Plan Review Details - Permit 16010845
Plan Review Stops For Permit 16010845
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2016-04-06 Cont ID  
Sent By tklarge Date 2016-04-06 Time 04:26 Rev Time 0.00
Received By tklarge Date 2016-04-04 Time 03:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2016-03-27 Cont ID  
Sent By tklarge Date 2016-03-27 Time 03:11 Rev Time 0.00
Received By tklarge Date 2016-03-27 Time 02:20 Sent To  
Notes
2016-03-27 03:00:111) THERE ARE TWO GAS DRAWINGS THAT SHOW THE PIPING TO
 THE WATER HEATER AS 1/2 INCH AND ALSO AS 3/4 INCH. THE
 GAS LINE TO THE WATER HEATER MUST BE A MINIMUM OF 3/4
 INCH, NOT 1/2 INCH.
 2) SUBMIT A CCOPY OF THE GAS SIZING TABLE THAT YOU USED
 TO SIZE THE PIPE TO THE WATER HEATER. 2014 FBCR
 SEC.G2413.
  
 I SUGGEST CONTACTIN ME TO SET UP AN APPOINTMENT TO
 REVIEW YOUR PLANS AND FIX THE ERRORS SO I CAN ISSUE
 YOUR PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2016-03-03 Cont ID  
Sent By tklarge Date 2016-03-03 Time 06:44 Rev Time 0.00
Received By tklarge Date 2016-03-03 Time 05:51 Sent To  
Notes
2016-03-03 06:44:321) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 2).INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 3) .SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE
 AND TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426.ALL
 VENTS SHALL BE LISTED AND LABELED.
  
 4) IS THE WATER HEATER LOCATED INSIDE THE LAUNDRY ROOM?
 CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-01-27 Cont ID  
Sent By tklarge Date 2016-01-27 Time 08:31 Rev Time 0.00
Received By tklarge Date 2016-01-27 Time 08:26 Sent To  
Notes
2016-01-27 08:31:051.SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE PER 2014 FBC-FUEL
 GAS, SECS. 402.4.1, 402.4.2. OR 2014 FBC-RES SEC.
 G2413.
  
 2.SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE.
 WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 3.BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM. REFER TO THE 2014 FBC-FUEL GAS SECS.401.8
 THRU 402.6.1 AND TABLES 402.4 (1) THRU 402.4 (37) OR
 2014 FBC-RES. SEC. G2413.
  
 5.SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 6.SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014
 FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G
 2407.
  
 7.INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM ON
 THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 8.SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER 2014 FBC-FUEL GAS
 SECS. 502 THRU 505. OR 2014 FBC-RES. SEC.G2426.
  
 9.SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 THE FUEL GAS CODE CAN BE REVIEWED AT
 WWW.FLORIDABUILDING.ORG
  
 ANY QUESTIONS REGARDING THESE REQUIREMENTS MAY BE
 REFERRED TO THE CHIEF PLUMBING INSPECTOR AT
 561-805-6692.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-06 Cont ID  
Sent By tklarge Date 2016-04-06 Time 04:26 Rev Time 0.00
Received By tklarge Date 2016-03-29 Time 12:32 Sent To  
Notes
2016-03-30 12:33:03RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-27 Cont ID  
Sent By tklarge Date 2016-03-27 Time 03:11 Rev Time 0.00
Received By tklarge Date 2016-03-25 Time 14:03 Sent To  
Notes
2016-03-25 14:04:04RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-03 Cont ID  
Sent By tklarge Date 2016-03-03 Time 06:44 Rev Time 0.00
Received By tklarge Date 2016-03-01 Time 10:26 Sent To  
Notes
2016-03-02 10:27:05RESUB ROUTED TO TKLARGE