Plan Review Details - Permit 16020274
Plan Review Stops For Permit 16020274
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-09 Cont ID  
Sent By cthroop Date 2016-03-09 Time 13:29 Rev Time 0.00
Received By cthroop Date 2016-03-09 Time 13:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-29 Cont ID  
Sent By cthroop Date 2016-02-29 Time 15:45 Rev Time 0.00
Received By cthroop Date 2016-02-29 Time 15:44 Sent To  
Notes
2016-02-29 15:48:461ST REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 1. FORM 100, SHEET 1 - CHANGE CODE REFERENCE TO 2014
 FBC
 2. PRODUCT APPROVALS ON SUBMITTAL AFFIDAVIT NOT
 PROVIDED. CHANGE SCHEDULE TO REFLECT MIAMI DADE NOA'S
 SUBMITTED
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-09 Cont ID  
Sent By mvaldes Date 2016-03-09 Time 13:18 Rev Time 0.00
Received By mvaldes Date 2016-03-09 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-29 Cont ID  
Sent By mvaldes Date 2016-02-29 Time 15:03 Rev Time 0.00
Received By mvaldes Date 2016-02-29 Time 15:03 Sent To  
Notes
2016-02-29 15:17:381ST REVIEW 2014 5TH FBC ED. NEC 2011/RESIDENTIAL
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
 - ON DOUBLE SINKS IN BATHROOMS A GFCI MUST BE WITHIN 3
 FT OF BASIN ( EITHER 1 ON EACH SIDE OR 1 IN THE MIDDLE.
 ) NEC 210.52 D
  
 - RECESSED LIGHTS SHALL BE 75 % HIGH EFFICIENT AS WELL
 AS IC RATED AND SEALED TO NOT COMPROMISE BUILDING
 THERMAL ENVELOPE. ( 2 CFM ) FBC- ER 404.1.1 & 402.4.4
  
 - PLEASE CLARIFY WHY ON THE FLOOR PLANS 2 50 AMP SUB
 PANELS ARE SHOWN AND RISER DIAGRAM REFLECTS 1.
 FURTHERMORE INCLUDE EXISTING SERVICE EQUIPMENT & PANEL
 BOARD LOCATIONS RELATIVE
 TO EACH OTHER ON ELECTRICAL FLOOR PLAN. WBA 107
  
 - WHERE FANS ARE TO BE INSTALLED 70 POUND FAN RATED BOX
 SHALL BE MOUNTED AND PROPOERLY SECURED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-09 Cont ID  
Sent By cthroop Date 2016-03-09 Time 13:29 Rev Time 0.00
Received By cthroop Date 2016-03-09 Time 13:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-29 Cont ID  
Sent By cthroop Date 2016-02-29 Time 15:44 Rev Time 0.00
Received By cthroop Date 2016-02-08 Time 09:26 Sent To  
Notes
2016-02-09 09:27:15R13

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-18 Cont ID  
Sent By gjohnson Date 2016-02-18 Time 15:09 Rev Time 0.00
Received By gjohnson Date 2016-02-18 Time 15:09 Sent To  
Notes
***NONE***