Plan Review Details - Permit 16010504
Plan Review Stops For Permit 16010504
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-04 Cont ID  
Sent By albarran Date 2016-02-04 Time 09:41 Rev Time 0.00
Received By albarran Date 2016-02-04 Time 08:34 Sent To I
Notes
2016-02-04 09:41:59APPROIVED THE APPLICATION BUT MADE A NOTE FOR THE
 INSPECTOR: NOTICE TO INSPECTOR:
 VERIFY SERVICE CONDUCTOR SIZING AS #2 AWG IS ONLY RATED
 FOR 115 AMP AND APPEARS TO BE PROTECTED WITH BY 150 AMP
 OCPD. WORK PERMITTED UNDER PERMIT 14020436.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-27 Cont ID  
Sent By albarran Date 2016-01-27 Time 19:19 Rev Time 0.00
Received By albarran Date 2016-01-27 Time 19:00 Sent To I
Notes
2016-01-27 19:19:51THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. CITY OF WEST PALM BEACH AMENDMENTS REQUIRES THAT THE
 ALL DRAWINGS BEAR NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 2. YOU SHALL SUBMIT A MINIMUM OF TWO SETS OF PLANS FOR
 APPROVAL.
 3. YOU SHALL INDICATE THE CONDUCTOR SIZE FOR THE
 SERVICE FEEDER.
 4. CONFIRM CONDUCTOR SIZING AND LOAD TO WATER HEATER.
 5. GO OVER YOUR LOAD CALCS AND CORRECT AS REQUIRED.
 6. NEC 250.94 REQUIRES THAT YOUR PROVIDE AN
 INTER-SYSTEM BONDING TERMINAL.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-04 Cont ID  
Sent By albarran Date 2016-02-04 Time 09:43 Rev Time 0.00
Received By albarran Date 2016-01-28 Time 15:20 Sent To  
Notes
2016-02-04 09:44:022/4/16 PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL READY BIN "A".
 MA
2016-01-28 15:21:01RESUB ROUTED TO ALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-27 Cont ID  
Sent By albarran Date 2016-01-27 Time 19:23 Rev Time 0.00
Received By albarran Date 2016-01-19 Time 13:19 Sent To  
Notes
2016-01-27 19:24:361/27/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL TO [email protected]. SENT FILE
 TO SMALL DENIED BIN "A". MA
2016-01-20 13:19:19ELEC <5K