2016-01-27 18:40:58 | THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN |
| REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC, |
| (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC, |
| (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| |
| 1. CITY OF WEST PALM BEACH AMENDMENTS REQUIRES THAT THE |
| ALL DRAWINGS BEAR NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE DESIGN. |
| 2. PER NEC 250.66 THE MINIMUM GEC FOR #1 COPPER IS #6 |
| CU. CORRECT YOUR DRAWING ACCORDINGLY. |
| 3. NEC 250.94 REQUIRES THAT YOUR PROVIDE AN |
| INTER-SYSTEM BONDING TERMINAL. |
| 4. YOU SHALL SUBMIT ACTUAL LOAD CALCS NOT SIMPLY THE |
| RESULTS OF ONE. |
| 5. FBC-R314 REQUIRES THAT YOU COME INTO SMOKE DETECTOR |
| COMPLIANCE. |
| |
| |
| WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE |
| NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE |
| STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE |
| INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK |
| VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| GREATLY APPRECIATED. |
| |
| IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| CONTACT ME DIRECTLY. |
| |
| THANK YOU, |