Plan Review Details - Permit 16010815
Plan Review Stops For Permit 16010815
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By shill Date 2016-02-09 Time 16:09 Rev Time 0.00
Received By shill Date 2016-02-03 Time 10:56 Sent To FIRE
Notes
2016-02-03 10:57:37****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 5TH EDITION EXISTING BUILDING 1106, ADDITIONS TO
 EXISTING BUILDINGS TO COMPLY WITH THE REQUIREMENTS OF
 TEH FBC, ENERGY CONSERVATION.
  
 FBC 5TH EDITION ENERGY CONSERVATION R101.5, ENERGY
 CALCS REQUIRED.
  
 2. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISO - BEDROOM TO STAY OPEN TO THE ENCLOSED LOGGIA
 (EMERGENCY ESCAPE AND RESCUE OPENING CANNOT BE BLOCKED)
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By vperez Date 2016-02-11 Time 13:30 Rev Time 0.00
Received By vperez Date 2016-02-11 Time 13:29 Sent To  
Notes
2016-02-11 13:53:18INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA RES BUILDING CODE 2014 5TH EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. PLEASE PROVIDE AND SHOW ON DRAWING THE RECEPTACLE
 OUTLETS NOW REQUIRED FOR WALL SPACE DUE TO ENCLOSING
 AREA. COMPLY WITH FBC RES- SEC E39012.1 AND 2.2
 2. SHOW AND PROVIDE THE REQUIRED LIGHTING OUTLETS PER
 FBC RES- SEC E3903.2 AND .3. INTERIOR AND EGRESS
 LOCATIONS
 3. PROVIDE A NOTE TO COMPLY WITH AFCI PROTECTION FOR
 BRANCH CIRCUITS AND TAMPER RESISTANT RECEPTACLE PER FBC
 RES- SEC E3902.12 AND E4002.14
 4. SEE FBC RES 314 SMOKE ALARM REQUIREMENTS PER
 ALTERATION. PROVIDE OR SHOW EXISTING SMOKE DETECTORS TO
 COMPLY. SEE EXCEPTION 314.4-3 FOR EASE OF COMPLIANCE.
 5. FURTHER COMMENTS MAT FOLLOW UPON RESUBMITTAL.
 6. ELECTRICAL PERMIT REQUIRED
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-02-11 Cont ID  
Sent By shill Date 2016-02-11 Time 16:02 Rev Time 0.00
Received By pleduc Date 2016-02-11 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-12 Cont ID  
Sent By vperez Date 2016-02-12 Time 10:57 Rev Time 0.00
Received By ccole Date 2016-02-11 Time 13:53 Sent To  
Notes
2016-02-11 17:28:212/11 TO CCOLE DESK
  
2016-02-11 13:54:04SENT TO SAM 2/11
2016-02-11 12:27:342/11 TO VAPEREZ DESK
  
2016-02-09 16:10:052/9 TO FIRE
  
  
2016-02-03 10:15:182/3 ON SH DESK
  
2016-01-27 09:16:21GIVEN TO SKENNEDY

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2016-02-03 Cont ID  
Sent By shill Date 2016-02-03 Time 10:15 Rev Time 0.00
Received By shill Date 2016-02-03 Time 10:15 Sent To  
Notes
2016-02-03 10:16:11MU 2015-22259
 RECEIPT #2015-0921-296

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By ccole Date 2016-02-12 Time 10:37 Rev Time 0.00
Received By ccole Date 2016-02-12 Time 10:37 Sent To  
Notes
2016-02-12 10:55:181ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 316010815
 2/12/16
  
 1) THE PERMIT APPLICATION AND PLANS WERE FORWARDED TO
 ME FOR MECHANICAL REVIEW BECAUSE A NEW ADDITION AT THE
 REAR OF THE BUILDING HAS BEEN CONSTRUCTED. PLEASE REFER
 TO SECTION 202 DEFINITIONS FBC-14 ENERGY CONSERVATION:
 ADDITION. AN EXTENSION OR INCREASE IN THE CONDITIONED
 SPACE FLOOR AREA OR HEIGHT OF A BUILDING OR STRUCTURE.
 AS STATED IN SECTIION R101.4.3 A NEW RESIDENTIAL
 ADDITION SHALL CONFORM TO THE PROVISIONS OF THE ENERGY
 CODE AS THEY RELATE TO NEW CONSTRUCTION. IN ORDER TO
 SHOW COMPLIANCE AS REQUIRED THE PLANS MUST BE REVISED
 TO SHOW COMPONENTS OF THE ADDITION'S THERMAL ENVELOPE
 AND MEP SYSTEMS, AND DOCUMENTATION OF ENERGY EFFICIENCY
 COMPLIANCE USING EITHER THE PRESCRIPTIVE OR PERFORMANCE
 BASED METHOD SHALL BE SUBMITTED. PLEASE SEE TABLE
 R101.5.1 AND SUBMIT DUPLICATE COPIES OF FORM R402 OR
 FORM R405..
 2) ALTHOUGH A NEW AC SYSTEM IS NOT SHOWN ON THE PLANS,
 DUE TO THE INCREASE IN CONDTIIONED FLOOR AREA, PLEASE
 PROVIDE AC COOLING AND HEATING CALCULATIONS AS OUTLINED
 IN SECTION R403.6.1.1. THE CALCULATIONS MUST INDICATE
 THAT THE EXISTING SYSTEM IS CAPABLE OF SUPPORTING THE
 ADDED LOAD, OR THE INSTALLATION OF A LARGER CAPACITY OR
 SUPPLEMENTAL SYSTEM MAY BE REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  