Plan Review Details - Permit 16010446
Plan Review Stops For Permit 16010446
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2016-01-25 Cont ID  
Sent By jwitmer Date 2016-01-25 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2016-01-25 Time 06:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-23 Cont ID  
Sent By albarran Date 2016-03-23 Time 13:12 Rev Time 0.00
Received By albarran Date 2016-03-23 Time 13:12 Sent To  
Notes
2016-03-23 13:14:10PER THE ATTACHED DOCUMENT THE DESIGN PROFESSIONAL HAS
 AGREED TO COMPLY WITH THE MENTIONED FBC-E CODE DAYLIGHT
 ZONE REQUIREMENTS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-03-22 Cont ID  
Sent By albarran Date 2016-03-22 Time 14:40 Rev Time 0.00
Received By albarran Date 2016-03-22 Time 13:03 Sent To  
Notes
2016-03-23 09:21:27SPOKE W/GLEN SPINA OFFICES AND THEY WILL SEND ME AN
 EMAIL ACKNOWLEDGING MY REQUIREMENTS. ONCE RECEIVED I
 WILL APPROVE THE ELECTRICAL REVIEW WITH A PROVISO
 REQUIRING DAYLIGHT ZONE CONTROL IN THESE UNITS.
2016-03-22 14:43:07ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 SATISFACTORILY ADDRESSED, BUT I MAY HAVE OVERSEEN THE
 TWO NEW COMMENTS ON THE LIGHTING PAGE AS MENTIONED
 BELOW.
  
 2ND ELECTRICAL REVIEW NOTES FOR PERMIT #:16010446
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014
 NFPA 70 2011 (NEC)
  
 CORRECTIONS REQUIRED:
 SHEET E2.1
 1. ROOMS 311, 314 & 318 DO NOT COMPLY WITH THE
 FBC-C405.2.2.3 DAYLIGHT ZONE CONTROLS. PLEASE SEPARATE
 FIXTURE SWITCHING TO COMPLY.
 2. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By albarran Date 2016-02-10 Time 16:48 Rev Time 0.00
Received By albarran Date 2016-02-10 Time 13:34 Sent To  
Notes
2016-02-10 16:50:131ST ELECTRICAL REVIEW NOTES:
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2010, NEC 2008
  
 CORRECTIONS REQUIRED: (ITEMS MARKED IN GREEN ARE ONLY
 ENERGY CONSERVATION AND CONVENIENCE SUGGESTIONS) UNIT
 DL WAS REVIEWED FIRST, BUT COMMENTS MARKED TYPICAL
 APPLY TO ENTIRE PROJECT AND MAY BE REMEDIED WITH A
 NOTE.
 SHEET E0.1
 1. CORRECT MISQUOTED FBC SECTIONS AS FOLLOWS: NOTE P:
 FBC-EC405.7.3.2 & NOTE Q: FBC-EC405.7.3.1
 SHEET 2.1
 2. FBC-B1011.1 ADDITIONAL EXIT SIGN REQUIRED WITHIN
 THIS AREA AS THERE CAN BE NO MORE THAN 100? BETWEEN
 EXIT SIGNS.
 3. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS.
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 4. FBC-EC405.5.2 INTERIOR LIGHTING POWER ALLOWANCE. THE
 TOTAL INTERIOR POWER ALLOWANCE IS DETERMINED ACCORDING
 TO THE APPLICABLE TABLES AS INDICATED IN THIS SECTION.
 SHEET E3.1
 5. NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-20 Cont ID  
Sent By pleduc Date 2016-01-20 Time   Rev Time 0.00
Received By pleduc Date 2016-01-20 Time 15:41 Sent To  
Notes
2016-01-20 16:15:36THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
 1. THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF
 THE FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE
 AND COMPLIANCE. ANY REMOVAL AND/OR CONSTRUCTION OF
 WALLS REQUIRE AN EVALUATION.
  
 2. THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 3. ANY AND ALL WORK ON THE FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP
 DRAWINGS AND BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 4. ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-23 Cont ID  
Sent By ccole Date 2016-03-23 Time 10:28 Rev Time 0.00
Received By ccole Date 2016-03-08 Time 09:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-11 Cont ID  
Sent By ccole Date 2016-02-11 Time 09:27 Rev Time 0.00
Received By ccole Date 2016-01-19 Time 11:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-03-23 Cont ID  
Sent By ccole Date 2016-03-23 Time 10:23 Rev Time 0.00
Received By ccole Date 2016-03-23 Time 10:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By ccole Date 2016-02-04 Time 09:27 Rev Time 0.00
Received By ccole Date 2016-02-04 Time 16:37 Sent To  
Notes
2016-02-04 16:42:351ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010446
 2/4/16
  
 1) THE NEW VAV-1 BOX MUST BE EQUIPPED WITH HEAT UNLESS
 IT IS BEING PROVIDED BY ANOTHER SOURCE- SEE SECTION
 309.1.
 2) FIRE DAMPERS APPEAR TO BE MISSING FOR THE DUCTS
 PENETRATING THROUGH THE RATED CORRIDOR/WORK STATIONS
 ROOM WALL.
 3) PROVIDE AN INSTALLATION DETAIL FOR THE NEW VAV.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-24 Cont ID  
Sent By tklarge Date 2016-01-24 Time 04:07 Rev Time 0.00
Received By tklarge Date 2016-01-24 Time 03:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2016-03-28 Cont ID  
Sent By skennedy Date 2016-03-28 Time 09:46 Rev Time 0.00
Received By skennedy Date 2016-03-28 Time 09:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2016-03-24 Cont ID  
Sent By skennedy Date 2016-03-24 Time 08:38 Rev Time 0.00
Received By skennedy Date 2016-03-24 Time 08:38 Sent To  
Notes
2016-03-24 08:43:391ST REVIEW: FBC 2014 5TH
  
 THE MEP SHEETS ARE NOT DIGITALLY SIGNED. SUBMIT
 DIGITALLY SIGNED COPIES OR HARD COPIES.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  