Plan Review Details - Permit 16010620
Plan Review Stops For Permit 16010620
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-01-26 Cont ID  
Sent By tklarge Date 2016-01-26 Time 05:26 Rev Time 0.00
Received By tklarge Date 2016-01-26 Time 05:07 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-01-21 Cont ID  
Sent By tklarge Date 2016-01-21 Time 12:33 Rev Time 0.00
Received By tklarge Date 2016-01-21 Time 11:43 Sent To  
Notes
2016-01-21 12:33:111) THE GAS TABLE REFERENCED ON THE PLAN FOR THE CSST
 (402.4 (13) ) IS FOR SEMIRIDGID COPPER TUBING IN THE
 GAS CODE. CLARIFY
 2) THE GAS TABLE REFERENCED ON THE PLAN FOR THE PE PIPE
 (402.4 (19) ) IS FOR CSST IN THE GAS CODE.CLARIFY.
 3) PER TABLE 402.4 (21), THE MAXIMUM BTU LOAD ON A 0.5
 PSI 3/4" PE LINE AT 30 FT. IS 222,000 BTU'S. THE 3/4"
 PE LINE COMING FROM THE METER NEEDS TO BE INCREASED TO
 1".
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-26 Cont ID  
Sent By tklarge Date 2016-01-26 Time 05:26 Rev Time 0.00
Received By tklarge Date 2016-01-22 Time 09:34 Sent To  
Notes
2016-01-25 09:35:11RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-21 Cont ID  
Sent By tklarge Date 2016-01-21 Time 12:33 Rev Time 0.00
Received By tklarge Date 2016-01-20 Time 16:20 Sent To  
Notes
2016-01-20 16:20:35PLUMB <5K