S OR OWNER'S LEGALLY AUTHORIZED AGENT
 CERTIFICATION AT THE BOTTOM OF THE FORM AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NO ADDRESSED AT ALL.
  
 B) ENERGY CALCULATIONS WERE PREPARED BY ANOTHER PERSON.
 PROVIDE THE NAME OF THE INDIVIDUAL WHO PREPARED THE
 ENERGY CALCULATIONS AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL. NEED THE NAME OF
 THE PERSON WHO PREPARED THE ENERGY CALCULATIONS NOT
 JUST THE SIGNATURE
  
 C) REVISE ORIENTATION OF DOORS ON PAGE 3 OF 4. SEC.
 R101. 5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. THERE ARE NO DOORS ON THE NORTH SIDE.
 SEE DRAWING A-2/2 AND REVISE AS REQUIRED.
  
 NEW COMMENTS:
 D) THE ATTIC VENTILATION RATIO WAS CHANGED ON PAGE 2 OF
 4. THE NEW VENT RATIO SPECIFIES 1/300 RATIO. SEC.
 R806.2 FBC-RESIDENTIAL REQUIRES 1/150 MIN. VENTILATION
 RATIO. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW THE HOUSE COMPLIES WITH THE 1/300
 VENTILATION RATIO. SEE EXCEPTION ON SEC. R806.2 FOR THE
 MINIMUM CRITERIA REQUIRED TO COMPLY WITH THE 1/300
 VENTILATION RATIO. NOTE: COORDINATE WITH PLANS
 SUBMITTED.
  
 E) ENERGY CALCULATIONS SUBMITTED SHOW GARAGE
 INFORMATION ON PAGE 3 OF 4. THERE IS NOT GARAGE IN THIS
 HOUSE. REVISE AS REQUIRED. SEC. R101. 5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED
 AT TIME OF INSPECTION WHEN THE ENERGY CALCULATIONS ARE
 NOT USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) OUTSWING EXTERIOR DOORS AS SHOWN ON PLANS.
 RESPONSE:
 REPEAT COMMENT. JELD -WEN DRAWINGS SUBMITTED NOW
 (NI006794D-R3) STILL DON'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET A-1/3.
 ALSO, THESE DOORS DON'T MATCH DOORS SHOWN ON PLANS AND
 ELEVATIONS. AND FINALLY DRAWINGS SUBMITTED DON'T HAVE A
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPONDS TO
 DRAWINGS SUBMITTED. SUBMIT FLORIDA OR MIAMI-DADE NOA
 PRODUCT APPROVAL FOR SINGLE OUTSWING EXTERIOR DOORS AS
 SHOWN ON PLANS (SOLID, WITHOUT GLAZING) THAT MEETS THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
  
 C) SINGLE HUNG WINDOWS.
 RESPONSE:
 REPEAT COMMENT. MI WINDOWS & DOORS DRAWINGS SUBMITTED
 NOW (08-02544) STILL DON'T MEET THE DESIGN PRESSURES
 CALCULATED BY THE ENGINEER OF RECORD ON SHEET A-1/3.
 ALSO, DRAWINGS SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL COVER PAGE THAT CORRESPONDS TO DRAWINGS
 SUBMITTED. SUBMIT FLORIDA OR MIAMI-DADE NOA PRODUCT
 APPROVAL FOR SINGLE HUNG WINDOWS THAT MEET THE DESIGN
 PRESSURES CALCULATED BY THE ENGINEER OF RECORD.
 NOTE: ORIGINALLY NOA 13-0430.09 WAS SUBMITTED FOR
 SINGLE HUNG WINDOWS. THIS NOA WAS ALREADY APPROVED.
 CLARIFY IF USING THE NOA THAT WAS ALREADY APPROVED OR
 IF NEW PRODUCT APPROVAL L WILL BE PROVIDED. DISCARD
 PRODUCT APPROVALS THAT WILL NOT BE USED.
  
 D) CASEMENT EGRESS WINDOWS AS SPECIFIED ON PLANS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-11-03 Cont ID  
Sent By jgomez Date 2016-11-03 Time 09:26 Rev Time 0.00
Received By jgomez Date 2016-11-02 Time 15:19 Sent To P
Notes
2016-11-02 16:15:46RESIDENTIAL (R3) ALTERATION, THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- ENERGY CALCULATIONS SUBMITTED:
 A) NEED THE OWNER/AGENT CERTIFICATION AT THE BOTTOM OF
 THE FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NO ADDRESSED.
  
 B) ENERGY CALCULATIONS WERE PREPARED BY ANOTHER PERSON.
 PROVIDE THE NAME OF THE INDIVIDUAL COMPLETING THE
 COMPLIANCE REPORT AS REQUIRED BY SEC. R405.4.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) ITEM #15 IS TAKING THE CROSS VENTILATION CREDIT.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE CROSS VENTILATION AS REQUIRED BY
 SEC. R405.7.4 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 D) DOORS ON PAGE 3 OF 4 SHOW (2) 6'X 8 INSULATED DOORS.
 WHERE ARE THESE DOORS LOCATED ON PLANS. REVISED AS
 REQUIRED TO MATCH PLANS. ALSO, SEE PLANS AND DOOR
 PRODUCT APPROVALS SUBMITTED. R101. 5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. INFORMATION WAS NOT
 CHANGED. WHERE ARE THESE DOORS LOCATED ON PLANS? .
 ALSO, SEE PLANS FOR CORRECT ORIENTATION OF EXTERIOR
 DOORS. REVISE AS REQUIRED TO MATCH PLANS AND PRODUCT
 APPROVALS SUBMITTED.
  
 E) WINDOWS INFORMATION ON PAGE 3 OF 4 SHOWS VINYL
 WINDOWS. THIS DOESN'T MATCH PRODUCT APPROVALS
 SUBMITTED. REVISE AS REQUIRED. SEE PRODUCT APPROVALS
 SUBMITTED. SEC. R101. 5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
 RESPONSE:
 NEW SINGLE HUNG FLORIDA PRODUCT APPROVAL FL14911.23 WAS
 SUBMITTED. NOTE: HISTORIC MAY NOT ALLOW VINYL WINDOWS.
 THIS WILL BE VERIFIED WITH HISTORIC. ON THE OTHER HAND,
 THERE WAS NOT PRODUCT APPROVAL SUBMITTED FOR THE NEW
 HORIZONTAL SLIDER WINDOWS SPECIFIED FOR THE SECOND
 FLOOR EGRESS WINDOWS. THEREFORE, UNABLE TO VERIFY IF
 THEY ARE GOING TO BE VINYL OR ALUMINUM.
  
 F) THE AIR BARRIER AND INSULATION INSPECTION COMPONENT
 CRITERIA CHECKLIST SUBMITTED WAS NOT COMPLETES. NEED TO
 BE COMPLETED. SEC. R405.4.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 G) PROVIDE COMPLETE EPL DISPLAY CARD AS REQUIRED BY
 SEC. R405.4.3 (1) FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 H) PROVIDE THE CORRECT CORRECT NAME OF THE BUILDER ON
 THE FRONT PAGE OF THE ENERGY CALCULATIONS. NOTE: ENERGY
 CALCULATIONS NAME "OWNER" AS THE BUILDER. "OWNER" IS
 NOT A BUILDER. SEC. R101.5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED
 WHEN THE ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE
 DEFAULT FACTOR FOR GLAZING.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. THERE ARE WINDOW
 MULLIONS ON DINING ROOM AREA AND STORAGE AREA. SEE
 PLANS.
  
 B) OUTSWING EXTERIOR DOORS AS SHOWN ON PLANS.
 RESPONSE:
 DRAWINGS SUBMITTED WITH FLORIDA PRODUCT APPROVAL
 FL13540-R3 DON'T MEET THE DESIGN PRESSURES CALCULATED
 BY THE ENGINEER OF RECORD ON SHEET A-1/3. NEED PRODUCT
 APPROVAL FOR DOORS THAT MEET THE CALCULATED DESIGN
 PRESSURES.
  
 C) SINGLE HUNG WINDOWS.
 RESPONSE:
 NEW SINGLE HUNG FLORIDA PRODUCT APPROVAL FL14911.23 WAS
 SUBMITTED. THIS PRODUCT APPROVAL DOESN'T MEET THE
 DESIGN PRESSURES CALCULATED BY THE ENGINEER OF RECORD
 ON SHEET A-1/3. NEED PRODUCT APPROVAL FOR WINDOWS THAT
 MEET THE CALCULATED DESIGN PRESSURES.
 NOTE: HISTORIC MAY NOT ALLOW VINYL WINDOWS. THIS WILL
 BE VERIFIED WITH HISTORIC.
 NOTE: ORIGINALLY NOA 13-0430.09 WAS SUBMITTED FOR
 SINGLE HUNG WINDOWS. THIS NOA WAS ALREADY APPROVED.
 CLARIFY IF USING THE NOA THAT WAS ALREADY APPROVED OR
 IF NEW PRODUCT APPROVAL L WILL BE PROVIDED. DISCARD
 PRODUCT APPROVALS THAT WILL NOT BE USED.
  
 D) HORIZONTAL SLIDER WINDOWS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
 NOTE: PLEASE MAKE SURE SUBMITTED PRODUCT APPROVAL MEETS
 THE DESIGN PRESSURES AS SPECIFIED BY THE ENGINEER OF
 RECORD ON THE REVISED DRAWINGS. ALSO: CONFIRM WITH
 HISTORIC IF HORIZONTAL SLIDER WINDOWS ARE ALLOWED.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-06-30 Cont ID  
Sent By jgomez Date 2016-06-29 Time 15:28 Rev Time 0.00
Received By jgomez Date 2016-06-29 Time 15:28 Sent To  
Notes
2016-06-29 15:29:01RESIDENTIAL (R3) ALTERATION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PLEASE COORDINATE INFORMATION ON THE ENERGY
 CALCULATIONS AND PLANS TO AVOID CONFLICTS OR DELAYS.
 RESPONSE:
 ENERGY CALCULATIONS SUBMITTED:
 A) NEED THE OWNER/AGENT CERTIFICATION AT THE BOTTOM OF
 THE FORM AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 B) THE ADDRESS OF THE HOUSE IS INCOMPLETE. 52ND STREET
 IS NOT AN ADDRESS. NEED COMPLETE AND CORRECT
 INFORMATION. ALSO, NEED TO PROVIDE THE JURISDICTION
 NUMBER. PALM BEACH COUNTY IS NOT THE JURISDICTION
 NUMBER. SEC. R101. 5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 C) REVISE ITEM #1. THIS HOUSE IS NOT NEW CONSTRUCTION.
 SEC. R101. 5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 D) THE CONDITIONED FLOOR AREA SPECIFIED ON ITEM # 6
 DOESN'T MATCH PLANS. SEC. R101. 5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 E) FLOOR TYPES ON ITEM #8 CALLS FOR CRAWL SPACE WITH
 R-19 INSULATION. PLANS DON'T SHOW ANY CRAWL SPACE.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101. 5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 F) ITEM #11 SPECIFIES DUCTS WITH R8 INSULATION. PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 PROVIDING THE R8 INSULATION. SEC. R103.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 G) THE CAPACITY OF THE COOLING SYSTEM LOOKS OVERSIZED
 FOR THE SIZE OF THIS HOUSE. REVISE AS REQUIRED. SEE
 MECHANICAL REVIEW COMMENTS. SEC. R101. 5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 H) ITEM #15 IS TAKING THE CROSS VENTILATION CREDIT.
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE CROSS VENTILATION AS REQUIRED BY
 SEC. R405.7.4 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 I) ATTIC INFORMATION ON PAGE 2 OF 4 SPECIFIES A VENT
 RATIO OF 1/300. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING WHY THE RATIO OF 1/300 IF THE
 REQUIRED RATIO IS 1/150. SEE SEC. R806.2 AND EXCEPTION
 #2 AND REVISE INFORMATION AS REQUIRED.
  
 J) CEILING INFORMATION ON PAGE 2 OF 4 SPECIFIES R-30
 INSULATION. PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW PROVIDING R-30 INSULATION ON THE MAIN FLOOR
 CEILING. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 K) DOORS ON PAGE 3 OF 4 SHOW (2) 6'X 8 INSULATED DOORS.
 WHERE ARE THESE DOORS LOCATED ON PLANS. REVISED AS
 REQUIRED TO MATCH PLANS. ALSO, SEE PLANS AND DOOR
 PRODUCT APPROVALS SUBMITTED. THEY ARE DOORS WITH
 GLAZING. DOORS WITH GLAZING NEEDS TO BE COUNTED IN THE
 GLAZING (WINDOWS) AREA. SEC. R101. 5.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 L) WINDOWS INFORMATION ON PAGE 3 OF 4 SHOWS VINYL
 WINDOWS. THIS DOESN'T MATCH PRODUCT APPROVALS
 SUBMITTED. REVISE AS REQUIRED. SEE PRODUCT APPROVALS
 SUBMITTED. SEC. R101. 5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 M) PROVIDE ALL THE INFORMATION REQUIRED BY SEC.
 R405.4.2 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 MISSING THE INSPECTION CHECKLIST.
  
 N) PROVIDE COMPLETE EPL DISPLAY CARD AS REQUIRED BY
 SEC. R405.4.3 (1) FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 O ) PROVIDE MANUFACTURER'S DOCUMENTATION SHOWING THE
 U-FACTOR AND SHGC FACTOR FOR DOORS AND WINDOWS
 SPECIFIED ON ITEM #7 OF THE COVER PAGE OF THE ENERGY
 CALCULATIONS SUBMITTED AS REQUIRED BY SEC. R1405.4.3
 (2) FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS U-FACTOR AND SHGC FACTOR
 SPECIFIED ON THE ENERGY CALCULATIONS WILL BE REQUIRED
 WHEN THE ENERGY CALCULATIONS ARE NOT USING THE SOFTWARE
 DEFAULT FACTOR FOR GLAZING.
  
 NEW COMMENT BASED ON THE ENERGY CALCULATIONS SUBMITTED:
 2- ENGINEER OF RECORD TO SPECIFY THE INSULATION BETWEEN
 THE MAIN FLOOR AND SECOND FLOOR AS SHOWN ON THE ENERGY
 CALCULATIONS. SEC. R103.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 ORIGINAL COMMENT:
 3- THE WIND SPEED SPECIFIED ON PLANS ON THE ENGINEERING
 NOTES BY THE TITLE BLOCK IS INCORRECT. CITY OF WEST
 PALM BEACH WIND SPEED IS 170 MPH NOT 160. REVISE AS
 REQUIRED. AND REVISE THE DOORS AND WINDOWS DESIGN
 PRESSURES ACCORDINGLY. SEC. R301.2.1 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
 RESPONSE:
 CODE DATA INFORMATION SUBMITTED ON SHEET A-1/3:
 A) ACCORDING TO SEC. R301.2.1.4 FBC-RESIDENTIAL, 5TH
 EDITION (2014) THIS BUILDING SEEMS TO BE IN EXPOSURE
 "C" NOT EXPOSURE "B". REVISE AS REQUIRED.
  
 B) REVISE THE WINDOWS AND DOORS DESIGNED PRESSURES THAT
 CORRESPOND TO EXPOSURE "C". AND, ENGINEER OF RECORD TO
 CLARIFY IN WRITING WHY THE DESIGN PRESSURES FOR THE
 WINDOWS ARE HIGHER THAN THE DOORS IF THE TRIBUTARY AREA
 OF THE WINDOW IS SMALLER. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 C) REVISE CODE NOTE #5.1. THE CURRENT CODE IS THE 2014
 NOT 2010. CHAPTER 553 F.S.
  
 NEW COMMENT:
 4- THE ADDRESS SHOWN ON RE-SUBMITTED DRAWINGS IS
 INCORRECT. THE CORRECT ADDRESS IS 424 52ND STREET NOT
 54TH STREET. REVISED AS REQUIRED. HAND MADE CHANGES ARE
 NOT ALLOWED. ORIGINAL DRAWINGS NEED TO BE REVISED.
 CHAPTER 471 F.S.
  
 ORIGINAL COMMENT:
 5- SCOPE OF WORK IS NOT CLEAR. PLANS TO CLEARLY SPECIFY
 WHAT'S NEW AND WHAT'S EXISTING. CLEARLY IDENTIFY EACH
 ROOM SHOWN ON PLANS. CLEARLY SPECIFY ALL EXTERIOR DOORS
 AND WINDOWS TO BE REPLACED. ALSO, SPECIFY SIZE AND TYPE
 OF EXISTING WINDOWS (SPECIALLY BEDROOM WINDOWS) AND
 TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
 RESPONSE:
 A) SOUTH ELEVATION ON SHEET A-2/2 IS MISSING THE EGRESS
 WINDOW SPECIFIED ON THE FLOOR PLAN FOR THE MASTER SUITE
 ON THE SECOND FLOOR FLOOR. REVISE AS REQUIRED TO MATCH.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 6- A) EXISTING INTERIOR STAIR SECTION SHOWN ON SHEET
 A-2 DOESN'T MATCH STAIRS SHOWN ON FLOOR PLANS. ALSO,
 TREAD SIZE DIMENSION IS NOT CLEAR. SEE SEC. R311.7.5.2
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) FOR PROPER WAY
 OF DIMENSIONING THE TREAD AND REVISE AS REQUIRED.
 RESPONSE:
 SECTION AT THE EXISTING INTERIOR STAIRS SHOWN ON SHEET
 A-1/3 DOESN'T MATCH PLANS. REVISE AS REQUIRED TO MATCH
 PLANS. SEC. 1074.2.1 CITY AMENDMENTS..
  
 ORIGINAL COMMENT:
 7- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES AS SPECIFIED ON PLANS.
 RESPONSE:
 NOT CLEAR IF DOING THE ROOF OR NOT.. ACCORDING TO
 ELEVATIONS ON SHEET A-2/2 IT LOOKS LIKE NEW SHINGLES
 ARE GOING TO BE INSTALLED. REVISE PLANS AS REQUIRED TO
 SHOW ACTUAL SCOPE OF WORK.
  
 B) METAL RIDGE VENTS AS SPECIFIED ON SHEET A-3.
 RESPONSE:
 NOT CLEAR IF DOING THE ROOF OR NOT.. ACCORDING TO
 INFORMATION ON SHEET A-2/2 AND A-3/3 IT LOOKS LIKE NEW
 SHINGLES ARE GOING TO BE INSTALLED. REVISE PLANS AS
 REQUIRED TO SHOW ACTUAL SCOPE OF WORK.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 DETAILS SHOWN ON PLANS. PROVIDE ONLY THE FLORIDA
 PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE
 SPECIFIED CONNECTOR OR ENGINEER OF RECORD TO LIST THE
 FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED
 CONNECTOR.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 E) "OUTSWING" EXTERIOR DOORS AS SHOWN ON PLANS. NOTE:
 NOA 09-0608.15 SUBMITTED IS FOR "INSWING" DOORS AND IS
 EXPIRED. NEED CORRECT AND CURRENT PRODUCT APPROVAL.
 RESPONSE:
 DRAWINGS SUBMITTED DON'T HAVE A FLORIDA PRODUCT
 APPROVAL OR MIAMI-DADE NOA NUMBER. NEED EITHER ONE.
 ALSO, DRAWING A011512 SUBMITTED IS NOT FOR SINGLE
 DOORS. PROVIDE COMPLETE PRODUCT APPROVAL FOR THE ENTRY
 DOOR AND SIDE DOOR AS SHOWN ON PLANS.
 NOTE: PLEASE MAKE SURE SUBMITTED PRODUCT APPROVAL MEETS
 THE DESIGN PRESSURES AS SPECIFIED BY THE ENGINEER OF
 RECORD ON THE REVISED DRAWINGS.
  
 NEW COMMENT:
 F) DRAWINGS SUBMITTED FOR THE SWING DOORS ARE FOR DOORS
 WITH NON-IMPACT GLAZING. IF SUBMITTING DOORS OR WINDOWS
 WITH NO IMPACT GLAZING, THEN HURRICANE SHUTTERS ARE
 REQUIRED. PROVIDE PRODUCT APPROVAL (2 COPIES) FOR THE
 HURRICANE SHUTTERS AND PROVIDE COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE OF INSTALLATION SCHEDULE.
  
 NEW COMMENT:
 G) DRAWINGS ON SHEET A-2/2 WERE REVISED. THEY SPECIFY
 HARDIE-BOARD SIDING. PROVIDE PRODUCT APPROVAL (2
 COPIES) FOR THE HARDIE BOARD SIDING.
  
 NEW COMMENT:
 H) NEW INFORMATION WAS SUBMITTED FOR THE SINGLE HUNG
 WINDOWS. DRAWINGS SUBMITTED DON'T HAVE A FLORIDA
 PRODUCT APPROVAL NUMBER OF MIAMI-DADE NOA NUMBER. NEED
 EITHER ONE. PROVIDE COMPLETE INFORMATION.
 NOTE: ORIGINALLY NOA 13-0430.09 WAS SUBMITTED FOR
 SINGLE HUNG WINDOWS. THIS NOA WAS ALREADY APPROVED.
 CLARIFY IF USING THE NEW SINGLE HUNG PRODUCT APPROVAL
 OR THE ONE THAT WAS SUBMITTED THE FIRST TIME.
 NOTE: PLEASE MAKE SURE SUBMITTED PRODUCT APPROVAL MEETS
 THE DESIGN PRESSURES AS SPECIFIED BY THE ENGINEER OF
 RECORD ON THE REVISED DRAWINGS.
  
 NEW COMMENT:
 I) SECOND FLOOR PLAN ON SHEET A-1/3 WAS REVISED. NEW
 HORIZONTAL SLIDER WINDOWS WERE SPECIFIED. PROVIDE
 PRODUCT APPROVAL (2 COPIES) FOR THE HORIZONTAL SLIDER
 WINDOWS.
 NOTE: PLEASE MAKE SURE SUBMITTED PRODUCT APPROVAL MEETS
 THE DESIGN PRESSURES AS SPECIFIED BY THE ENGINEER OF
 RECORD ON THE REVISED DRAWINGS.
  
 ORIGINAL COMMENT:
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-03-07 Cont ID  
Sent By jgomez Date 2016-03-07 Time 16:03 Rev Time 0.00
Received By jgomez Date 2016-03-07 Time 17:36 Sent To  
Notes
2016-03-07 16:03:42RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.4.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). PLEASE COORDINATE INFORMATION ON THE ENERGY
 CALCULATIONS AND PLANS TO AVOID CONFLICTS OR DELAYS.
  
 2- THE WIND SPEED SPECIFIED ON PLANS ON THE ENGINEERING
 NOTES BY THE TITLE BLOCK IS INCORRECT. CITY OF WEST
 PALM BEACH WIND SPEED IS 170 MPH NOT 160. REVISE AS
 REQUIRED. AND REVISE THE DOORS AND WINDOWS DESIGN
 PRESSURES ACCORDINGLY. SEC. R301.2.1 OF
 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 3- SCOPE OF WORK IS NOT CLEAR. PLANS TO CLEARLY SPECIFY
 WHAT'S NEW AND WHAT'S EXISTING. CLEARLY IDENTIFY EACH
 ROOM SHOWN ON PLANS. CLEARLY SPECIFY ALL EXTERIOR DOORS
 AND WINDOWS TO BE REPLACED. ALSO, SPECIFY SIZE AND TYPE
 OF EXISTING WINDOWS (SPECIALLY BEDROOM WINDOWS) AND
 TYPE AND SIZE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE
 WITH THE EGRESS REQUIREMENTS OF SEC. 704 OF
 FBC-EXISTING BUILDING, 5TH EDITION (2014).
  
 4- A) EXISTING INTERIOR STAIR SECTION SHOWN ON SHEET
 A-2 DOESN'T MATCH STAIRS SHOWN ON FLOOR PLANS. ALSO,
 TREAD SIZE DIMENSION IS NOT CLEAR. SEE SEC. R311.7.5.2
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) FOR PROPER WAY
 OF DIMENSIONING THE TREAD AND REVISE AS REQUIRED.
  
 B) SPECIFY FIREBLOCKING IN STAIRS AS REQUIRED BY SEC.
 R302.11 OF FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 5- STRUCTURAL NOTES ON SHEET A-2:
 A) THE LIVE LOADS SPECIFIED ARE INCORRECT. SEE TABLE
 R301.5 OF FBC-RESIDENTIAL, 5TH EDITION (2014) AND
 REVISE AS REQUIRED.
  
 B) UPDATE ALL THE SPECIFIED STANDARDS. SEE CHAPTER 45
 OF FBC-RESIDENTIAL, 5TH EDITION (2014) FOR CURRENT YEAR
 OF STANDARDS ADOPTED AND REVISE AS REQUIRED.
  
 C) REVISE THE WIND SPEED. SEE ITEM #2 ABOVE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES AS SPECIFIED ON PLANS.
  
 B) METAL RIDGE VENTS AS SPECIFIED ON SHEET A-3.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS. AND SPECIFY
 MULLION SIZE TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301 OF FBC-RESIDENTIAL, 5TH EDITION
 (2014).
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 DETAILS SHOWN ON PLANS.
  
 E) "OUTSWING" EXTERIOR DOORS AS SHOWN ON PLANS. NOTE:
 NOA 09-0608.15 SUBMITTED IS FOR "INSWING" DOORS AND IS
 EXPIRED. NEED CORRECT AND CURRENT PRODUCT APPROVAL.
  
 F) FIXED WINDOWS. ACCORDING TO MIAMI-DADE WEBSITE THE
 FILE STATUS OF NOA 10-1015.02 SUBMITTED IS IN THE
 PROCESS OF BEING REMOVED. NEED TO PROVIDE CURRENT
 PRODUCT APPROVAL.
  
 G) "OUTSWING" EXTERIOR DOORS AS SHOWN ON PLANS.
 DRAWINGS FOR FLORIDA PRODUCT APPROVAL FL14569-R5
 SUBMITTED ARE FOR "INSWING" DOORS. NEED OUTSWING DOORS.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-10-18 Cont ID  
Sent By vperez Date 2016-10-18 Time 10:12 Rev Time 0.00
Received By vperez Date 2016-10-18 Time 10:12 Sent To  
Notes
2016-10-18 10:13:38PROVISO: AT FINAL PROVIDE AS-BUILTS P[ER MARKUP ON
 PLANS
  
 V PEREZ
 *6717

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-11 Cont ID  
Sent By vperez Date 2016-07-11 Time 08:25 Rev Time 0.00
Received By vperez Date 2016-07-11 Time 08:25 Sent To  
Notes
2016-07-11 08:31:252ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS NOT ADDRESSED:
  
 2.CLARIFY IF ELECTRICAL SERVICE IS BEING UPGRADED.-
 PROVIDE ELECTRICAL PANEL LOAD CALCULATION. AIC RATING
 OF EQUIPMENT SERVICE. CONDUCTORS FEEDING INTERIOR PANEL
 SIZE. . CLARIFY NO GROUNDS TO AC, DRYER AND WATER
 HEATER?? LOADS
 3.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES-
 E3603.1
 4.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES-
 E3609.3
 6.2ND FLOOR, ADD WITHIN 3FT OF BASIN A RECEPTACLE
 BATHROOM OUTLET AT THE DOUBLE SINK LOCATION TO COMPLY
 WITH FBC RES E3901.6
 12.PROVIDE A PANEL SCHEDULE REFLECTING CIRCUIT
 IDENTIFICATION. FBC RES E3706.3
 13.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-03-03 Cont ID  
Sent By vperez Date 2016-03-03 Time 06:28 Rev Time 0.00
Received By vperez Date 2016-03-02 Time 13:30 Sent To  
Notes
2016-03-03 06:29:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE REFLECT NEC 2011 NOT NEC 2008 AS SHOWN.
 2.CLARIFY IF ELECTRICAL SERVICE IS BEING UPGRADED.
 3.PLEASE SHOW SIZE OF THE SERVICE CONDUCTORS. FBC RES-
 E3603.1
 4.SHOW A INTERSYSTEM BONDING TERMINATION PER FBC RES-
 E3609.3
 5.PROVIDE GFCI PROTECTION FOR RECEPTACLES IN BATHROOM
 AREA. SEE 1ST FLOOR-FBC RES- E3902.1
 6.2ND FLOOR, ADD WITHIN 3FT OF BASIN A RECEPTACLE
 BATHROOM OUTLET AT THE DOUBLE SINK LOCATION TO COMPLY
 WITH FBC RES E3901.6
 7.2ND FLOOR; ADD A RECEPTACLE FOR WALL SPACE IN
 BEDROOM, WALL BEHIND THE DOUBLE VANITY. FBC RES
 E3901.2.2
 8.SHOW EGRESS LIGHTING OUTLETS PER FBC RES E3903.3
 9.PROVIDE A RECEPTACLE OUTLET WITHIN 25FT OF A/C
 EQUIPMENT PER FBC RES E3901.12
 10.CLARIFY SPACE ON 1ST FLOOR SHOWN WITH A FAN AND NO
 RECEPTACLE OUTLETS. LABEL AREA TO COMPLY WITH WALL
 SPACING REQUIREMENTS. FBC RES E3901.2.2
 11.PROVIDE ON DRAWINGS THE LOCATION OF SERVICE
 EQUIPMENT AND PANEL BOARD. FBC 107.3.5
 12.PROVIDE A PANEL SCHEDULE REFLECTING CIRCUIT
 IDENTIFICATION. FBC RES E3706.3
 13.FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL
 FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE
 ANY QUESTIONS OR CONCERNS.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  

Review Stop HIST HISTORICAL
Rev No 5 Status P Date 2017-07-26 Cont ID  
Sent By fmittner Date 2017-07-26 Time 09:33 Rev Time 0.00
Received By fmittner Date 2017-07-26 Time 09:33 Sent To  
Notes
2017-07-25 13:25:30ROUTED TO FREDERIKE MITTNER

Review Stop HIST HISTORICAL
Rev No 4 Status F Date 2017-01-04 Cont ID  
Sent By fmittner Date 2017-01-04 Time 13:21 Rev Time 0.00
Received By fmittner Date 2016-12-22 Time 15:25 Sent To  
Notes
2017-01-04 13:21:55SMALL AND LARGE PLANS DO NOT MATCH. CASEMENT OR SINGLE
 HUNG ON SECOND FLOOR?

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2016-11-03 Cont ID  
Sent By fmittner Date 2016-11-01 Time 10:46 Rev Time 0.00
Received By fmittner Date 2016-11-01 Time 10:46 Sent To  
Notes
2016-11-01 10:46:35HARDIE BOARD REQUIRES HISTORIC PRESERVATION BOARD
 APPROVAL, VINYL WINDOWS NOT PERMITTED IN HISTORIC
 DISTRICTS WITHOUT BOARD APPROVAL. WINDOWS SHALL BE
 SINGLE HUNG OR CASEMENTS IN ALUMINUM OR WOOD NOT
 HORIZONTAL SLIDERS. QUESTIONS, CONTACT FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT (561)
 822-1457.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By fmittner Date 2016-07-08 Time 15:27 Rev Time 0.00
Received By fmittner Date 2016-07-08 Time 15:27 Sent To  
Notes
2016-06-29 15:23:07REVISED DRAWINGS SUBMITTED. JG.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-03-08 Cont ID  
Sent By fmittner Date 2016-03-08 Time 13:35 Rev Time 0.00
Received By fmittner Date 2016-03-08 Time 13:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2017-07-26 Cont ID  
Sent By jgomez Date 2017-07-26 Time 17:09 Rev Time 0.00
Received By jgomez Date 2017-07-24 Time 10:45 Sent To  
Notes
2017-07-25 10:45:30RESUB ROUTED TO FMITTNER VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 18:23 Rev Time 0.00
Received By gjohnson Date 2016-12-15 Time 09:29 Sent To  
Notes
2016-12-16 09:29:38R29

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-12-16 Cont ID  
Sent By lmarchan Date 2016-12-16 Time 09:24 Rev Time 0.00
Received By lmarchan Date 2016-10-11 Time 13:49 Sent To  
Notes
2016-10-11 13:49:38R33

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-13 Cont ID  
Sent By tklarge Date 2016-07-13 Time 09:08 Rev Time 0.00
Received By tklarge Date 2016-06-09 Time 11:10 Sent To P
Notes
2016-07-01 09:22:28R20
2016-06-30 11:12:1506/30/16 PLANS NEED REVIEWS BY DIFFERENT TRADES. SENT
 TO "LIBRARY" TILL THERE IS A BIN OPEN. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-08 Cont ID  
Sent By cpuell Date 2016-03-08 Time 13:51 Rev Time 0.00
Received By cpuell Date 2016-02-09 Time 16:05 Sent To  
Notes
2016-03-03 06:30:543/3 TO BIN R16
2016-02-09 16:08:57R16

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2017-07-26 Cont ID  
Sent By jgomez Date 2017-07-26 Time 17:07 Rev Time 0.00
Received By jgomez Date 2017-07-26 Time 17:07 Sent To  
Notes
2017-07-26 17:09:31PROVIDE A/C PLAN AND EQUIPMENT SIZING CALCULATIONS
 UNDER A SEPARATE PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2017-01-09 Cont ID  
Sent By jgomez Date 2017-01-09 Time 14:02 Rev Time 0.00
Received By jgomez Date 2017-01-09 Time 13:49 Sent To P
Notes
2017-01-09 13:57:43RESIDENTIAL (R3) ALTERATION, FOURTH MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
  
 NOTE:
 ENGINEER OF RECORD MAY BE CHARGED 4 TIMES THE PLAN
 REVIEW FEE AS REQUIRED BY SEC. 553.80(2)(B) FLORIDA
 STATUTE.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 2- DRAWING M-1 SUBMITTED:
 A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) ENGINEER OF RECORD TO CLARIFY HOW HE IS SPECIFYING
 THE CFM'S FOR EACH SUPPLY REGISTER IF THE SIZE OF THE
 EQUIPMENT IS NOT PROVIDED. EQUIPMENT MAY NOT BE
 ADEQUATE TO PROVIDE THE SPECIFIED CFM'S. COORDINATE
 CFM'S WITH THE EQUIPMENT SIZING CALCULATIONS. SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) FOOTPRINT OF FLOOR PLANS DON'T MATCH FOOTPRINT OF
 PLANS SHOWN ON SHEE A-1/3. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING THE CONSTRUCTION THE OF A/C
 SHAFT AS SHOWN ON PLANS. NOTE: NEED TO REVISE PLANS AND
 EXTERIOR ELEVATIONS TO SHOW THE NEW A/C SHAFT. SEC.
 R301.1 FBC-RESIDENTIAL, 5TH EDITION (2014).
  
 D) CLARIFY SIZE OF A/C GRILLES SPECIFIED ON PLANS. WHY
 THE GRILLES ARE SPECIFIED WITH 3 NUMBERS. WHAT ARE
 THEY?. PROVIDE TYPICAL DETAIL SHOWING SPECIFIED SIZES.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-11-03 Cont ID  
Sent By jgomez Date 2016-11-03 Time 13:09 Rev Time 0.00
Received By jgomez Date 2016-11-03 Time 13:08 Sent To  
Notes
2016-11-03 11:45:13RESIDENTIAL (R3) ALTERATION, THIRD MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 CONTRACTOR'S RESPONSE LETTER STATES THAT MECHANICAL
 CONTRACTOR WILL SUBMIT LOAD CALCULATIONS INFORMATION
 UNDER A SEPARATE PERMIT. IF MECHANICAL CONTRACTOR IS
 GOING TO APPLY FOR A SEPARATE PERMIT, THEN MECHANICAL
 CONTRACTOR TO PROVIDE COMPLETE INFORMATION INCLUDING
 EQUIPMENT SIZING CALCULATIONS AND A/C PLANS UNDER A
 SEPARATE PERMIT. REMOVE A/C PLANS FROM THIS SUBMITTAL.
  
  
 NOTE:
  
 COMMENTS BELOW FROM PREVIOUS CHECKLIST WERE NOT
 REVIEWED ON REVISED PLANS SUBMITTED BECAUSE CONTRACTOR
 STATED THAT MECHANICAL CONTRACTOR WILL APPLY FOR THE
 SEPARATE PERMIT. PLEASE REMOVE THE A/C PLANS.
 MECHANICAL CONTRACTOR TO SUBMIT PLANS ALONG WITH THE
 EQUIPMENT SIZING CALCULATIONS AT TIME OF MECHANICAL
 PERMIT APPLICATION.
  
  
 2- DRAWING M-1 SUBMITTED:
 ORIGINAL COMMENT:
 A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE:
 REVISED PLAN SUBMITTED DOESN'T SHOW THE DUCT SIZES AND
 LOCATION. NEED TO SHOW ALL DUCTWORK.
 NOTE: BALANCE RETURN AIR REQUIREMENTS WILL BE REVIEWED
 ONCE THE DUCTWORK IS PROVIDED.
  
 ORIGINAL COMMENT:
 C) LABEL EACH FLOOR. FIRST AND SECOND FLOOR. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE;
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-06-30 Cont ID  
Sent By jgomez Date 2016-06-30 Time 10:50 Rev Time 0.00
Received By jgomez Date 2016-06-30 Time 10:50 Sent To  
Notes
2016-06-30 10:51:30RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
  
 NOTE:
 CONTRACTOR MAY SUBMIT COMPLETE HVAC INFORMATION UNDER A
 SEPARATE PERMIT. PLEASE ADVICE IF RE-SUBMITTING ALL THE
 REQUIRED INFORMATION NOW OR IF ALL THE INFORMATION WILL
 BE SUBMITTED BY THE MECHANICAL CONTRACTOR UNDER A
 SEPARATE PERMIT.
  
  
  
 ORIGINAL COMMENT:
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 2- DRAWING M-1 SUBMITTED:
 ORIGINAL COMMENT:
 A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE:
 REVISED PLAN SUBMITTED DOESN'T SHOW THE DUCT SIZES AND
 LOCATION. NEED TO SHOW ALL DUCTWORK.
 NOTE: BALANCE RETURN AIR REQUIREMENTS WILL BE REVIEWED
 ONCE THE DUCTWORK IS PROVIDED.
  
 ORIGINAL COMMENT:
 C) LABEL EACH FLOOR. FIRST AND SECOND FLOOR. SEC.
 107.2.1 CITY AMENDMENTS.
 RESPONSE;
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By jgomez Date 2016-03-08 Time 09:33 Rev Time 0.00
Received By jgomez Date 2016-03-08 Time 09:31 Sent To  
Notes
2016-03-08 09:54:23RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. SPECIFY
 MANUFACTURER AND MODEL NUMBER AS REQUIRED BY SEC.
 R403.6.1 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 2- DRAWING M-1 SUBMITTED:
 A) LIST THE EQUIPMENT SPECIFIED ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.3.5.3(10) CITY AMENDMENTS.
  
 B) SPECIFY THE CFM'S FOR EACH GRILL SHOWN ON PLAN. SEC.
 107.2.1 CITY AMENDMENTS.
  
 C) LABEL EACH FLOOR. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- CONDENSING UNIT ANCHORING SPECIFICATIONS SHOWN ON
 THE A/C PLAN SUBMITTED: ENGINEER TO PROVIDE COMPLETE
 DETAIL AND SPECIFICATIONS SHOWING HOW THE CONDENSING
 UNIT IS ATTACHED TO THE CONCRETE SLAB THE WAY IS
 SPECIFIED. ARE THE TAPCONS ALONE HOLDING THE UNIT
 WITHOUT ANY REINFORCEMENT?. CLEARLY SPECIFY LOCATION
 AND NUMBER OF TAPCONS. PROVIDE ENGINEERING ANALYSIS
 SHOWING HOW THE UNIT WILL RESIST THE WIND LOADS THE WAY
 IT WAS SPECIFIED. SEC. 107.2.1.3 CITY AMENDMENTS.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2017-01-12 Cont ID  
Sent By gjohnson Date 2017-01-12 Time 18:23 Rev Time 0.00
Received By gjohnson Date 2017-01-12 Time 18:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-11-03 Cont ID  
Sent By gjohnson Date 2016-11-03 Time 15:07 Rev Time 0.00
Received By gjohnson Date 2016-11-03 Time 15:07 Sent To  
Notes
2016-11-03 15:08:323RD REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS: 3RD REQUEST
  
 1. DESCRIPTION ON PLUMBING PERMIT INDICATES REPIPING OF
 SANITARY AND WATER PLEASE PROVIDE PLUMBING RISER
 DIAGRAM FOR ALL PIPING BEING REPLACED. PER WPB AMEND.
 TO FBC 107.3.5.3(11)
  
2016-11-03 11:43:42NEW DRAWINGS SUBMITTED. OLD DRAWINGS WERE NOT
 RESUBMITTED. JG.

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-11-03 Cont ID  
Sent By tklarge Date 2016-07-13 Time 09:08 Rev Time 0.00
Received By gjohnson Date 2016-07-13 Time 09:08 Sent To  
Notes
2016-06-16 12:34:332ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. DESCRIPTION ON PLUMBING PERMIT INDICATES REPIPING OF
 SANITARY AND WATER PLEASE PROVIDE PLUMBING RISER
 DIAGRAM FOR ALL PIPING BEING REPLACED. PER WPB AMEND.
 TO FBC 107.3.5.3(11)
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-24 Cont ID  
Sent By gjohnson Date 2016-02-24 Time 08:22 Rev Time 0.00
Received By gjohnson Date 2016-02-24 Time 08:18 Sent To  
Notes
2016-02-24 08:21:25 
 1ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
 1. PLEASE PROVIDE A CLEAR AND PRECISE SCOPE OF PLUMBING
 WORK TO BE DONE.
 PER WPB AMEND. TO FBC SEC. 107.2.1

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2016-11-03 Cont ID  
Sent By jgomez Date 2016-11-03 Time 09:10 Rev Time 0.00
Received By jgomez Date 2016-11-03 Time 09:10 Sent To  
Notes
2016-11-03 09:11:30CONTRACTOR AND DRAWINGS SUBMITTED STATED THAT THERE IS
 NO ROOFING ON THIS PERMIT. NOA 15-1102.03 SUBMITTED WAS
 DISCARDED. JG.
  
 NOTE: THERE IS AN EXPIRED ROOFING PERMIT ON THIS HOUSE.
 ROOFING PERMIT #15070234.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2016-06-30 Cont ID  
Sent By jgomez Date 2016-06-30 Time 11:02 Rev Time 0.00
Received By jgomez Date 2016-06-30 Time 11:02 Sent To  
Notes
2016-06-30 11:04:25ORIGINAL COMMENT:
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES AS SPECIFIED ON PLANS.
 RESPONSE:
 NOT CLEAR IF DOING THE ROOF OR NOT.. ACCORDING TO
 ELEVATIONS ON SHEET A-2/2 IT LOOKS LIKE NEW SHINGLES
 ARE GOING TO BE INSTALLED. REVISE PLANS AS REQUIRED TO
 SHOW ACTUAL SCOPE OF WORK.
  
 ORIGINAL COMMENT:
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ****PLEASE REMOVE ANY REVISED DRAWING. DON'T STAPLE OLD
 DRAWINGS. SUBMIT OLD DRAWINGS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-03-08 Cont ID  
Sent By jgomez Date 2016-03-08 Time 09:30 Rev Time 0.00
Received By jgomez Date 2016-03-08 Time 09:30 Sent To  
Notes
2016-03-08 09:30:361- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF SHINGLES AS SPECIFIED ON PLANS.
  
 B) METAL RIDGE VENTS AS SPECIFIED ON SHEET A-3.

Review Stop Z ZONING
Rev No 3 Status P Date 2016-11-01 Cont ID  
Sent By fmittner Date 2016-11-01 Time 10:46 Rev Time 0.00
Received By fmittner Date 2016-11-01 Time 10:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-08 Cont ID  
Sent By fmittner Date 2016-07-08 Time 15:27 Rev Time 0.00
Received By fmittner Date 2016-07-08 Time 15:27 Sent To  
Notes
2016-06-30 11:12:47NEW DRAWINGS SUBMITTED. JG.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-03-08 Cont ID  
Sent By fmittner Date 2016-03-08 Time 13:36 Rev Time 0.00
Received By fmittner Date 2016-03-08 Time 13:36 Sent To  
Notes
***NONE***