Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-12 Cont ID  
Sent By albarran Date 2016-02-12 Time 12:59 Rev Time 0.00
Received By albarran Date 2016-02-12 Time 12:11 Sent To I
Notes
2016-02-12 12:59:42CONDITIONAL APPROVAL FOR PERMIT 16010595
  
 COMPLIANCE W/NEC 230.70 THOUGH REQUIRED IS NOT CLEAR ON
 THE DRAWING. DISCONNECT REQUIRED.
 YOU SHALL PROVIDE THE INTER-SYSTEM BONDING TERMINAL
 REQUIRED IN NEC 250.94
 YOU SHALL INSTALL SMOKE DETECTORS AS REQUIRED IN
 FBC-R314 & 315
 WORK SUBJECT TO FIELD INSPECTOR?S APPROVAL. ADDITIONAL
 ITEMS MAY BE REQ'D.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-25 Cont ID  
Sent By albarran Date 2016-01-25 Time 18:53 Rev Time 0.00
Received By albarran Date 2016-01-25 Time 18:36 Sent To I
Notes
2016-01-25 18:55:14I SPOKE WITH THE EC AND ASKED HIM TO PROVIDE A FULL
 RISER DIAGRAM AND ON IT CIRCLE/MARK HIS SCOPE OF WORK.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-12 Cont ID  
Sent By albarran Date 2016-02-12 Time 13:02 Rev Time 0.00
Received By albarran Date 2016-02-09 Time 15:41 Sent To  
Notes
2016-02-12 13:02:442/12/16 PASSED ELECTRICAL REVIEW W/PROVISOS AS MARKED
 ON PLANS. CONTRACTOR NOTIFIED VIA EMAIL. SENT FILE TO
 SMALL READY BIN "S". MA
2016-02-09 15:41:29RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-25 Cont ID  
Sent By albarran Date 2016-01-25 Time 18:55 Rev Time 0.00
Received By albarran Date 2016-01-20 Time 09:33 Sent To  
Notes
2016-01-25 18:57:261/25/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA PHONE CALL. SENT FILE TO SMALL DENIED BIN
 "S". MA
2016-01-21 09:33:13ELEC <5K