Plan Review Details - Permit 16010552
Plan Review Stops For Permit 16010552
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-08-05 Cont ID  
Sent By cthroop Date 2016-08-05 Time 09:02 Rev Time 0.00
Received By cthroop Date 2016-08-05 Time 09:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-07-29 Cont ID  
Sent By cthroop Date 2016-07-29 Time 09:20 Rev Time 0.00
Received By cthroop Date 2016-07-29 Time 09:20 Sent To  
Notes
2016-07-29 09:22:09BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER ? PX3169
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 2ND REVIEW
 ACTION: DENIED
 DATE: 7/29/16
  
 1. DESIGNER TO SIGN AND SEAL PLANS.
 2. PROVIDE DESIGN WIND LOADS PER FBC CHPT. 16 AND ASCE
 7-10.
  
 FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF
 CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL
 INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL
 BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT
 APPLICATION. THE CONSTRUCTION DOCUMENTS SHALL BE
 PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE
 REQUIRED BY CHAPTER 471, FLORIDA STATUTES& 61G15
 FLORIDA ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA
 STATUTES& 61G1 FLORIDA ADMINISTRATIVE CODE. WHERE
 SPECIAL CONDITIONS EXIST, THE BUILDING OFFICIAL IS
 AUTHORIZED TO REQUIRE ADDITIONAL CONSTRUCTION DOCUMENTS
 TO BE PREPARED BY A
 REGISTERED DESIGN PROFESSIONAL. ELECTRONIC MEDIA
 DOCUMENTS SHALL BE SUBMITTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL, AND MAY REQUIRE ONLY ONE SET OF
 SUBMITTALS.
  
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 2. RISK CATEGORY.
 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-03-04 Cont ID  
Sent By cthroop Date 2016-03-04 Time 08:50 Rev Time 0.00
Received By cthroop Date 2016-03-04 Time 08:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-08-04 Cont ID  
Sent By mvaldes Date 2016-08-04 Time 14:18 Rev Time 0.00
Received By mvaldes Date 2016-08-04 Time 14:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-07-28 Cont ID  
Sent By cthroop Date 2016-07-29 Time 09:20 Rev Time 0.00
Received By mvaldes Date 2016-07-28 Time 14:29 Sent To B
Notes
2016-07-28 14:49:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 EAST ELEVATION ORIGINAL PLANS WERE PASSED WITH A
 PROVISO WITH FBC-E SECTION C405.2.4 EXTERIOR LIGHTING
 CONTROLS ( MARKED ON PLANS ) , 2ND SUBMITTAL IS MISSING
 THIS NOTE PLEASE COMPLY.
  
 1) LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. FBC-E SECTION
 C405.2.4 PLEASE ADD THIS NOTE !
  
 2) DESIGN PROFFESIONAL FOR A COMMERCIAL SIGN SHALL BE A
 LICENSED ENGINEER OR ARCHITECT PER FLORIDA STATUE 471 &
 481
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-03-07 Cont ID  
Sent By mvaldes Date 2016-03-07 Time 09:15 Rev Time 0.00
Received By mvaldes Date 2016-03-07 Time 09:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-08-05 Cont ID  
Sent By cthroop Date 2016-08-05 Time 09:02 Rev Time 0.00
Received By cthroop Date 2016-08-05 Time 08:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-07-29 Cont ID  
Sent By cthroop Date 2016-07-29 Time 09:19 Rev Time 0.00
Received By cthroop Date 2016-07-27 Time 16:12 Sent To E
Notes
2016-07-26 14:00:40THE APPLICANT HAS RESUBMITTED THE PERMIT DUE TO NEW
 ZONING REGULATIONS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-07 Cont ID  
Sent By aaponte Date 2016-02-11 Time 09:56 Rev Time 0.00
Received By mvaldes Date 2016-01-19 Time 11:37 Sent To  
Notes
2016-02-11 09:57:00MISC 2 BOX.
2016-01-20 11:37:34ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2016-07-26 Cont ID  
Sent By   Date 2016-07-27 Time   Rev Time 0.00
Received By kmartin Date 2016-07-26 Time 14:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By aaponte Date 2016-02-11 Time 09:55 Rev Time 0.00
Received By aaponte Date 2016-02-11 Time 09:55 Sent To  
Notes
2016-02-11 09:56:42RACEWAYS ARE NOT PERMITTED. LETTERS SHALL BE ATTACHED
 DIRECTLY TO THE BUILDING FACADE.
 FOR ADDITONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.