Plan Review Details - Permit 16010798
Plan Review Stops For Permit 16010798
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By cthroop Date 2016-03-14 Time 16:06 Rev Time 0.00
Received By cthroop Date 2016-03-14 Time 16:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-02-23 Cont ID  
Sent By cthroop Date 2016-02-23 Time 15:41 Rev Time 0.00
Received By cthroop Date 2016-02-23 Time 14:29 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By skennedy Date 2016-03-14 Time 15:34 Rev Time 0.00
Received By skennedy Date 2016-03-14 Time 15:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-22 Cont ID  
Sent By rlecky Date 2016-02-22 Time 13:16 Rev Time 0.00
Received By rlecky Date 2016-02-22 Time 12:34 Sent To  
Notes
2016-02-22 13:22:30PROVIDE A 20 AMPERE BRANCH CIRCUIT FOR THE NEW
 BATHROOM. NEC 210.11 (C) (3); FBC R E3703.4
  
 THE ELECTRIC PANEL CANNOT BE LOCATED IN A BATHROOM. NEC
 240.24 (E); FBC R E3705.7
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
 561-373-3701
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By skennedy Date 2016-03-14 Time 15:34 Rev Time 0.00
Received By skennedy Date 2016-03-14 Time 15:34 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-01-31 Cont ID  
Sent By tklarge Date 2016-01-31 Time 04:02 Rev Time 0.00
Received By tklarge Date 2016-01-31 Time 04:00 Sent To  
Notes
2016-01-31 04:02:10A SEPARATE PERMIT IS REQUIRED FOR THE GAS INSTALLATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By cthroop Date 2016-03-14 Time 16:06 Rev Time 0.00
Received By cthroop Date 2016-03-07 Time 09:47 Sent To  
Notes
2016-03-08 09:48:06R04

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-23 Cont ID  
Sent By cthroop Date 2016-02-23 Time 14:29 Rev Time 0.00
Received By cthroop Date 2016-01-26 Time 09:50 Sent To  
Notes
2016-01-27 09:50:54R03

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By skennedy Date 2016-03-14 Time 15:34 Rev Time 0.00
Received By skennedy Date 2016-03-14 Time 15:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-23 Cont ID  
Sent By skennedy Date 2016-02-23 Time 14:16 Rev Time 0.00
Received By skennedy Date 2016-02-23 Time 14:12 Sent To  
Notes
2016-02-23 14:19:111ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL/EXISTING
 BUILDING
  
 FBC- 107.3.5.3 ? PROVIDE A MECHANICAL PLAN TO SHOW
 SUPPLY DUCTS PER FBC-R M16 & BATH EXHAUST PER FBC-R
 M15.
  
 FBCE-R101.5.1.1 BUILDING THERMAL ENVELOPE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R402
 SHALL BE SUBMITTED TO THE BUILDING OFFICIAL TO
 DEMONSTRATE CODE COMPLIANCE BY THIS METHOD.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 R403.6.1 EQUIPMENT SIZING.
 HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS.
  
 R403.6.1.1 COOLING EQUIPMENT CAPACITY.
 COOLING ONLY EQUIPMENT SHALL BE SELECTED SO THAT ITS
 TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED TOTAL
 LOAD, BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE
 TOTAL LOAD CALCULATED ACCORDING TO THE PROCEDURE
 SELECTED IN SECTION 403.6, OR THE CLOSEST AVAILABLE
 SIZE PROVIDED BY THE MANUFACTURER?S PRODUCT LINES. THE
 CORRESPONDING LATENT CAPACITY OF THE EQUIPMENT SHALL
 NOT BE LESS THAN THE CALCULATED LATENT LOAD.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By skennedy Date 2016-03-14 Time 15:34 Rev Time 0.00
Received By skennedy Date 2016-03-14 Time 15:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-31 Cont ID  
Sent By tklarge Date 2016-01-31 Time 04:00 Rev Time 0.00
Received By tklarge Date 2016-01-31 Time 03:39 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By jroach Date 2016-03-14 Time 14:55 Rev Time 0.00
Received By jroach Date 2016-03-14 Time 14:55 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By jroach Date 2016-02-12 Time 10:44 Rev Time 0.00
Received By jroach Date 2016-02-08 Time 15:36 Sent To  
Notes
2016-02-12 10:45:01ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.12.2016
 PERMIT NO.: 16010798
 ADDRESS: 327 POTTER ROAD
 CONTRACTOR/CONTACT: JOHN KERN
 TELEPHONE NO.: 561.762.4849
 SCOPE OF REVIEW: PORCH ADDITION, GARAGE, BATHROOM
 REMODEL.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-486 OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS, SINGLE FAMILY RESIDENCES
 ARE REQUIRED TO PROVIDE TWO (2) OFF-STREET PARKING
 SPACES. WITH THE REMOVAL OF THE GARAGE AND THE STORAGE
 ADDITION, IT APPEARS THAT THERE WILL NOT BE SUFFICIENT
 SPACE TO ACCOMMODATE TWO (2) VEHICLES. EACH SPACE WOULD
 BE AT LEAST 18 FEET IN LENGTH, REQUIRING A 36 FOOT LONG
 DRIVEWAY.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  
2016-02-03 15:17:432-3-16