Plan Review Details - Permit 16010797
Plan Review Stops For Permit 16010797
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-14 Cont ID  
Sent By jwitmer Date 2016-03-14 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2016-03-14 Time 06:58 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-05 Cont ID  
Sent By jwitmer Date 2016-02-05 Time 06:46 Rev Time  
Received By jwitmer Date 2016-02-05 Time 06:01 Sent To  
Notes
2016-02-05 06:45:41BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010797
 ADD: 701 NORTHPOINT PKY. SUITE 150
 CONT: CHANDLIER
 TEL: 791-6934
 E-MAIL: JOHN @BUILDERCCC.COM
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. FEB. 05/2016
 ACTION: DENIED
  
 1) SHEET A-2:
  
 1A) THE OFFICE 104 (2) OFFICES 104) AND CONFERENCE ROOM
 # 107 BOTH SHOW A DETAIL 1/ A-3 WHICH IS A 1-HOUR FIRE
 RATED WALL. IN THE OFFICE DOORWAY A DOOR IDENTIIFED AS
 A B TYPE DOOR IS SHOWN. ONSHEET A-3 THE B TYPE DOORWAY
 IS SHOWN AS A SOLID CORE WOOD DOOR WITH A 3/8 INCH
 TEMPERED GLASS. PLEASE PROVIDE COMPLIANCE WITH SECTION
 TABLE 716.5 OPENING FIRE PROTECTION ASSEMBLIES, RATINGS
 AND MARKINGS & TABLE 716.6 FIRE WINDOW ASSEMBLY FIRE
 PROTECTION RATINGS.
  
 1B) IN THE CONFERENCE ROOM THE DOOR IS IDENTIFIED AS A
 DOOR TYPE C BUT IS NOT SHOWN ON THE DOOR SCHEDULE FOUND
 ON SHEET A3. THE FLOOR PLANS DO APPEAR TO BE THE SAME
 CONFIGURATION AS THE OFFICE DOOR AND SIDELIGHT IN
 OFFICE 104. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-09 Cont ID  
Sent By vperez Date 2016-03-09 Time 10:18 Rev Time 0.00
Received By vperez Date 2016-03-09 Time 10:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By vperez Date 2016-02-12 Time 07:48 Rev Time 0.00
Received By vperez Date 2016-02-12 Time 07:48 Sent To  
Notes
2016-02-12 08:02:31INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE UPDATE REFERENCE ON ELECTRICAL SPECS TO
 INDICATE NEW SECTIONS OF THE FLORIDA ENERGY
 CONSERVATION CODE 2014 5TH EDITION. SECTIONS HAVE BEEN
 MOVED OVER TO FBC EC 405.7 NOT SECTION 505
 2. PROVIDE A NOTE TO INDICATE THE CARD READERS AND
 DATA/PHONES TO BE ON SEPARATE PERMIT. A NOTE WILL
 SUFFICE. FBC 107.
 3. PROVIDE A NOTE TO MAINTAIN FIRE RATING ON DEMISING
 WALLS. NEC 300.21
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By pleduc Date 2016-03-07 Time   Rev Time 0.00
Received By pleduc Date 2016-03-07 Time 15:43 Sent To  
Notes
2016-03-07 15:51:18THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. SHEET T - AN INCORRECT REFERENCE TO THE FIRE CODE
 WAS NOTED; HOWEVER, IT DOES NOT APPEAR TO HAVE AN
 IMPACT ON THE SUBMITTAL. FURTHER REVIEW MAY BE
 WARRANTED BY YOUR DESIGNERS OR CONTRACTORS.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
  
  
 PLEASE UPDATE YOUR RECORDS FOR FUTURE SUBMISSIONS.
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-01-29 Cont ID  
Sent By pleduc Date 2016-01-29 Time   Rev Time 0.00
Received By pleduc Date 2016-01-29 Time 11:30 Sent To  
Notes
2016-01-29 13:02:44THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1. SHEET A - 2, INDICATES TWO DOORS LABELED AS "C". THE
 DOOR SCHEDULE DOES NOT INDICATE A "C" DOOR DESCRIPTION.
 PLEASE CORRECT.
  
 2. SHEET 3 - 1, INDICATES CARD READERS ON EXIT DOORS,
 PROVIDE NOTE INDICATING THAT THEY SHALL DELAY OR
 RESTRICT EGRESS.
  
 3. SHEET 3 - 1, PROVIDE A NOTE INDICATING THAT FIRE
 ALARM WORK SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-14 Cont ID  
Sent By jwitmer Date 2016-03-14 Time 07:31 Rev Time 0.00
Received By jwitmer Date 2016-03-03 Time 12:46 Sent To  
Notes
2016-03-09 10:19:163/9 TO B11
2016-03-03 12:46:49B11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-12 Cont ID  
Sent By lmarchan Date 2016-02-12 Time 09:53 Rev Time 0.00
Received By lmarchan Date 2016-02-12 Time 08:02 Sent To  
Notes
2016-02-12 08:03:15TO CAROLINE/LAURA
2016-01-26 15:35:35B06

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-10 Cont ID  
Sent By ccole Date 2016-03-10 Time 17:13 Rev Time 0.00
Received By ccole Date 2016-03-10 Time 17:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-05 Cont ID  
Sent By ccole Date 2016-02-05 Time 13:47 Rev Time 0.00
Received By ccole Date 2016-02-05 Time 13:47 Sent To  
Notes
2016-02-05 13:50:571ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16010797
 2/5/16
  
 1) PROVIDE EXHAUST DUCT RUN DETAILS FOR CF-1 INCLUDING
 TYPE AND SIZE OF DUCT, RUN LENGTH AND TERMINATION
 LOCATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-31 Cont ID  
Sent By tklarge Date 2016-01-31 Time 03:38 Rev Time 0.00
Received By tklarge Date 2016-01-31 Time 03:14 Sent To  
Notes
***NONE***