Plan Review Details - Permit 16020244
Plan Review Stops For Permit 16020244
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-01 Cont ID  
Sent By   Date 2016-03-01 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2016-03-01 Time 05:31 Sent To  
Notes
2016-03-01 06:37:09BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020244
 ADD: 6101 S. DIXIE HWY.
 CONT: GAST CONSTRUCTION GROUP
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 01/ 2016
  
 ACTION: BUILDING PROVISO
  
 1) SHEET LIFE SAFETY & A-1: FRONT ENTRY HAS A 4 INCH
 STEP DOWN, SIGNAGE IS REQUIRED INDICATING WHERE THE
 ACCESSIBLE ENTRANCE IS LOCATED.
  
 2014 FBC-ACCESSIBILITY CODE SECTION 216.4.3 DIRECTIONAL
 SIGNS.
 SIGNS REQUIRED BY SECTION 1003.2.13.6 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION) OR SECTION
 1007.7 OF THE INTERNATIONAL BUILDING CODE (2003
 EDITION) (INCORPORATED BY REFERENCE, SEE ?REFERENCED
 STANDARDS? IN CHAPTER 1) TO PROVIDE DIRECTIONS TO
 ACCESSIBLE MEANS OF EGRESS SHALL COMPLY WITH 703.5.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By jwitmer Date 2016-02-17 Time 07:42 Rev Time 0.00
Received By jwitmer Date 2016-02-16 Time 14:16 Sent To  
Notes
2016-02-17 07:42:43BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020244
 ADD: 6101 S. DIXIE HWY.
 CONT: GAST CONSTRUCTION GROUP
 TEL: 561-281-1001
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 17/ 2016
 ACTION: DENIED
  
 1) SHEET A-1:
  
 1A) ROOM PM-3 SHOWS A NEW DOOR # 3. JUST TO THE LEFT OF
 THE DOOR THERE IS A OFFSET IN THE WALL IN THE REQUIRED
 18 INCHES MANEUVERING CLEARANCES. PLEASE PROVIDE
 COMPLIANCE WITH THE:
 2014 FBC-ACCESSIBILITY CODE SECTION 404.2.4.3 RECESSED
 DOORS AND GATES.
 MANEUVERING CLEARANCES FOR FORWARD APPROACH SHALL BE
 PROVIDED WHEN ANY OBSTRUCTION WITHIN 18 INCHES (455 MM)
 OF THE LATCH SIDE OF A DOORWAY PROJECTS MORE THAN 8
 INCHES (205 MM) BEYOND THE FACE OF THE DOOR, MEASURED
 PERPENDICULAR TO THE FACE OF THE DOOR OR GATE.
  
 1B) BOTH THE FRONT AND EXIT DO NOT SHOW IF THEY ARE
 LEVEL WITH THE EXTERIOR OF THE BUILDING, A ACCESSIBLE
 ENTRY AND OR EXIT TO THE BUILDING.
 2014 FBC-ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES
 IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 1C) DOOR # 1 PLEASE REVIEW THE FLOOR PLAN TO ALLEN?S
 OFFICE AND SHOW THE ACCESSIBLE ENTRY. THE COLUMN
 LOCATION WILL CAUSE A WHEEL CHAIR BOUND INDIVIDUAL TO
 TRAVEL ALL THE WAY AROUND THE CONFERENCE ROOM. SEE 2014
 FBC-ACCESSIBILITY FIGURE 404.2.4.1(B).
  
 2) SHEET A-2:
  
 2A) PLEASE REVIEW DETAIL 3 THE PLANS APPEAR TO HAVE A
 SINK IN A BASE CABINET AT 3'-0" TALL. THE 2014
 FBC-ACCESSIBILITY CODE 606.3 HEIGHT. LAVATORIES AND
 SINKS SHALL BE INSTALLED WITH THE FRONT OF THE HIGHER
 OF THE RIM OR COUNTER SURFACE 34 INCHES (865 MM)
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 2B) PLEASE REVIEW DETAIL 4 THE PLANS INDICATE A
 MICROWAVE SHELF AT A HEIGHT OF 54 INCHES ABOVE THE
 FLOOR. THE 2014 FBC-ACCESSIBILITY CODE FOR BOTH FORWARD
 AND SIDE OBSTRUCTED REACH ARE A MAXIMUM OF 48 INCHES.
 FIGURE 308.2.2 & 308.3.2. ALSO REVIEW OPERABLE PARTS
 SECTION 309. 1 - 4.
  
 3) THE ARCHITECTS SIGNATURE IS A STAMP SIGNATURE NOT AN
 ORIGINAL. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-04-22 Cont ID  
Sent By vperez Date 2016-04-22 Time 14:29 Rev Time 0.00
Received By vperez Date 2016-04-22 Time 14:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-02 Cont ID  
Sent By vperez Date 2016-03-02 Time 14:09 Rev Time 0.00
Received By vperez Date 2016-03-02 Time 14:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By vperez Date 2016-02-18 Time 13:40 Rev Time 0.00
Received By vperez Date 2016-02-18 Time 12:35 Sent To  
Notes
2016-02-18 13:41:14INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS FOR ALL LOW VOLTAGE SYSTEMS TO INCLUDE PHONE
 AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 FBC 107.3.5
 2. PLEASE LABEL THE KITCHEN RECEPTACLE OUTLET WITHIN
 6FT OF SINK TO BE GFCI PROTECTED. NEC 210.8B5
 3. SHOW THE SIZE OF THE FEEDER CONDUCTORS TO BE AS PER
 NEC 310.15B16 ?3/0 FOR 200AMP SERVICE?
 4. CORRECT PANEL LOAD CENTER DESIGNATION TO REFLECT NEW
 NOT EXISTING, SHOW THE AIC RATING OF PANEL BOARD.FBC
 107.3.5
 5. PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-23 Cont ID  
Sent By rlindow Date 2016-02-23 Time   Rev Time 0.00
Received By rlindow Date 2016-02-23 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-11 Cont ID  
Sent By rlindow Date 2016-02-11 Time   Rev Time 0.00
Received By rlindow Date 2016-02-11 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-04-22 Cont ID  
Sent By vperez Date 2016-04-22 Time 14:29 Rev Time 0.00
Received By vperez Date 2016-04-22 Time 14:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-03 Cont ID  
Sent By hmoser Date 2016-03-03 Time 13:06 Rev Time 0.00
Received By hmoser Date 2016-03-03 Time 10:20 Sent To  
Notes
2016-03-03 10:20:35RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-02 Cont ID  
Sent By vperez Date 2016-03-02 Time 14:09 Rev Time 0.00
Received By vperez Date 2016-03-02 Time 14:09 Sent To  
Notes
2016-03-02 14:09:483/2 TO CAROLINE
2016-02-19 14:45:47B01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-18 Cont ID  
Sent By gjohnson Date 2016-02-18 Time 15:47 Rev Time 0.00
Received By gjohnson Date 2016-02-08 Time 09:30 Sent To  
Notes
2016-02-18 13:41:532/18 ELECT TO CAROLINE/LAURA DESK
2016-02-09 09:31:17B01

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-03-03 Cont ID  
Sent By hmoser Date 2016-03-03 Time 13:05 Rev Time 0.00
Received By hmoser Date 2016-03-03 Time 13:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-29 Cont ID  
Sent By ccole Date 2016-02-29 Time 08:06 Rev Time 0.00
Received By ccole Date 2016-02-29 Time 08:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By ccole Date 2016-02-12 Time 16:50 Rev Time 0.00
Received By ccole Date 2016-02-12 Time 16:50 Sent To  
Notes
2016-02-12 16:54:251ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020244
 2/12/16
  
 1) THE GRILLS IN THE ALLEN ROOM, & PM I & 2 ROOMS
 APPEAR TO BE UNDERSIZED PER SECTION 601.5 EXCEPTION #2
 WHICH REQUIRES 50 SQ. IN. TO 100 CFM OF SUPPLY AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-03-03 Cont ID  
Sent By tklarge Date 2016-03-03 Time 11:42 Rev Time 0.00
Received By tklarge Date 2016-03-03 Time 11:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-27 Cont ID  
Sent By tklarge Date 2016-02-27 Time 11:47 Rev Time 0.00
Received By tklarge Date 2016-02-27 Time 11:31 Sent To  
Notes
2016-02-27 11:47:231) THE LEADING EDGE OF THE HIGH SIDE OF THE DRINKING
 FOUNTAIN IS ABOVE 27 INCHES AND SHALL PROTRUDE INTO THE
 ACCESSIBLE ROUTE NO MORE THAN 4 INCHES PER THE 2014 FAC
 SEC.307.2. AN OPTIONAL SKIRT ATTTACHED TO THE HIGH SIDE
 DRINKING FOUNTAIN WILL PROBABLY BRING THE LEADING EDGE
 BELOW 27 INCHES AND COMPLY WITH SEC. 307.2.
 2) HOT WATER IS REQUIRED TO THE NEW SINK PER THE 2014
 FPC SEC. 607.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By gjohnson Date 2016-02-18 Time 15:34 Rev Time 0.00
Received By gjohnson Date 2016-02-18 Time 15:34 Sent To  
Notes
2016-02-18 15:46:561ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 1.SHOW CLEAR FLOOR SPACE FOR BRAKE ROOM SINK TO COMPLY
 WITH . FBC ACC. SEC. 606.
 2. SNT. A2 DETAIL 3 SHOWS HIGHT OF COUNTER AT 36IN IT
 SHALL BE 34IN MAX PER FBC ACC. SEC 606.3
 3. PROVIDE WATER RISER DIAGRAM FOR NEW SINK. PER WPB
 AMEND. TO FBC SEC. 107.3.5.1.3
  