Plan Review Details - Permit 16010805
Plan Review Stops For Permit 16010805
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-16 Cont ID  
Sent By jwitmer Date 2016-03-16 Time 06:13 Rev Time 0.00
Received By jwitmer Date 2016-03-16 Time 05:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-05 Cont ID  
Sent By jwitmer Date 2016-02-05 Time 09:51 Rev Time 0.00
Received By jwitmer Date 2016-02-05 Time 08:13 Sent To  
Notes
2016-02-05 09:50:58BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010805
 ADD: 1645 PALM BEACH LAKES SUITE # 1050
 CONT: CHANDLER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 05/2016
 ACTION: DENIED
  
 1) SHEET A-2 VERSES A-3. INDICATED ON SHEET A-2 IN THE
 WALL LEGEND IS THE WALL TYPE FOR A 1-HOUR FIRE RATED
 PARTITION. SHEET A-2 SHOWS VARIOUS NEW WALLS WITHIN THE
 TENANT SPACE WITH A WALL DETAIL OF 1/A3 WHICH INDICATES
 THIS TYPE OF WALL AS A 1-HOUR FIRE RATED PARTITION. THE
 DESIGNER CAN DESIGN OVER AND ABOVE THE MINIMUM CODE, IF
 THIS THE ENTENT THEN THE DOORS WITHIN THE RATED WALL
 WILL ALSO NEED TO COMPLY WITH OPENING PROTECTIVES FOUND
 UNDER 2014 FBC-B TABLE716.5.
  
 2) THE COMBINED AREA OF SUITE 1050 IS NOW 6098 OR
 6098/100= 61 OCCUPANTS. THE FRONT ENTRY DOORS SWING,
 SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL WHERE
 SERVING A ROOM OR AREA CONTAINING AN OCCUPANT LOAD OF
 50 OR MORE PERSONS OR A GROUP H OCCUPANCY.2014 FBC-B
 1008.1.2. NEW WORK SHALL NOT CREATE A NONCONFORMITY.
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3) SHEET A-3 THE BREAKROOM # 114 SHOWS A MICROWAVE ON A
 SHELF APPROXIMATELY 5 FEET ABOVE FINISH FLOOR. PLEASE
 REVIEW THE 2014 FBC-ACCESSIBILITY CODE FOR OPERABLE
 PARTS:
 309.1 GENERAL. OPERABLE PARTS SHALL COMPLY WITH 309.
  
 309.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR OR GROUND SPACE COMPLYING WITH 305 SHALL
 BE PROVIDED.
  
 309.3 HEIGHT.
 OPERABLE PARTS SHALL BE PLACED WITHIN ONE OR MORE OF
 THE REACH RANGES SPECIFIED IN 308.
  
 309.4 OPERATION.
 OPERABLE PARTS SHALL BE OPERABLE WITH ONE HAND AND
 SHALL NOT REQUIRE TIGHT GRASPING, PINCHING, OR TWISTING
 OF THE WRIST. THE FORCE REQUIRED TO ACTIVATE OPERABLE
 PARTS SHALL BE 5 POUNDS (22.2 N) MAXIMUM.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-15 Cont ID  
Sent By rlecky Date 2016-03-15 Time 14:07 Rev Time 0.00
Received By rlecky Date 2016-03-15 Time 13:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By rlecky Date 2016-02-08 Time 14:06 Rev Time 0.00
Received By rlecky Date 2016-02-08 Time 13:51 Sent To  
Notes
2016-02-08 14:06:52PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE A FEEDER DETAIL AND SUMMARY LOAD CALCULATION
 FOR THIS OCCUPANCY. NEC 215.5
  
 PROVIDE A SAFETY LABELING SCHEDULE FOR FLASH PROTECTION
 FOR THE SERVICE, PANEL BOARDS AND MAIN DISCONNECTING
 MEANS. NEC 110.16, 110.22
  
 PROVIDE A DIMENSIONED DETAIL FOR THE ELECTRIC EQUIPMENT
 SHOWING THE LOCATION AND ALL SAFETY CLEARANCES WITH
 ADEQUATE HEAD ROOM. NEC 110.26
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By scaldero Date 2016-03-14 Time 11:41 Rev Time 0.00
Received By scaldero Date 2016-03-14 Time 11:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-02-16 Cont ID  
Sent By scaldero Date 2016-02-16 Time 12:00 Rev Time 0.00
Received By scaldero Date 2016-02-16 Time 11:56 Sent To  
Notes
2016-02-16 12:00:33PERMIT #16010805
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) SEE COMMENTS UNDER BUILDING PLAN REVIEW. DRAWINGS
 WILL BE STAMPED, INITIALED, AND DATED BY THE FIRE
 DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS HAVE BEEN
 SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-16 Cont ID  
Sent By   Date 2016-03-16 Time 6:14 Rev Time 0.00
Received By lmarchan Date 2016-03-09 Time 13:32 Sent To  
Notes
2016-03-09 13:33:00C18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-19 Cont ID  
Sent By shill Date 2016-02-19 Time 13:24 Rev Time 0.00
Received By shill Date 2016-01-26 Time 11:59 Sent To  
Notes
2016-01-26 11:59:25C06

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-02-05 Cont ID  
Sent By jwitmer Date 2016-02-05 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2016-02-05 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-15 Cont ID  
Sent By ccole Date 2016-03-15 Time 15:17 Rev Time 0.00
Received By ccole Date 2016-03-15 Time 15:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-05 Cont ID  
Sent By ccole Date 2016-02-05 Time 13:33 Rev Time 0.00
Received By ccole Date 2016-02-05 Time 13:33 Sent To  
Notes
2016-02-05 13:39:431ST REVIEW: FBC 2014 MECHANICAL & EXISTING BUILDING
 CODE
 PERMIT #16010805
 2/5/16
  
 1) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED NEW TENANT SPACE PER SECTION 809.2 FBC-14
 EXISTING BUILDING CODE AND TABLE 403.3 FBC-14
 MECHANICAL.
 2) THE VAV SCHEDULE INDICATES VAV-12 BUT IT IS NOT
 SHOWN IN THE LAYOUT PLAN. VAV-8 IS SHOWN IN THE LAYOUT
 PLAN BUT NOT IN THE SCHEDULE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-30 Cont ID  
Sent By tklarge Date 2016-01-30 Time 08:10 Rev Time 0.00
Received By tklarge Date 2016-01-30 Time 07:49 Sent To  
Notes
***NONE***