2016-02-18 14:31:23 | BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 16020105 |
| ADD: 1001 S. FLAGLER DR. STAIR PRESSURIZATION |
| CONT: HILL YORK SERVICES |
| TEL: 561-689-7355 |
| E-MAIL: [email protected] |
| |
| 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: THURS. FEB. 18/2016 |
| ACTION: DENIED |
| |
| 1) A MEETING WAS HELD TODAY WITH THE CONTRACTOR CHRIS |
| TYSON AND THE PRESIDENT OF P.B.A.U. AND MYSELF ON THE |
| TOPIC OF STAIR PRESSUREIZATION AND THE COORDINATING OF |
| THE PLANS FOR THE VARIOUS TRADES, WHO WILL BE THE |
| DESIGNER OF RECORD FOR THE WHOLE PROJECT AND THE SHOP |
| DRAWING OF THE APPROVAL BY THE DESIGNER OF RECORD. THE |
| (2) SUBMITTED STAIR PRESSURE DESIGN DOCUMENTS WILL |
| REFLECT THE SAME EQUIPMENT AND DESIGN, NOT TO DIFFERENT |
| DESIGNS. |
| 2) WE ALSO TALKED ABOUT THE REQUIREMENT ON THE NEXT |
| SUBMITTAL ALL EXISITNG PERMIT APPLICATIONS AND THE |
| ADDITIONAL ELECTRICAL AND FIRE ALARM. |
| 3) THE CGC PERMIT APPLICATION WILL NEED TO BE MODIFIED |
| IN THE SCOPE OF WORK TO REFLECT WHAT CAN BE COVERED |
| UNDER THE CGC LICENSURE. |
| 4) THE CGC PERMIT AND PLANS WILL ALSO NEED TO REFLECT |
| THE ROOF TOP CURBS, AND INTAKE FANS, AS WEL AS THE NEW |
| A/C STANDS THAT WERE ADDED UNDER THE ROOFING PERMIT |
| WHICH DOES NOT SHOW ANY OF THESE PRODUCT APPROVALS |
| SUBMITTED UNDER THAT PERMIT IN FILE NET THE BUILDING |
| DEPARTMENT RECORD RETENSION PROGRAM. |
| THE ROOFING PERMIT ALSO INDICATES THE INSTALATION OF A |
| NEW DOOR ITEM # 18 CORRIN DOOR, NO PRODUCT APPROVAL HAD |
| BEEN SUBMITTED. |
| , 1609.6.4.4.1 COMPONENTS & CLADDING |
| |
| FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| (31)(A) EXTERIOR DOORS. |
| (D) ROOFING PRODUCTS AND ASSEMBLIES |
| (G) PRE-ENGINEERED A/C STANDS |
| |
| 5) THE NEW HOLES IN EITHER THE ROOF SLAB AND OR WALL |
| WILL ALSO NEED TO BE ADDRESSED AND THE REQUIRED |
| ANCHORING OF THE ROOF TOP EXHAUST BACK DRAFT DAMPER. |
| PLEASE PROVIDE THE WIND DESIGN CRITERIA AND ANCORING. |
| 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| |
| 6) WORK TO BE DETREMINED BY OTHERS: |
| 6A) NEW POWER WIRING, ELECTRICAL PLANS, DISCONNECTS BY |
| ELECTRICAL CONTRACTOR. |
| 6B) CONTROL WIRING BY ELECTRICAL CONTRACTOR. |
| 6C) ROOF FLASHING FOR ROOF CURBS AND WALLS |
| 6D) INTERFACE OF NEW STAIRWELL PRESSURIZATION SYSTEM |
| INTO THE EXISTING FIRE ALARM |
| 6E) EMERGENCY POWER FOR NEW STAIRWELL PRESSURIZATION |
| FAN ( NOT HIGHRISE, MAY NOT HAVE A BACKUP GENERATOR)? |
| 6F) DOOR CLOSER AND ADJUSTMENTS |
| |
| 7) 2014 FBC-B 909.2 GENERAL DESIGN REQUIREMENTS. |
| BUILDINGS, STRUCTURES OR PARTS THEREOF REQUIRED BY THIS |
| CODE TO HAVE A SMOKE CONTROL SYSTEM OR SYSTEMS SHALL |
| HAVE SUCH SYSTEMS DESIGNED IN ACCORDANCE WITH THE |
| APPLICABLE REQUIREMENTS OF SECTION 909 AND THE |
| GENERALLY ACCEPTED AND WELL-ESTABLISHED PRINCIPLES OF |
| ENGINEERING RELEVANT TO THE DESIGN. THE CONSTRUCTION |
| DOCUMENTS SHALL INCLUDE SUFFICIENT INFORMATION AND |
| DETAIL TO ADEQUATELY DESCRIBE THE ELEMENTS OF THE |
| DESIGN NECESSARY FOR THE PROPER IMPLEMENTATION OF THE |
| SMOKE CONTROL SYSTEMS. THESE DOCUMENTS SHALL BE |
| ACCOMPANIED BY SUFFICIENT INFORMATION AND ANALYSIS TO |
| DEMONSTRATE COMPLIANCE WITH THESE PROVISIONS. |
| |
| 8) 2014 FBC-B 909.4 ANALYSIS. A RATIONAL ANALYSIS |
| SUPPORTING THE TYPES OF SMOKE CONTROL SYSTEMS TO BE |
| EMPLOYED, THEIR METHODS OF OPERATION, THE SYSTEMS |
| SUPPORTING THEM AND THE METHODS OF CONSTRUCTION TO BE |
| UTILIZED SHALL ACCOMPANY THE SUBMITTED CONSTRUCTION |
| DOCUMENTS AND SHALL INCLUDE, BUT NOT BE LIMITED TO, THE |
| ITEMS INDICATED IN SECTIONS 909.4.1 THROUGH 909.4.6. |
| |
| 9) PLEASE SEE THE REQUIREMENTS FOR ROOF TOP GUARDS, |
| 1013.6 MECHANICAL EQUIPMENT. |
| GUARDS SHALL BE PROVIDED WHERE APPLIANCES, EQUIPMENT, |
| FANS, ROOF HATCH OPENINGS OR OTHER COMPONENTS THAT |
| REQUIRE SERVICE ARE LOCATED WITHIN 10 FEET (3048 MM) OF |
| A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND SUCH |
| EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES (762 |
| MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD |
| SHALL BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A |
| SPHERE 21 INCHES (533 MM) IN DIAMETER. THE GUARD SHALL |
| EXTEND NOT LESS THAN 30 INCHES (762 MM) BEYOND EACH END |
| OF SUCH APPLIANCE, EQUIPMENT, FAN OR COMPONENT. |
| |
| 10) 1013.7 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE |
| THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 |
| MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE |
| AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 |
| INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. |
| THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE |
| PASSAGE OF A SPHERE 21 INCHES (533 MM) IN DIAMETER. |
| |
| 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: 561-805-6715 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |