Plan Review Details - Permit 16010904
Plan Review Stops For Permit 16010904
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-25 Cont ID  
Sent By jwitmer Date 2016-02-25 Time 11:29 Rev Time 0.00
Received By jwitmer Date 2016-02-25 Time 11:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-05 Cont ID  
Sent By jwitmer Date 2016-02-05 Time 07:29 Rev Time 0.00
Received By jwitmer Date 2016-02-05 Time 06:45 Sent To  
Notes
2016-02-05 07:26:51W. P. B. PERMIT: 16010904
 ADD: 201 CLEMATIS ST.
 CONT: BSA CORP.
 TEL: 561-272-6350
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB.05/ 2016
 ACTION: DENIED
  
 1) SHEET A001 THE PLANS INDICATE THIS IS A TYPE VB
 BUILDING, SPRINKLERED, 2 STORY , A-1 OCCUPANCY WITH A
 TOTAL BUILDING AREA OF 17, 208 SQ. FT. PLEASE PROVIDE
 THE SQUARE FEET OF THE 1ST FLOOR, (FOOTPRINT) IF FIRE
 SPRINKLER INCREASE WERE TAKEN OR IF FRONTAL INCREASES
 WERE TAKEN FBC-B 504.2 & OR 506.2.
  
 2) IN ONE SET OF PLANS SHEET A003, THE PLANS ARE SIGNED
 BUT NOT SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3) SHEET A003 THE DOORS TO THE 2 NEW OFFICE NOR IS THE
 DOOR TO THE STORAGE ROOM, THE SIZE PROVIDED. PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B SECTION
 1008.1.1. SIZE OF DOORS. 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF 32 INCHES (813 MM). CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-29 Cont ID  
Sent By vperez Date 2016-02-29 Time 11:37 Rev Time 0.00
Received By vperez Date 2016-02-29 Time 11:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By vperez Date 2016-02-12 Time 13:17 Rev Time 0.00
Received By vperez Date 2016-02-12 Time 13:17 Sent To  
Notes
2016-02-12 13:18:33INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, AUDIO/SPEAKERS, PHONE AND DATA. A NOTE WILL
 SUFFICE.
 2. PROVIDE A PANEL SCHEDULE REFLECTING ALL PERTINENT
 INFORMATION: FOR EXAMPLE, NEW LOADS, AIC RATING ETC.
 FBC 107.
 3. ID THE FLOOR PLAN WITH CIRCUIT DESIGNATION. FBC
 107.3
 4. PLEASE SHOW AUTOMATIC LIGHTING CONTROLS COMPLIANCE
 PER FBC EC 405
 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-17 Cont ID  
Sent By pleduc Date 2016-02-17 Time   Rev Time 0.00
Received By pleduc Date 2016-02-17 Time 12:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-02 Cont ID  
Sent By pleduc Date 2016-02-02 Time   Rev Time 0.00
Received By pleduc Date 2016-02-01 Time 13:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-29 Cont ID  
Sent By vperez Date 2016-02-29 Time 11:37 Rev Time 0.00
Received By vperez Date 2016-02-29 Time 11:37 Sent To  
Notes
2016-02-29 11:37:392/29 TO CAROLINE FOR COMPLETION
2016-02-16 14:28:55B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-12 Cont ID  
Sent By vperez Date 2016-02-12 Time 13:18 Rev Time 0.00
Received By vperez Date 2016-02-12 Time 13:18 Sent To  
Notes
2016-02-12 13:18:58TO LAURA
2016-01-28 15:29:26B08

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-26 Cont ID  
Sent By ccole Date 2016-02-26 Time 14:19 Rev Time 0.00
Received By ccole Date 2016-02-26 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By ccole Date 2016-02-08 Time 12:03 Rev Time 0.00
Received By ccole Date 2016-02-08 Time 12:03 Sent To  
Notes
2016-02-08 12:12:551ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010904
 2/8/16
  
 1) SHEET M000: THE DRAWINGS AND PRINT IN DETAIL N0.3 IS
 VERY FAINT AND NOT SUITABLE FOR PLAN REVIEW OR COMPUTER
 FILE SCANNING- PLEASE SUBMIT LEGIBLE PLANS PER SECTION
 107.2 WPB AMENDMENTS TO THE FBC-14 BUILDING CODE.
 2) M100: THE PRINT ION THE SYMBOL LEGEND IS VERY FAINT
 AND NOT LEGIBLE- PLEASE SUBMIT LEGIBLE PLANS.
 3) REFER TO SECTION 809.2 FBC-14 EXISITNG BUILDING AND
 PROVIDE A VENTILATION CALCULATIONS FOR THE PROPOSED NEW
 OFFICES- SHOW THE REQUIRED AND PROVIDED CFM'S OF O/A
 AIR.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  