Plan Review Details - Permit 16020030
Plan Review Stops For Permit 16020030
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-29 Cont ID  
Sent By rmcdouga Date 2016-03-29 Time 19:23 Rev Time 0.00
Received By rmcdouga Date 2016-03-29 Time 19:23 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-02-10 Cont ID  
Sent By rmcdouga Date 2016-02-10 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2016-02-10 Time 07:28 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-30 Cont ID  
Sent By rmcdouga Date 2016-03-30 Time 13:50 Rev Time 0.00
Received By albarran Date 2016-03-30 Time 12:14 Sent To  
Notes
2016-03-30 13:51:04ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014, NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. ACCORDING TO THE SUBMITTED SITE PLAN, THE OVERHEAD
 SERVICE CONDUCTORS ARE CROSSING OVER THE POOL. SEE NEC
 TABLE 680.8 FOR MINIMUM REQUIREMENTS.
 2. THERE SEEMS TO BE A CONFLICT BETWEEN THE SITE PLAN
 AND THE SITE SURVEY. THE SURVEY SHOWS THE O/H
 CONDUCTORS, YET THE SITE PLAN DOES NOT. COMPARING THE
 PREVIOUSLY SUBMITTED SITE DRAWING TO THE CURRENT THERE
 CONTINUES TO BE A CONFLICT. THE OLD SITE PLAN SHOWS THE
 O/H CONDUCTORS WITH A NOTE INDICATING THAT THEY WILL BE
 REMOVED BY OWNER. THE CURRENT SITE PLAN NO LONGER HAS
 THE O/H SERVICE CONDUCTORS, BUT OUR SYSTEM DOES NOT
 REFLECT THAT AN ELECTRICAL PERMIT FOR THE CHANGE WAS
 EVER ISSUED. THIS MATTER NEEDS TO BE CLARIFIED PRIOR TO
 THE ISSUANCE OF THE PERMIT.
 3. YOU MUST SHOW THE EQUI-POTENTIAL BONDING ON THE
 DRAWINGS AS INDICATED IN NEC 680.26.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-05 Cont ID  
Sent By albarran Date 2016-02-05 Time 10:42 Rev Time 0.00
Received By albarran Date 2016-02-05 Time 09:38 Sent To  
Notes
2016-02-05 10:42:131ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 5TH EDITION 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 1. YOU SHALL PROVIDE AN ELECTRICAL RISER DIAGRAM
 INDICATING ALL THE PROPOSED POOL EQUIPMENT AND
 LIGHTING. THIS SHOULD ALSO INDICATE THE TYPE OF POOL
 LIGHTING PROPOSED IF ANY.
 2. FROM THE SITE PLAN PROVIDED, ACTUAL MEASUREMENTS FOR
 THE LOCATION OF OVERHEAD SERVICE CONDUCTORS IN RELATION
 TO THE POOL WOULD NOT BE PRACTICAL. THE PLAN HAS A NOTE
 INDICATING THAT THE SERVICE DROP WILL BE REMOVED BY THE
 OWNER. VERIFY OVERHEAD CONDUCTOR CLEARANCES AS
 INDICATED IN NEC 680.8 IF IT IS TO REMAIN AND REVISE
 THE DRAWING TO REMOVE SUCH NOTE.
 3. WHEN DIGGING THE HOLE FOR THE POOL SHELL, ASCERTAIN
 COMPLIANCE WITH NEC 680.10 WHICH PROHIBITS ANY
 UNDERGROUND WIRING WITHIN 5? HORIZONTALLY OF THE POOL
 SHELL UNLESS THE WIRING IS DIRECTLY RELATED TO THE
 POOL.
 4. ALL POOL BONDING AS REQUIRED BY NEC 680.26 SHALL BE
 INDICATED ON DRAWINGS.
 5. IN ADDITION TO THE ABOVE, COMPLIANCE WITH FBC-R
 CHAPTER 42.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2016-02-08 Cont ID  
Sent By tklarge Date 2016-02-08 Time 04:57 Rev Time 0.00
Received By tklarge Date 2016-02-08 Time 04:57 Sent To  
Notes
2016-02-08 04:57:48THERE IS NO GAS ASSOCIATED WITH THIS POOL.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-04 Cont ID  
Sent By tklarge Date 2016-04-04 Time 06:04 Rev Time 0.00
Received By tklarge Date 2016-03-22 Time 09:41 Sent To  
Notes
2016-03-22 09:41:28RESUB ROUTED TO AJONES VIA ZONING INBOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-10 Cont ID  
Sent By rmcdouga Date 2016-02-10 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2016-02-01 Time 13:53 Sent To  
Notes
2016-02-02 13:53:38ROUTED TO ZONING

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-04 Cont ID  
Sent By tklarge Date 2016-04-04 Time 06:04 Rev Time 0.00
Received By tklarge Date 2016-04-04 Time 05:45 Sent To  
Notes
2016-04-04 05:53:31NONE OF THE PLUMBING COMMENTS FROM THE FIRST REVIEW
 HAVE BEEN ADDRESSED.
  
 1) PROVIDE MANUFACTURER'S SPECIFICATIONS ON THE PUMP,
 TSUNAMI VALVE,& MDX REMOVAL SYSTEM. FBC
 SEC.107.2.1.SUBMIT COMPLETE SPECIFICATIONS FOR THE
 PUMP. THE ONE SHEET THAT WAS SUBMITTED IS UNACCEPTABLE.
 2) SUPPLY TOTAL DYNAMIC HEAD CALCULATIONS, PUMP
 CURVE,TURNOVER RATE, ETC. FBC SEC.107.2.1.
 3) PLEASE REVISE THE CODE REFERENCE ON THE THE PLANS TO
 FBC-RESIDENTIAL.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By tklarge Date 2016-02-08 Time 05:07 Rev Time 0.00
Received By tklarge Date 2016-02-08 Time 04:40 Sent To  
Notes
2016-02-08 05:07:081) PROVIDE MANUFACTURER'S SPECIFICATIONS ON THE PUMP,
 TSUNAMI VALVE,& MDX REMOVAL SYSTEM. FBC SEC.107.2.1.
 2) SUPPLY TOTAL DYNAMIC HEAD CALCULATIONS, PUMP
 CURVE,TURNOVER RATE, ETC. FBC SEC.107.2.1.
 3) PLEASE REVISE THE CODE REFERENCE ON THE THE PLANS TO
 FBC-RESIDENTIAL.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2016-02-04 Cont ID  
Sent By ajones Date 2016-02-04 Time 16:47 Rev Time 0.00
Received By ajones Date 2016-02-04 Time 16:47 Sent To B
Notes
***NONE***