Plan Review Details - Permit 16010623
Plan Review Stops For Permit 16010623
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-04-11 Cont ID  
Sent By skennedy Date 2016-04-11 Time 10:53 Rev Time 0.00
Received By skennedy Date 2016-04-11 Time 10:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 09:18 Rev Time 0.00
Received By jwitmer Date 2016-03-15 Time 08:05 Sent To  
Notes
2016-03-15 09:18:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010623
 ADD: 716 N. SAPODILLA AVE.
 CONT: NUJAK DEVELOPMENT
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. MARCH 15/2016
 ACTION: DENIED
  
 1-8) COMPLIED.
  
 8) PLEASE PROVIDE AN ACCESSIBLE DOOR TO THE RESTROOM,
 PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE 404.2.4 MANEUVERING CLEARANCES, SEE FIGURE
 404.2.4.1 (E) & (H).
  
  
 9) THE RESPONSE TO COMMENT INDICATES THERE IS A 4 INCH
 DROP FROM THE INTERIOR FLOOR TO THE EXTERIOR SIDEWALKS
 AT THE FRONT ENTRY. PLEASE PROVIDE FOR AN ACCESSIBLE
 ENTRY TO THE (2) TENANT SPACES. NOTE IF THE SLOPE IS
 GREATER THAN 1;20 IT IS CONSIDERED A RAMP. AT THE 1:20
 THE SLOPE WOULD BE CONSIDERED GRADE. THE 1:20 SLOPE
 WOULD HAVE TO BE SLOPED NOT ONLY TO THE FRONT BUT TO
 THE SIDES AS WELL.
 PLANS DO NOT INDICATE IF THE ENTRANCE IS AN ACCESSIBLE
 LEVEL ENTRY WAY. 107.2.1.3 ADDITIONAL INFORMATION IS
 REQUIRED. 2014 FBC-ACCESSIBILIRTY CODE 202.4.2
 ACCESSIBLE FEATURES IN THE EVENT OF DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS
  
 10) THE VALUE OF THE PROVECT IS INDICATED AS $2,500.00
 DOLLARS. THIS VALUE IS LOW FOR THE NEW DOORS AND
 INTERIOR WALL STUDDING, DRYWALL, ELECTRICAL ETC...
 PLEASE ALSO UPDATE THE VALUE OF THE PERMIT.
  
 11) AWNING, NOTICE BY SEPARATE PERMIT.
  
 12) GRAB BARS ARE DIMENSIONED TO THE CENTERLINE 33-36
 INCHES, PLEASE NOTE THAT THE 2014 ACCESSIBLITY CODE
 DIMENSIONS TO THE TOP OF THE GRIPPING SURFACE. 2014
 FBC-ACCESSIBILITY CODE 609.4.
  
 13) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-03 Cont ID  
Sent By jwitmer Date 2016-02-03 Time 07:15 Rev Time 0.00
Received By jwitmer Date 2016-02-03 Time 06:30 Sent To  
Notes
2016-02-03 06:49:31BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010623
 ADD: 716 N. SAPODILLA AVE.
 CONT: NUJAK DEVELOPMENT
 TEL: 561-320-2566
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. FEB.03/2016
 ACTION: DENIED
  
 1) PLEASE PROVIDE A LIFE SAFETY PLAN SHOWING THE DINING
 ROOM LAYOUT OF TABLES AND CHAIRS EGRESS AISLES TO THE
 EXIT AS WELL AS THE COMMERCIAL KITCHEN LAYOUT.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS;
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING.
  
 2) SHEET A1.00 SHOWS ON THE INTERIOR OF THE TENANT
 SPACE ONLY NO SEATING. FOR A RESTARAUNT. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 226.1 REQUIRES DINING
 SURFACES ARE PROVIDED FOR THE CONSUMPTION OF FOOD OR
 DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES AND
 STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902
  
 3) NOTE IF THERE IS EXTERIOR SEASONAL SEATING THEN
 THOUGHS SEATS WILL ALSO NEED TO BE CONSIDERED IN THE 5
 % OF THE OVERAL SEATING. COMPLIANCE WITH 226.2 OF THE
 ACCESSIBILITY CODE WOULD ALSO THEN BE A ISSUE. 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4) THE DINING TABLE TOPS FOR THE ACCESSIBLE TABLES WILL
 NEED TO COMPLY WITH: 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES (710 MM)
 MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 5) PLANS HAVE TO SHOW WHERE THE RESTARAUNT KITCHEN IS
 LOCATED, 2014 FBC-B 1210.4 TOILET ROOM LOCATION. TOILET
 ROOMS SHALL NOT OPEN DIRECTLY INTO A ROOM USED FOR THE
 PREPARATION OF FOOD FOR SERVICE TO THE PUBLIC.
  
 6) SUBMITTED DOOR PRODUCT APPROVAL, CORAL 213 SERIES
 ENTRANCE DOOR. THIS APPROVAL DOES NOT HAVE A COVERSHEET
 ATTACHED IDENTIFYING IF IT IS A FLORIDA APPROVAL AND TO
 THE CURRENT CODE. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010
 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS
 THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
  
 7) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.1 THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) PLEASE PROVIDE AN ACCESSIBLE DOOR TO THE RESTROOM,
 PLEASE PROVIDE COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE 404.2.4 MANEUVERING CLEARANCES, SEE FIGURE
 404.2.4.1 (E) & (H).
  
 9) PLANS DO NOT INDICATE IF THE ENTRANCE IS AN
 ACCESSIBLE LEVEL ENTRY WAY. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. 2014 FBC-ACCESSIBILIRTY CODE
 202.4.2 ACCESSIBLE FEATURES IN THE EVENT OF
 DISPROPORTIONALITY.
 WHEN THE COST OF ALTERATIONS NECESSARY TO MAKE THE PATH
 OF TRAVEL TO THE ALTERED AREA FULLY ACCESSIBLE IS
 DISPROPORTIONATE TO THE COST OF THE OVERALL ALTERATION,
 THE PATH OF TRAVEL SHALL BE MADE ACCESSIBLE TO THE
 EXTENT THAT IT CAN BE MADE ACCESSIBLE WITHOUT INCURRING
 DISPROPORTIONATE COSTS. IN CHOOSING WHICH ACCESSIBLE
 ELEMENTS TO PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE
 ELEMENTS THAT WILL PROVIDE THE GREATEST ACCESS, IN THE
 FOLLOWING ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (III) AT LEAST
 ONE ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS
  
 10) AWNING, NOTICE BY SEPARATE PERMIT.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-04-04 Cont ID  
Sent By vperez Date 2016-04-04 Time 10:54 Rev Time 0.00
Received By vperez Date 2016-04-04 Time 10:54 Sent To  
Notes
2016-04-04 10:55:06SENT TO SK 4/4

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-15 Cont ID  
Sent By vperez Date 2016-03-15 Time 11:22 Rev Time 0.00
Received By vperez Date 2016-03-15 Time 11:04 Sent To  
Notes
2016-03-15 11:24:492ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 PENDING COMMENTS NOT ADDRESSED:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE AND
 DATA. A NOTE WILL SUFFICE.
 2. PLEASE CLARIFY IF THERE ARE EXISTING ELECTRICAL
 SERVICES AT THIS LOCATION AS A NEW SERVICE IS BEING
 SHOWN FOR THIS PROJECT. PER NEC 230.2; SPECIAL
 PERMISSION REQUIRED BY AHJ TO BE SUBMITTED IN WRITING.
 COMMENTS TO FOLLOW UPON RE-REVIEW OF ELECTRICAL SERVICE
 SHOWN.
 5. PROVIDE A PANEL SCHEDULE REFLECTING ALL PERTINENT
 INFORMATION: FOR EXAMPLE, AIC RATING ETC. FBC 107.
 7. PROVIDE SPEC SHEETS FOR INSTANT- HOT WH SELECTED TO
 VERIFY LOADS, FBC 107
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By vperez Date 2016-02-11 Time 10:13 Rev Time 0.00
Received By vperez Date 2016-02-11 Time 10:13 Sent To B
Notes
2016-02-11 10:13:30INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO PHONE AND
 DATA. A NOTE WILL SUFFICE.
 2. PLEASE CLARIFY IF THERE ARE EXISTING ELECTRICAL
 SERVICES AT THIS LOCATION AS A NEW SERVICE IS BEING
 SHOWN FOR THIS PROJECT. PER NEC 230.2 SPECIAL
 PERMISSION REQUIRED BY AHJ TO BE SUBMITTED IN WRITING.
 COMMENTS TO FOLLOW UPON RE-REVIEW OF ELECTRICAL SERVICE
 SHOWN.
 3. SEE MECHANICAL COMMENTS REGARDING EQUIPMENT FOR A
 COMPLETE REVIEW.
 4. PLEASE REVIEW DEMAND LOADS TO BE IN COMPLIANCE WITH
 NEC 220 REQUIREMENTS, PROVIDE A COMPLETE CALCULATION.
 5. PROVIDE A PANEL SCHEDULE REFLECTING ALL PERTINENT
 INFORMATION: FOR EXAMPLE, AIC RATING ETC. FBC 107.
 6. ID THE FLOOR PLAN WITH CIRCUIT DESIGNATION. FBC 107.
 7. PROVIDE SPEC SHEETS FOR INSTANT- HOT WH SELECTED TO
 VERIFY LOADS, FBC 107
 8. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING
 THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2016-03-16 Cont ID  
Sent By scaldero Date 2016-03-16 Time 08:42 Rev Time 0.00
Received By scaldero Date 2016-03-16 Time 08:41 Sent To  
Notes
2016-03-16 08:42:18PERMIT # 16010623
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-26 Cont ID  
Sent By scaldero Date 2016-01-26 Time 12:45 Rev Time 0.00
Received By scaldero Date 2016-01-26 Time 12:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-04-11 Cont ID  
Sent By skennedy Date 2016-04-11 Time 10:53 Rev Time 0.00
Received By skennedy Date 2016-04-01 Time 13:30 Sent To  
Notes
2016-04-01 13:30:34B31

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-30 Cont ID  
Sent By skennedy Date 2016-03-17 Time 09:16 Rev Time 0.00
Received By skennedy Date 2016-03-10 Time 16:05 Sent To  
Notes
2016-03-10 16:06:09B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-11 Cont ID  
Sent By cpuell Date 2016-02-11 Time 10:43 Rev Time 0.00
Received By cpuell Date 2016-01-20 Time 09:42 Sent To  
Notes
2016-01-21 09:42:24B29

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-03-15 Cont ID  
Sent By jwitmer Date 2016-03-15 Time 08:37 Rev Time 0.00
Received By jwitmer Date 2016-03-15 Time 08:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-04-11 Cont ID  
Sent By skennedy Date 2016-04-11 Time 10:52 Rev Time 0.00
Received By skennedy Date 2016-04-11 Time 10:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-17 Cont ID  
Sent By ccole Date 2016-03-17 Time 09:51 Rev Time 0.00
Received By ccole Date 2016-03-17 Time 09:51 Sent To  
Notes
2016-03-17 09:53:292ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010623
 3/17/16
  
 1) COMMENTS #3 & 4 FROM THE 1ST REVIEW STILL EXIST. I
 AM REPRINTING THEM BELOW. ADDITIONALLY, PLEASE SUBMIT
 AC CHANGE-OUT FORMS FOR THE REPLACED THROUGH-THE-WALL
 AC SYSTEMS, AND PROVIDE EQUIPMENT SCHEDULES ON THE
 PLANS.
  
 1ST REVIEW:
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED TENANT SPACES. SHOW THE REQUIRED AND PROVIDED
 CFM'S OF OUTDOOR AIR.
 4) ENERGY COMPLIANCE IS REQUIRED IN ACCORDANCE WITH
 SECTION C101.4.3 FBC-14 ENERGY CONSERVATION. SEE THE
 DEFINITION OF RENOVATED BUILDING- SECTION 202. PLEASE
 NOTE THE NEW EXTERIOR DOORS MUST MEET OR EXCEED THE
 CURRENT EFFICIENCY RATINGS ACCORDING TO THE CODE.
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-01 Cont ID  
Sent By ccole Date 2016-02-01 Time 14:34 Rev Time 0.00
Received By ccole Date 2016-02-01 Time 14:35 Sent To  
Notes
2016-02-01 14:46:131ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010623
 2/1/16
  
 1) PROVIDE TOILET EXHAUST FAN SCHEDULES.
 2) PROVIDE TOILET ROOM EXHAUST VENTILATION PLANS THAT
 INCLUDE THE THE TYPES AND SIZES OF EXHAUST FAN DUCTS,
 THE DUCT RUNS, AND TERMINATION LOCATIONS.
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING, AND
 PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 PROPOSED TENANT SPACES. SHOW THE REQUIRED AND PROVIDED
 CFM'S OF OUTDOOR AIR.
 4) ENERGY COMPLIANCE IS REQUIRED IN ACCORDANCE WITH
 SECTION C101.4.3 FBC-14 ENERGY CONSERVATION. SEE THE
 DEFINITION OF RENOVATED BUILDING- SECTION 202. PLEASE
 NOTE THE NEW EXTERIOR DOORS MUST MEET OR EXCEED THE
 CURRENT EFFICIENCY RATINGS ACCORDING TO THE CODE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-04-11 Cont ID  
Sent By skennedy Date 2016-04-11 Time 10:53 Rev Time 0.00
Received By skennedy Date 2016-04-11 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-17 Cont ID  
Sent By gjohnson Date 2016-03-17 Time 15:17 Rev Time 0.00
Received By gjohnson Date 2016-03-17 Time 15:17 Sent To  
Notes
2016-03-17 15:17:072ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. HORIZONTAL DRY VENTS ARE NOT ALLOWED THEY SHALL
 COMPLY WITH FBC PL SEC. 905.3 VENT CONNECTION TO
 DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.THE VENT BETWEEN TOILET AND LAV IS NOT REQUIRED IT
 MAY BE ELIMINATED TO COMPLY.
 2. SHOW DIMENSION FOR TOILET TO COMPLY WITH FBC PL
 604.2 LOCATION.
 THE WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES (405 MM) MINIMUM
 TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE WALL OR
 PARTITION, EXCEPT THAT THE WATER CLOSET SHALL BE 17
 INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM
 FROM THE SIDE WALL OR PARTITION IN THE AMBULATORY
 ACCESSIBLE TOILET COMPARTMENT SPECIFIED IN 604.8.2.
 WATER CLOSETS SHALL BE ARRANGED FOR A LEFT-HAND OR
 RIGHT-HAND APPROACH
 3. SHOW CLEAR FLOOR SPACE FOR TOILET TO COMPLY WITH FBC
 PL SEC.604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL
 4. SHOW CLEAR FLOW SPACE FOR LAV TO COMPLY WITH
 FBC PL 606.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-24 Cont ID  
Sent By tklarge Date 2016-01-24 Time 05:32 Rev Time 0.00
Received By tklarge Date 2016-01-24 Time 04:53 Sent To  
Notes
2016-01-24 05:13:401)SHT.A100 SHOWS CONTINUOUS GRAB BARS IN THE ACCESSIBLE
 TOILET ROOMS. GRAB BARS SHALL COMPLY WITH 2014
 FBC-ACCESS. SECS.604.5.1, 604.5.2, & 609. NOTE 11 ON
 A11 INDDICATES 24" & 36" GRAB BARS.CLARIFY.
 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
 604.5.2 REAR WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
 609.1 GENERAL.
 GRAB BARS IN TOILET FACILITIES AND BATHING FACILITIES
 SHALL COMPLY WITH 609.
 609.2 CROSS SECTION.
 GRAB BARS SHALL HAVE A CROSS SECTION COMPLYING WITH
 609.2.1 OR 609.2.2.
 609.2.1 CIRCULAR CROSS SECTION.
 GRAB BARS WITH CIRCULAR CROSS SECTIONS SHALL HAVE AN
 OUTSIDE DIAMETER OF 11/4 INCHES (32 MM) MINIMUM AND 2
 INCHES (51 MM) MAXIMUM.
 609.2.2 NON-CIRCULAR CROSS SECTION.
 GRAB BARS WITH NON-CIRCULAR CROSS SECTIONS SHALL HAVE A
 CROSS-SECTION DIMENSION OF 2 INCHES (51 MM) MAXIMUM AND
 A PERIMETER DIMENSION OF 4 INCHES (100 MM) MINIMUM AND
 4.8 INCHES (120 MM) MAXIMUM.
 609.3 SPACING.
 THE SPACE BETWEEN THE WALL AND THE GRAB BAR SHALL BE 1
 1/2 INCHES (38 MM). THE SPACE BETWEEN THE GRAB BAR AND
 PROJECTING OBJECTS BELOW AND AT THE ENDS SHALL BE 1 1/2
 INCHES (38 MM) MINIMUM. THE SPACE BETWEEN THE GRAB BAR
 AND PROJECTING OBJECTS ABOVE SHALL BE 12 INCHES (305
 MM) MINIMUM.
 EXCEPTION: THE SPACE BETWEEN THE GRAB BARS AND SHOWER
 CONTROLS, SHOWER FITTINGS, AND OTHER GRAB BARS ABOVE
 SHALL BE PERMITTED TO BE 1 1/2 INCHES (38 MM) MINIMUM.
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE.
 2) CLEARLY SHOW ON THE WATER RISER THAT BOTH LAVATORIES
 ARE SUPPLIED WITH HOT OR TEMPERED WATER, LIMITED TO 110
 DEGREES IN ACCORDANCE WITH THE 2014 FBC-PLUMBING
 SEC.607.1, 607.1.1, 607.1.2.
 3) SHOW THE NEW LAVATORY IN THE NEW ACCESSIBLE TOILET
 ROOM ON THE SANITARY RISER.
 4) THE SANITARY SHOWS A FLAT DRY VENT WHICH IS NOT
 PERMITTED PER THE PLUMBING CODE. THE VENT SHALL CONNECT
 TO THE HORIZONTAL DRAIN ABOVE THE CENTERLINE OF THE
 HORIZONTAL DRAIN PIPE. 2014 FBCP SEC.905.3.
 5) SHT. A100 - THE TYPICAL HANDICAP RESTROOM DETAIL
 SHOWS THE MINIMUM INSIDE DIMENSION AS 7'-6" AND THE
 PLAN VIEW SHOWS THE RESTROOM AS 7'-8" FROM THE INSIDE
 FACE OF THE WALL TO THE OUTSIDE FACE OF THE WALL AS
 7'-8". CLARIFY. SHOW THE THE INSIDE CLEAR DIMENSIONS OF
 THE ACCESSIBLE TOILET ROOMS.THE MINIMUM WIDTH WHEN THE
 THE PLUMBING FIXTURES ARE ON THE SAME WALL IS 85
 INCHES.86 INCHES ALLOWS FOR TOLERANCE.
 6) THE MANUF. SPECS/INSTALLATION MANUAL FOR THE
 TANKLESS WATER HEATER SHALL BE ONSITE FOR THE
 INSPECTOR.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  