Plan Review Stops For Permit 16010606 |
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
P |
Date |
2016-01-28 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-01-28 |
Time |
15:00 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-01-28 |
Time |
14:49 |
Sent To |
I |
|
Notes |
2016-01-28 15:05:03 | THOUGH NOT INCLUDED OR INDICATED ON THE APPROVED PLANS | | YOU SHALL PROVIDE: | | 2 SMALL APPLIANCE CIRCUITS | | 1 LAUNDRY CIRCUIT | | 1 DEDICATED GFCI 20 AMP CKT FOR THE MASTER BATH | | THE REQUIRED EXTERIOR LIGHTING AND RECEPTACLES. | | ALL WORK IS SUBJECT TO FIELD INSPECTOR'S APPROVAL AND | | SHALL COMPLY WITH THE 2011 NEC | | | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-01-28 |
|
|
Cont ID |
|
Sent By |
albarran |
Date |
2016-01-28 |
Time |
15:31 |
Rev Time |
0.00 |
Received By |
albarran |
Date |
2016-01-20 |
Time |
14:26 |
Sent To |
|
|
Notes |
2016-01-28 15:33:11 | 1/28/16 PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR | | NOTIFIED VIA EMAIL. FILE SENT TO SMALL READY BIN "A". | | MA | 2016-01-21 14:27:09 | ROUTED TO ELEC INBOX |
|
|
|