Plan Review Details - Permit 16020057
Plan Review Stops For Permit 16020057
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By cthroop Date 2016-03-03 Time 15:57 Rev Time 0.00
Received By cthroop Date 2016-03-03 Time 15:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By aclange Date 2016-02-08 Time 16:45 Rev Time 0.00
Received By aclange Date 2016-02-08 Time 16:45 Sent To P
Notes
2016-02-08 17:10:06****CORRECTIONS****
  
 ART LANGE - BUILDING INSPECTOR
 561-805-6667 [email protected]
 FBC FLORIDA BUILDING CODE 2014 5TH EDITION
  
 1. PERMIT VALUE TOO LOW. PROVIDE A SIGNED CONTRACT AND
 REVISE PERMIT VALUE WHEN YOU RESUBMIT PLANS.
 FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2. PROVIDE MEASUREMENTS ON PLANS FOR DOOR ?A?. SHOW
 COMPLIANCE WITH THE FOLLOWING. FLORIDA ACCESSIBILITY
 CODE 404.2.4.1 (A) FRONT APPROACH , PULL SIDE AND (C)
 FRONT APPROACH, PUSH SIDE IF DOOR HAS A CLOSER. SEE
 FIGURES 404.2.4.1.
 SHOW DOOR HANDLE HARDWARE AND CLOSER IF USED.
  
 3. SHOW IF DOORS WILL BE PROVIDED FOR THE FOLLOWING
 ROOMS: OFFICE, MASSAGE ROOM #1 AND EXAM ROOM #1.
  
 4. PLEASE PROVIDE A DETAIL FOR THE RECEPTION PAST
 THROUGH. SHOW HOW IT WILL COMPLY WITH FLORIDA
 ACCESSIBILITY CODE SECTION 308.
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By vperez Date 2016-03-03 Time 10:56 Rev Time 0.00
Received By vperez Date 2016-03-03 Time 10:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 10:45 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 10:45 Sent To  
Notes
2016-02-10 10:45:51INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA. A NOTE
 WILL SUFFICE. FBC 107
 2. AN ELECTRICAL PERMIT WILL BE REQUIRED FOR THIS
 PROJECT. ALTHOUGH THE SCOPE OF WORK SAYS NO ELECTRICAL,
 THE CHANGE IN OCCUPANCY TO A CHIROPRACTIC OFFICE
 REQUIRES THE ELECTRICAL INSTALLATION TO BE IN
 CONFORMANCE WITH THE NFPA 70 NEC 2011 ARTICLE 517. ALSO
 THERE IS A NEW EXIT/EM LIGHTING SHOWN.
 3. THE EXAMINATION AREAS WHERE HUMAN BEINGS WILL COME
 IN CONTACT WITH EXAMINATION EQUIPMENT MUST BE WIRED IN
 A MANNER AS DESCRIBE IN NEC 2011 517.13. PLEASE REFLECT
 ON DRAWINGS A NOTE TO INDICATE THIS REQUIREMENT.
 4. GFCI PROTECTION IS REQUIRED FOR RECEPTACLE OUTLET
 SERVING ANY HYDRO MESSAGE EQUIPMENT AS SHOWN ON
 DRAWING. NEC 680- PART VI. CLARIFY WHAT TYPE OF
 EQUIPMENT IS BEING USED.
 5. IF A DRINKING FOUNTAIN IS PART OF THE SCOPE SHOW THE
 RECEPTACLE PROTECTED BY GFCI BREAKER. NEC 422.52
 6. CLARIFY IF THERE IS X-RAY EQUIPMENT BEING INSTALLED.
 FURTHER COMMENTS TO FOLLOW PER CLARIFICATION.
 7. SHOW WINDOW RECEPTACLE OUTLETS NOT SHOWN ON PLANS.
 PLEASE CLARIFY AND COMPLY WITH NEC 220.14G AND NEC
 210.62.
 8. CLARIFY IF ANY CHANGES OR MODIFICATIONS ARE WITHIN
 THE SCOPE OF WORK FOR THE MECHANICAL UNIT. IF NOT SHOW
 AS EXISTING ON DRAWING AND THE LOCATION.
 9. ALL NEW LOADS TO BE REFLECTED ON A PANEL SCHEDULE.
 SHOW THE EXISTING RISER DIAGRAM TO VERIFY CAPACITY
 REQUIREMENTS. FBC 107 NEC 220
 10. CLARIFY IF THERE IS AN EXISTING OUTLET FOR THE
 FRONT SIGN. NEC 600.5
 11. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-28 Cont ID  
Sent By sathomas Date 2016-03-28 Time 17:07 Rev Time 0.00
Received By sathomas Date 2016-03-28 Time 17:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-08 Cont ID  
Sent By vperez Date 2016-02-10 Time 10:47 Rev Time 0.00
Received By sathomas Date 2016-02-08 Time 09:12 Sent To B
Notes
2016-02-08 09:15:49PERMIT # 16020057
  
 PROVISO
 ENSURE THAT ALARM NOTIFICATION/SPRINKLER COVERAGE ARE
 NOT COMPROMISED BY NEW INTERIOR LAYOUT. HAVE EVALUATED
 BY LICENSED ALARM/SPRINKLER COMPANY.
  
 SLT 7805

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-03 Cont ID  
Sent By cthroop Date 2016-03-03 Time 15:56 Rev Time 0.00
Received By cthroop Date 2016-03-03 Time 10:11 Sent To  
Notes
2016-03-03 10:57:133/3 TO STEVE K.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 10:47 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 10:47 Sent To FIRE
Notes
2016-02-10 10:47:40SENT TO CAROLINE/LAURA

Review Stop P PLUMBING
Rev No 2 Status N Date 2016-03-03 Cont ID  
Sent By skennedy Date 2016-03-03 Time 10:26 Rev Time 0.00
Received By skennedy Date 2016-03-03 Time 10:26 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By tklarge Date 2016-02-10 Time 08:48 Rev Time 0.00
Received By tklarge Date 2016-02-10 Time 06:31 Sent To  
Notes
2016-02-10 08:35:311) SHT. S-0 - SCOPE OF WORK REFERS TO THE RELOCATION OF
 A WATER FOUNTAIN BUT THERE IS NO WATER FOUNTAIN SHOWN
 ON THE PLANS. CLARIFY.
 2) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ALL
 CHANGES TO THE SANITERY AND WATER PIPNG SYSTEM. 2014
 FBC SEC. 107.2.1.
 3) THIS APPEARS TO BE A CHANGE OF OCCUPANCY FROM AN S-2
 TO A "B: OCCUPANCY.IF IT IS, THEN CCOMPLIANCE WITH THE
 2014 FBC-EXISTING BUILDING CODE CHAPTER 10 IS REQUIRED.
 SEE SECTIONS 1002 THROUGH 1012.
 4) PLEASE PLACE THE CORRECT OCCUPANT LOAD ON THE PLANS.
 THE PLANS REFER TO AN OCCUPANT LOAD OF 9, 11 &14. THE
 CORRECT OCCUPANT LOAD FOR A SPACEE OF 915 SQUARE FEET
 IS10 PERSONS PER 2014 FBC TABLE 1004.1.2.
 5) IF A DRINKING FOUNTAIN IS INSTALLED A MINIMUM OF 2
 ARE REQUIRED PER THE 2014 FBC- ACCESS. SEC. 211.2.
 6) CLARIFY HOW YOU ARRIVED AT THE MINIMUM SANITARY
 FIXTURE REQUIREMENTS. THE PLANS SHOW THE REQUIRED WATER
 CLOSETS AS 2, REQUIRED LAVATORIES AS 2, ONE JANITOR
 SINK AND TWO DRINKING FFOUNTAINS.THE PLANS DO NOT SHOW
 THIS NUMBER AND TYPE OF SANITARY FACILITIES. CLARRIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  