Plan Review Details - Permit 16020305
Plan Review Stops For Permit 16020305
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-17 Cont ID  
Sent By mvaldes Date 2016-02-17 Time 09:06 Rev Time 0.00
Received By mvaldes Date 2016-02-17 Time 09:06 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-10 Cont ID  
Sent By mvaldes Date 2016-02-10 Time 12:35 Rev Time 0.00
Received By mvaldes Date 2016-02-10 Time 12:34 Sent To  
Notes
2016-02-10 12:38:23FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 - NEC 230.2 NUMBER OF SERVICES. A BUILDING OR OTHER
 STRUCTURE
 SERVED SHALL BE SUPPLIED BY ONLY ONE SERVICE.PROPERLY
 IDENTIFY EACH SERVICE DISCONNECT. ( LABEL )
  
 - PLEASE TAKE A LOOK AT FPL APROVED RISER DIAGRAMS.
  
 - NEC 230.72 ALL DISCONNECTS MUST BE GROUPED.
  
 - NEC 250.94 PROVIDE INTERSYSTEM BONDING
  
 - NEC 215.5 PROVIDE A SITE PLAN SHOWING LOCATION OF
 EQUIPMENT RELATIVE TO EACH OTHER, PLEASE SHOW GROUNDING
 WIRE SIZE AND EXISTING LOAD CALCS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-17 Cont ID  
Sent By mvaldes Date 2016-02-17 Time 09:06 Rev Time 0.00
Received By mvaldes Date 2016-02-17 Time 09:06 Sent To  
Notes
2016-02-12 11:47:04RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-11 Cont ID  
Sent By cpuell Date 2016-02-11 Time 07:59 Rev Time 0.00
Received By cpuell Date 2016-02-09 Time 11:25 Sent To  
Notes
2016-02-09 11:25:24ELEC -$5000