Plan Review Details - Permit 16010922
Plan Review Stops For Permit 16010922
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-03 Cont ID  
Sent By cthroop Date 2016-02-03 Time 10:19 Rev Time 0.00
Received By cthroop Date 2016-02-03 Time 10:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-28 Cont ID  
Sent By rmcdouga Date 2016-01-28 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2016-01-28 Time 17:40 Sent To  
Notes
2016-01-28 18:10:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE E(4) SYSTEM SELECTED ON PAGE 24 OF NOA NO.
 14-0529.02 HAS A MAXIMUM DESIGN PRESSURE OF -52.5 PSF,
 WHICH IS NOT ADEQUATE FOR THE PERIMETER AND CORNER ROOF
 AREAS OF THE FLAT ROOF OF A STRUCTURE WITH A 15' MRH IN
 EXPOSURE C. SUBMIT TWO SETS OF SIGNED AND SEALED RAS
 117 CALCULATIONS AS REQUIRED BY LIMITATION #7 ON PAGE
 42 OF THE NOA.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-03 Cont ID  
Sent By cthroop Date 2016-02-03 Time 10:15 Rev Time 0.00
Received By cthroop Date 2016-02-03 Time 10:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-28 Cont ID  
Sent By rmcdouga Date 2016-01-28 Time 18:10 Rev Time 0.00
Received By rmcdouga Date 2016-01-28 Time 12:44 Sent To  
Notes
2016-01-28 12:44:52RMCDOUGAL DESK