Plan Review Details - Permit 16010555
Plan Review Stops For Permit 16010555
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-05 Cont ID  
Sent By cthroop Date 2016-08-05 Time 12:41 Rev Time 0.00
Received By cthroop Date 2016-08-05 Time 12:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-29 Cont ID  
Sent By cthroop Date 2016-07-29 Time 09:04 Rev Time 0.00
Received By cthroop Date 2016-07-29 Time 09:04 Sent To  
Notes
2016-07-29 09:07:29BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 ACTION: DENIED
 DATE: 7/29/16
  
 1. DESIGNER TO SIGN AND SEAL PLANS.
 2. PROVIDE DESIGN WIND LOADS PER FBC CHPT. 16 AND ASCE
 7-10.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-19 Cont ID  
Sent By cthroop Date 2016-02-19 Time 15:40 Rev Time 0.00
Received By cthroop Date 2016-02-19 Time 15:40 Sent To E
Notes
2016-02-19 15:43:05CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE DETAIL ON EXTERIOR WALL AT PROPOSED SIGN
 LOCATION.
 PROVIDE SPECS. FOR FASTENERS FOR WALL TYPE.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-04 Cont ID  
Sent By mvaldes Date 2016-08-04 Time 17:38 Rev Time 0.00
Received By mvaldes Date 2016-08-04 Time 17:29 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-28 Cont ID  
Sent By cthroop Date 2016-07-29 Time 09:04 Rev Time 0.00
Received By mvaldes Date 2016-07-28 Time 13:02 Sent To B
Notes
2016-07-28 13:51:31REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1) DESIGN PROFFESIONAL FOR A COMMERCIAL SIGN MUST BE
 EITHER BE A LICENSED ENGINEER OR ARCHITECT PER FLORIDA
 STATUE 471 & 481
  
 2) SIGN SHALL BE SUPPLIED BY A MINIMUM DEDICATED 20 AMP
 BRANCH CIRCUIT ACCORDING TO NEC 600.5(A). IF EXISTING
 PLEASE MARK ON PLANS !
 - SECOND REQUEST, NOT ADDRESSED.
  
 3) FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. PLEASE ADD A NOTE !
 - SECOND REQUEST, NOT ADDRESSED

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-22 Cont ID  
Sent By mvaldes Date 2016-02-22 Time 11:00 Rev Time 0.00
Received By mvaldes Date 2016-02-22 Time 11:00 Sent To  
Notes
2016-02-22 11:06:391ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  
  
  
 - NEC 600.5 A THE BRANCH CIRCUIT FOR A SIGN SHALL BE A
 DEDICATED 20 AMP CIRCUIT SERVING NO OTHER LOADS.
 - C405.2.4 EXTERIOR LIGHTING CONTROLS
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS..
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-05 Cont ID  
Sent By cthroop Date 2016-08-05 Time 12:41 Rev Time 0.00
Received By cthroop Date 2016-08-04 Time 13:24 Sent To  
Notes
2016-08-04 13:24:09RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-29 Cont ID  
Sent By cthroop Date 2016-07-29 Time 09:04 Rev Time 0.00
Received By cthroop Date 2016-07-27 Time 15:45 Sent To E
Notes
2016-07-27 15:45:35GIVEN TO AAPONTE
2016-07-26 14:03:21THE APPLICANT HAS RESUBMITTED THE PERMIT DUE TO NEW
 ZONING REGULATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-22 Cont ID  
Sent By mvaldes Date 2016-02-22 Time 11:07 Rev Time 0.00
Received By mvaldes Date 2016-01-19 Time 11:38 Sent To  
Notes
2016-02-12 15:40:52MISC 2 BOX
2016-01-20 11:38:24ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-26 Cont ID  
Sent By kmartin Date 2016-07-27 Time   Rev Time 0.00
Received By kmartin Date 2016-07-26 Time 14:02 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-12 Cont ID  
Sent By aaponte Date 2016-02-12 Time 15:38 Rev Time 0.00
Received By aaponte Date 2016-02-12 Time 15:38 Sent To  
Notes
2016-02-12 15:40:191. SIGN SHALL BE AFFIXED FLAT TO THE BUILDING FACADE.
 PLEASE INSTALL THE LETTERS DIRECLTY INTO THE FACADE
 WITHOUT THE RACEWAY.
 2. PLEASE INDICATE IF THERE ARE ANY OTHER SIGNS ALREADY
 INSTALLED ON THE FACADE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.