Plan Review Details - Permit 16020141
Plan Review Stops For Permit 16020141
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-09-16 Cont ID  
Sent By cthroop Date 2016-09-16 Time 12:11 Rev Time 0.00
Received By cthroop Date 2016-09-16 Time 12:11 Sent To M
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-05 Cont ID  
Sent By cthroop Date 2016-05-05 Time 12:05 Rev Time 0.00
Received By cthroop Date 2016-05-05 Time 10:48 Sent To  
Notes
2016-05-05 12:09:302ND REVIEW: FBC 2014 5TH ED
 CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-7918
 [email protected]
  
 1. PROVIDE WIND LOAD ENGINEERING FOR NEW EXTERIOR
 COMPONENTS.
  
 FBC 449.4.2.4.3
 ALL NEW ROOF APPENDAGES SUCH AS DUCTS, TANKS,
 VENTILATORS, RECEIVERS, DX CONDENSING UNITS AND
 DECORATIVE MANSARD ROOFS AND THEIR ATTACHMENT SYSTEMS
 SHALL BE STRUCTURALLY ENGINEERED TO MEET THE WIND LOAD
 REQUIREMENTS OF THE APPLICABLE BUILDING CODE. ALL OF
 THESE ATTACHMENT SYSTEMS SHALL BE CONNECTED DIRECTLY TO
 THE UNDERLYING ROOF STRUCTURE OR ROOF SUPPORT
 STRUCTURE.
  
 FBC 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-02-04 Cont ID  
Sent By cthroop Date 2016-02-04 Time 15:09 Rev Time 0.00
Received By cthroop Date 2016-02-04 Time 15:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By mvaldes Date 2016-04-07 Time 18:12 Rev Time 0.00
Received By mvaldes Date 2016-04-07 Time 18:12 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-04 Cont ID  
Sent By mvaldes Date 2016-02-04 Time 17:35 Rev Time 0.00
Received By mvaldes Date 2016-02-04 Time 17:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-08-31 Cont ID  
Sent By pleduc Date 2016-08-31 Time   Rev Time 0.00
Received By pleduc Date 2016-08-31 Time 14:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By pleduc Date 2016-04-07 Time   Rev Time 0.00
Received By pleduc Date 2016-04-07 Time 11:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By pleduc Date 2016-02-10 Time   Rev Time 0.00
Received By pleduc Date 2016-02-10 Time 10:36 Sent To Z
Notes
2016-02-10 11:36:31THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET A 1 - THE CORRIDOR WALLS APPEAR TO BE 1 HOUR
 FIRE RATED. THE NEW WALL, W2, DOES NOT HAVE A RATING.
 THE NEW WALL SHALL MEET THE REQUIREMENTS OF THE
 EXISTING CORRIDOR WALLS; 1 HOUR.
  
 2. SHEET A 1 - DOOR 02 IS LOCATED WITHIN W2 IS REQUIRED
 TO BE A FIRE RATED WALL. THE DOOR AND DOOR ASSEMBLY
 SHALL BE FIRE RATED TO MATCH THE WALL.
  
 3. SHEET A 1 - THERE IS A WALL TYPE IN THE CORNER OF
 THE EXHAUST ROOM INDICATED AS W1A, THERE IS NO DESIGN
 DETAIL CALL-OUT FOR THAT WALL TYPE.
  
 4. SHEET A 1 - THE BACK WALL OF THE EXHAUST ROOM
 ADDITION IS INDICATED AS W3, HOWEVERM THE EXISTING WALL
 TYPE IS NOT INDICATED. BASED ON THE EXISTING WALL TYPE
 DOES THE ADDITIONAL WAAL TYPE REQUIRE IT TO BE SEALED
 AS ALL THE OTHE OTHER WALL TYPES WITHIN THAT ROOM?
  
 5. PROVIDE A NOTE INDICATING THAT FIRE SPRINKLER AND
 FIRE ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-09-19 Cont ID  
Sent By ccole Date 2016-09-19 Time 08:54 Rev Time 0.00
Received By ccole Date 2016-08-26 Time 10:41 Sent To  
Notes
2016-08-29 10:41:25B32

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-05 Cont ID  
Sent By cthroop Date 2016-05-05 Time 12:05 Rev Time 0.00
Received By cthroop Date 2016-04-04 Time 15:10 Sent To  
Notes
2016-04-04 15:10:14B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-08 Cont ID  
Sent By lmarchan Date 2016-03-08 Time 13:32 Rev Time 0.00
Received By lmarchan Date 2016-02-03 Time 10:01 Sent To  
Notes
2016-03-08 13:23:54TO S. KENNEDY.
2016-02-05 11:43:31B28
2016-02-04 10:02:09BLDG MISC 2

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-09-19 Cont ID  
Sent By ccole Date 2016-09-19 Time 08:54 Rev Time 0.00
Received By ccole Date 2016-09-19 Time 08:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-09-07 Cont ID  
Sent By ccole Date 2016-09-07 Time 15:11 Rev Time 0.00
Received By ccole Date 2016-09-07 Time 15:11 Sent To  
Notes
2016-09-07 15:25:383RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16020141
 9/7/16
  
 1) THE RELOCATED GENERATOR ROOM EXHAUST DOES NOT APPEAR
 TO BE A MINIMUM 10' ABOVE THE WALKWAY AS REQUIRED BY
 SECTION 501.3.1 (2). PROVIDE A CLEARANCE DISTANCE
 MEASUREMENT FROM THE ADJOINING GRADE PLANE TO THE
 BOTTOM LIP OF THE DUCT OPENING. PLEASE NOTE THE EXHAUST
 IS ALSO PROHIBITED FROM BEING DIRECTED ONTO WALKWAYS
 PER SECTION 501.3.1.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-04-11 Cont ID  
Sent By ccole Date 2016-04-11 Time 12:22 Rev Time 0.00
Received By ccole Date 2016-04-11 Time 12:22 Sent To  
Notes
2016-04-11 12:48:502ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16020141
 4/11/16
  
 1) PLEASE REFER TO NFPA 37-2010 ANNEX EXPLANATORY
 MATERIAL, SECTIONS A.8.2.3.1 AND A.11.4.2.3, IT APPEARS
 THAT THE INTENTION IS TO HAVE THE EXHAUST FROM BOTH THE
 GENERATOR ENGINE AND FROM THE GENERATOR ROOM TERMINATE
 OUTSIDE OF THE BUILDING AND NOT UNDERNEATH THE
 STRUCTURE.
  
 A.8.2.3.1: EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER
 STRUCTURES (INCLUDING LOADING PLATFORMS) OR WHERE
 EXHAUST GAS ENTRAINMENT INTO VENTILATION INTAKES MIGHT
 OCCUR.
  
 A.11.4.2.3: MECHANICAL VENTILATION SYSTEMS CAN CONSIST
 OF THE NORMAL VENTILATION SYSTEM FOR THE ROOM OR
 ENCLOSURE OR A DEDICATED PURGE SYSTEM. EXHAUST AIR
 SHOULD DISCHARGE OUTSIDE THE STRUCTURE, AWAY FROM
 OPERABLE WINDOWS AND OUTSIDE AIR INTAKES. IN LOCATING
 THE EXHAUST AIR DISCHARGE, CONSIDERATION SHOULD BE
 GIVEN TO BOTH THE ENGINE ENCLOSURE AND NEARBY
 STRUCTURES.
 CHAPTER 15, "AIRFLOW AROUND BUILDINGS," OF THE ASHRAE
 1997 HANDBOOK-FUNDAMENTALS CAN BE CONSULTED FOR
 GUIDELINES ONEXHAUST AIR STACK HEIGHT AND DISTANCE FROM
 OTHER STRUCTURES, AS WELL AS AIR INTAKES NEEDED TO
 PROVIDE ADEQUATE DILUTION AND TO AVOID DETRIMENTAL
 EFFECTS OF DOWNDRAFTS.
  
 A) REFER TO SECTIONS 501.3 AND 501.3.1(4) FBC-14
 MECHANICAL WHICH REQUIRE THE EXHAUST SYSTEMS NOT TO
 TERMINATE WHERE THEY COULD CAUSE A NUISANCE, OR BE
 READILY DRAWN INTO A VENTILATING SYSTEM, AND MUST BE 3'
 FROM EXTERIOR WALLS AND ROOFS.
  
 2) THE SCREENING FOR THE GENERATOR ROOM EXHAUST DUCT
 SHALL BE CORROSION RESISTANT WITH OPENINGS NOT LESS
 THAN 1/4" AND NOT LARGER THAN 1/2". THE 1" WELDED
 STAINLESS MEXH SPECIFIED ON THE PLANS DOES NOT MEET THE
 CODE.
  
 3) PLEASE PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE GEF-1 AND EXHAUST DUCTWORK- SECTION
 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-05 Cont ID  
Sent By ccole Date 2016-02-05 Time 10:30 Rev Time 0.00
Received By ccole Date 2016-02-05 Time 09:50 Sent To  
Notes
2016-02-05 11:16:111ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #160201421
 2/5/16
  
 1) THE NEW W2 WALL AND ALL OTHER WALLS AND CEILINGS
 HOUSING THE EXTENDED GENERATOR ROOM MUST HAVE A MINIMUM
 1HR. FIRE-RESISTANCE RATING PER SECTION 4.1.2.1.1 NFPA-
 37. PLEASE REVISE THE PLANS ACCORDINGLY AND INCLUDE A
 MINIMUM 45 MINUTE FIRE-RATED DOOR WITH SELF CLOSING
 HARDWARE- SECTION 716 FBC-14 BUILDING. THIS NEW ROOM IS
 AN EXHAUST PLENUM FOR THE GENERATORS AND DOES NOT
 APPEAR TO BE SEPARATED BY FIRE-RATED CONSTRUCTION.
 2) PROVIDE UL TESTED AND APPROVED FIRE-STOPPING
 ASSEMBLIES FOR THE 56"X26" ROOM EXHAUST DUCT AND THE
 ENGINE EXHAUST PIPE THIMBLES PENETRATING FIRE-RATED
 WALLS. CLARIFY IF THE DUCT WILL HAVE A GRILL COVER AND
 PROVIDE A DETAIL.
 3) INDICATE THE DIAMETERS OF THE EXHAUST THIMBLES-
 MINIMUM 12" IS REQUIRED PER SECTION 8.3.3 (1) NFPA 37.
 4) PROVIDE DETAILS FOR BOTH THE ROOM EXHAUST AND ENGINE
 EXHAUST DUCTS: TYPE AND GAUGE OF STEEL, HANGER TYPES
 AND SIZES, SPAN OF HANGER SUPPORTS, REINFORCEMENT AND
 SEALING METHODS.
 5) PROVIDE AN ELEVATION VIEW OF THE EXHAUST OUTLETS
 INDICATING REQUIRED CLEARANCE DISTANCE MEASUREMENTS AS
 OUTLINED IN SECTION 501.3.1 FBC-214 MECHANICAL.
 6) PROVIDE APPROVED TERMINATION CAPS FOR THE ENGINE
 EXHAUST DUCTS- REFER TO SECTION 8.2.3 NFPA 37.
 7) PLEASE NOTE THE DRAWING INDEX INDICATES M1.2 WHCIH
 WAS NOT INCLUDED IN THE PLAN SETS. SHEET M3.1 WAS
 INCLUDED IN THE SETS BUT IS NOT SHOWN IN THE INDEX.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2016-04-27 Cont ID  
Sent By aaponte Date 2016-04-27 Time 10:01 Rev Time 0.00
Received By aaponte Date 2016-04-27 Time 10:01 Sent To  
Notes
2016-04-27 10:01:39EXHAUST SHALL NOT PROJECT OUT FROM THE BUILDING FACE.

Review Stop Z ZONING
Rev No 1 Status P Date 2016-03-08 Cont ID  
Sent By aaponte Date 2016-03-08 Time 13:23 Rev Time 0.00
Received By aaponte Date 2016-03-08 Time 13:23 Sent To  
Notes
2016-03-08 13:23:35EXHAUST SHALL NOT PROJECT OUT FROM THE BUILDING FACE.


Account Summary | Usage Policy | Privacy Policy