Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-15 Cont ID  
Sent By albarran Date 2016-03-15 Time 17:52 Rev Time 0.00
Received By albarran Date 2016-03-15 Time 17:35 Sent To I
Notes
2016-03-15 17:53:20ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE BEEN
 CORRECTED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-29 Cont ID  
Sent By albarran Date 2016-02-29 Time 19:49 Rev Time 0.00
Received By albarran Date 2016-02-02 Time 09:30 Sent To I
Notes
2016-02-29 19:59:312ND ELECTRICAL REVIEW NOTES FOR REVISION #:16010443
 REVIEWED FOR COMPLIANCE WITH:
 FBC 2010 EDITION
 NFPA 70 2011 (NEC)
  
 THESE PLANS WERE INITIALLY REVIEWED ON 1/22/16 AND
 BELOW ARE YOUR RESPONSES TO THE INITIAL REVIEW
 COMMENTS. YOU WILL FIND THAT FURTHER CORRECTIONS STILL
 REMAINING. PLEASE SEE THE NOTE BELOW AND IF YOU HAVE
 ANY QUESTIONS CONTACT ME.
  
 CORRECTIONS REQUIRED:
 1. YOU WERE ASKED TO REVISE THE PLAN TO UPDATE THE
 INCORRECTLY QUOTED CODE AND YOU RESPONDED THAT THIS WAS
 NOT PART OF THE SCOPE. THE PLANS SHALL INDICATE THE
 CODE CYCLE TO WHICH THE WORK WILL BE PERFORMED.
 2. RESPONSE ACCEPTED
 3. PER NEC 110.12, WORK SHALL BE CONDUCTED IN A NEAT
 AND WORKMANLIKE MANNER AND FOR THE SAFETY OF THE PUBLIC
 ALL SHARP ENDS OF THE UNI-STRUT CHANNELS SHALL BE
 PROTECTED.
 4. NEC 110.27, REQUIRES THAT YOU PROVIDE PHYSICAL
 PROTECTION ABOUT THE NEW ELECTRICAL APPARATUS. IT IS IN
 A VERY VULNERABLE LOCATION EXPOSED TO VEHICULAR
 TRAFFIC.
 5. RESPONSE ACCEPTED
 6. RESPONSE ACCEPTED
 7. RESPONSE ACCEPTED.
 8.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  
2016-02-02 10:45:222/2/16 SPOKE W/SCOTT ABOUT NOTES REQUIRED ON PLANS. HE
 WILL REVISE AND SUBMIT. FILE RETURNED TO SMALL DENIED
 "C". MA
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-22 Cont ID  
Sent By albarran Date 2016-01-22 Time 13:13 Rev Time 0.00
Received By albarran Date 2016-01-22 Time 10:54 Sent To I
Notes
2016-01-22 13:13:02THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. THE APPLICABLE EDITION OF THE NEC IS THE 2011, AS
 REFERENCED IN THE 5TH EDITION OF THE FBC-2014. CORRECT
 ELECTRICAL LIGHTING SITE KEY NOTE 5.
 2. ALL TRENCHES SHALL REMAIN OPEN FOR INSPECTION UNLESS
 PRIOR ARRANGEMENTS ARE MADE WITH THE ELECTRICAL
 INSPECTOR. NO SITE TUBES WILL BE ACCEPTED
 3. PROTECTION SHALL BE PROVIDED AT THE ENDS OF THE
 UNI-STRUT. END CAPS REQUIRED.
 4. PHYSICAL PROTECTION FOR THE RACK AS DESCRIBED IN NEC
 110.27(B) SHALL BE PROVIDED.
 5. PROVIDE A LIGHT DENSITY ALLOWANCE CHART AS PER
 FBC-EC405.6.2; THIS SHALL INCLUDE EXISTING LIGHTING IN
 ADDITION TO THE PROPOSED.
 6. PROVIDE SPECS FOR THE PROPOSED SIGNS.
 7. NEC 408.4 REQUIRES A CIRCUIT DIRECTORY, THE SIGN
 CIRCUITS DO NOT APPEAR ON THE PANEL SCHEDULE.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-15 Cont ID  
Sent By albarran Date 2016-03-15 Time 17:55 Rev Time 0.00
Received By albarran Date 2016-03-15 Time 12:53 Sent To  
Notes
2016-03-15 17:56:053/15/16 PASSED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL READY BIN "C:.
 MA
2016-03-15 12:53:41RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-29 Cont ID  
Sent By albarran Date 2016-02-29 Time 20:00 Rev Time 0.00
Received By albarran Date 2016-02-24 Time 15:22 Sent To  
Notes
2016-02-29 20:02:272/29/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT FILE TO SMALL DENIED BIN C. MA
2016-02-24 15:23:03RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-22 Cont ID  
Sent By albarran Date 2016-01-22 Time 11:36 Rev Time 0.00
Received By albarran Date 2016-01-15 Time 15:17 Sent To  
Notes
2016-01-22 13:14:201/22/16 FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. FILE SENT TO SMALL DENIED BIN "C".
 MA
2016-01-19 15:17:21ELEC <5K