Plan Review Details - Permit 16020145
Plan Review Stops For Permit 16020145
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-01 Cont ID  
Sent By jwitmer Date 2016-03-01 Time 14:55 Rev Time 0.00
Received By jwitmer Date 2016-03-01 Time 14:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By jwitmer Date 2016-02-10 Time 07:14 Rev Time  
Received By jwitmer Date 2016-02-10 Time 06:31 Sent To  
Notes
2016-02-10 07:07:08BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16020145
 ADD: 2475 MERCER AVE. SUITE # 206
 CONT: CROSSROADS CONSTRUCTION
 TEL: 561-346-6160
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB. 10/2016
 ACTION: DENIED
  
 1) SHEET A-1 THE KITCHEN SHOWS A 6 INCH CHANGE IN
 ELEVATION IN THE FLOOR LEVEL. WAS THIS AT A TENANT
 DEMISSING WALL LOCATION WHERE THIS CHANGE IN ELEVATION
 OCCURS ALONG THE WHOLE WALL? HOW WILL THE CHANGE IN
 GRADE BE MADE ACCESSIBLE, VERTICAL ACCESSIBILITY, 2014
 FBC-ACCESSIBILITY 201.1.1.
  
 2) SHEET A-1 THE KITCHEN SHOWS THE 30X48 INCH PARALELL
 APPROACH, BUT THE SINK IS NOT CENTERED ON THE 24 INCHES
 FROM THE WALL. SINKS ARE SUPPOSE TO BE CENTERED FOR THE
 USER WITH THE SIDE APPROACH. 2014 FBC-ACCESSIBILITY
 305.5.POSITION.
  
 3) SHEET A-1 THE DOOR INTO THE ACCESSIBLE RESTROOM
 APPEARS TO HAVE LESS THAN 18 INCHES ON THE LATCH SIDE
 OF THE DOOR, SHOW COMPLIANCE WITH:
 2014 FBC-ACCESSIBILITY CODE 404.2.4 AND FIGURE
 404.2.4.1(A).
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-16 Cont ID  
Sent By rlecky Date 2016-02-16 Time 11:36 Rev Time 0.00
Received By rlecky Date 2016-02-16 Time 11:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By pleduc Date 2016-03-03 Time   Rev Time 0.00
Received By pleduc Date 2016-03-03 Time 12:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-09 Cont ID  
Sent By pleduc Date 2016-02-09 Time   Rev Time 0.00
Received By pleduc Date 2016-02-09 Time 12:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 09:34 Rev Time 0.00
Received By ccole Date 2016-02-25 Time 08:52 Sent To  
Notes
2016-02-26 08:52:47B10

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-26 Cont ID  
Sent By lmarchan Date 2016-02-25 Time 08:51 Rev Time 0.00
Received By lmarchan Date 2016-02-03 Time 09:59 Sent To  
Notes
2016-02-04 09:59:17B09

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 09:31 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 09:31 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-25 Cont ID  
Sent By ccole Date 2016-02-25 Time 15:59 Rev Time 0.00
Received By ccole Date 2016-02-11 Time 12:35 Sent To  
Notes
2016-02-11 12:39:361ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020145
 2/11/16
  
 1) THE 10" TRANSFER DUCT FROM OFFICE #1 MUST BE
 ENLARGED TO 1.5 TIMES THE SIZE OF THE MAIN 10X10 SUPPLY
 DUCT INTO THE ROOM- SECTION 601.5.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-05 Cont ID  
Sent By tklarge Date 2016-03-05 Time 06:48 Rev Time 0.00
Received By tklarge Date 2016-03-05 Time 06:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By tklarge Date 2016-02-08 Time 05:23 Rev Time 0.00
Received By tklarge Date 2016-02-08 Time 05:09 Sent To  
Notes
2016-02-08 05:19:071) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. FBC SEC.
 107.2.1.
 2) HOT WATER OR TEMPERED WATER SHALL BE SUPPLIED TO THE
 NEW SINK. FBC-PLBG. SEC. 607.1.
 3) THE NEW SINK CANNOT BE INSTALLED ON A WET VENT PER
 2014 FPC SEC.912.1, 912.1.1. THE NEW SINK SHALL BE
 STACKED AND VENTED AND CONNECT TO THE HORIZONTAL DRAIN
 DOWNSTREAM OF THE WATER CLOSET.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  