Plan Review Stops For Permit 16020255 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2016-02-09 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-02-09 |
Time |
10:47 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-09 |
Time |
10:02 |
Sent To |
I |
|
Notes |
2016-02-09 10:51:07 | I SPOKE W/THE EC TO EXPLAIN THAT ALL NEC 404.2(C) | | REQUIRES THAT HE HAVE A NEUTRAL AT EVERY SWITCH OUTLET | | WHEN USING MC OR SIMILAR CABLE. FURTHERMORE I REMINDED | | HIM OF THE WPB 107.2.1 AMENDMENT. PLANS WILL BE SIGNED | | AT TIME OF PICK UP, |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-02-09 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-02-09 |
Time |
10:52 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-02-08 |
Time |
09:24 |
Sent To |
|
|
Notes |
2016-02-09 10:53:04 | 2/9/16 PASSED ELECTRICAL REVIEW AS NOTED. EC NOTIFIED | | VIA EMAIL. SENT FILE TO SMALL READY BIN "S". MA | 2016-02-09 09:24:54 | REVISION ROUTED TO MALBARRAN |
|
|
|