Plan Review Stops For Permit 16010936 |
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-01-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-28 |
Time |
19:01 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-28 |
Time |
14:41 |
Sent To |
|
|
Notes |
2016-01-28 14:41:43 | RMCDOUGAL'S DESK |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
P |
Date |
2016-02-01 |
|
|
Cont ID |
|
Sent By |
skennedy |
Date |
2016-02-01 |
Time |
13:00 |
Rev Time |
0.00 |
Received By |
skennedy |
Date |
2016-02-01 |
Time |
13:00 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2016-01-28 |
|
|
Cont ID |
|
Sent By |
rmcdouga |
Date |
2016-01-29 |
Time |
7:49 |
Rev Time |
0.00 |
Received By |
rmcdouga |
Date |
2016-01-28 |
Time |
18:47 |
Sent To |
|
|
Notes |
2016-01-28 19:01:59 | 2010 FBC | | REVISION DENIED | | | | 1) THE ORIGINAL APPROVED PLANS WERE PRODUCED BY ANOTHER | | A/C CONTRACTOR. THE NEW PLANS FROM A DIFFERENT A/C | | CONTRACTOR CAN NOT REFER TO DETAILS ON THE OTHER | | CONTRACTOR'S DRAWINGS. THE NEW CONTRACTOR IS REQUIRED | | TO REPRODUCE THE PLANS ENTIRELY WITH ALL DETAILS AND | | SCHEDULES. FBC 107.2.3 AND FS 471.003 (2)(H) | | | | 2) SHOW COMPLIANCE WITH 2010 FBCR - M1503.4 FOR | | REQUIRED MAKEUP AIR FOR THE 600 CFM KITCHEN EXHAUST | | HOOD. | | | | 3) THE NEW MECHANICAL PLANS ARE MISSING SOME OF THE | | WALLS FROM THE FLOOR PLANS. FBC 107.2.1 | | |
|
|
|