Plan Review Details - Permit 16020089
Plan Review Stops For Permit 16020089
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 15:46 Rev Time 0.00
Received By cthroop Date 2016-03-22 Time 15:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By cthroop Date 2016-02-10 Time 11:38 Rev Time 0.00
Received By cthroop Date 2016-02-10 Time 10:08 Sent To  
Notes
2016-02-10 11:47:30CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE PRODUCT APPROVAL FOR WINDOW MULLIONS.
 PROVIDE ELEVATION OF LANDING AT NEW DOOR. IF LANDING IS
 GREATER THAN 30" ABOVE GRADE, PROVIDE GUARD.
 CLARIFY WALL LEGEND, PG A-1.
  
 FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
 SPECIFICALLY, PROVIDE WINDOW MULLION SUBMITTALS.
  
 FBCR312.1.1 GUARDS SHALL BE LOCATED ALONG OPEN-SIDED
 WALKING SURFACES, INCLUDING STAIRS, RAMPS AND LANDINGS,
 THAT ARE LOCATED MORE THAN 30 INCHES (762 MM) MEASURED
 VERTICALLY TO THE FLOOR OR GRADE BELOW AT ANY POINT
 WITHIN 36 INCHES (914 MM) HORIZONTALLY TO THE EDGE OF
 THE OPEN SIDE. INSECT SCREENING SHALL NOT BE CONSIDERED
 AS A GUARD.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-02-25 Cont ID  
Sent By rlecky Date 2016-02-25 Time 12:28 Rev Time 0.00
Received By rlecky Date 2016-02-25 Time 11:58 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-03-08 Cont ID  
Sent By fmittner Date 2016-03-08 Time 13:29 Rev Time 0.00
Received By fmittner Date 2016-03-08 Time 13:29 Sent To  
Notes
2016-02-16 16:28:362/16/16

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-24 Cont ID  
Sent By tklarge Date 2016-03-24 Time 05:55 Rev Time 0.00
Received By tklarge Date 2016-03-10 Time 15:36 Sent To  
Notes
2016-03-10 15:36:57R01

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-10 Cont ID  
Sent By lmarchan Date 2016-03-10 Time 15:34 Rev Time 0.00
Received By lmarchan Date 2016-03-09 Time 19:14 Sent To  
Notes
2016-03-09 19:17:153/9/2016 SMALL DENIED A. JV.
2016-02-03 10:23:07R07

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2016-03-22 Cont ID  
Sent By cthroop Date 2016-03-22 Time 15:46 Rev Time 0.00
Received By cthroop Date 2016-03-22 Time 15:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2016-03-09 Cont ID  
Sent By jvalido Date 2016-03-09 Time 19:14 Rev Time 0.00
Received By jvalido Date 2016-03-09 Time 19:14 Sent To  
Notes
2016-03-09 19:01:46NOTICE TO INSPECTORS
 THIS PERMIT IS BEING ISSUED WITHOUT ANY MECHANICAL. IF
 ANY MECHANICAL WORK IS OBSERVED, PLLEASE STOP THE JOB
 AND REPORT TO CONSTRUCTION SERVICES.

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-24 Cont ID  
Sent By tklarge Date 2016-03-24 Time 05:54 Rev Time 0.00
Received By tklarge Date 2016-03-24 Time 05:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-02-10 Cont ID  
Sent By tklarge Date 2016-02-10 Time 13:10 Rev Time 0.00
Received By tklarge Date 2016-02-10 Time 12:33 Sent To  
Notes
***NONE***