Plan Review Details - Permit 16010271
Plan Review Stops For Permit 16010271
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-02-02 Cont ID  
Sent By tklarge Date 2016-02-02 Time 09:02 Rev Time 0.00
Received By tklarge Date 2016-02-02 Time 09:02 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-01-14 Cont ID  
Sent By tklarge Date 2016-01-14 Time 06:36 Rev Time 0.00
Received By tklarge Date 2016-01-14 Time 06:32 Sent To  
Notes
2016-01-14 06:36:171) THE COPIES OF THE GAS TABLES THAT HAVE BEEN
 SUBMITTED ARE OUTDATED. SUBMIT COPIES OF THE APPLICABLE
 GAS SIZING TABLES FROM THE 2014 FLORIDA FUEL GAS CODE.
 2) THERE ARE NO PIPE SIZES ON THE CSST TO THE TANKLESS
 WATER HEATER & RANGE. A COMPLETE REVIEW CANNOT BE DONE
 WITHOUT THE PIPE SIZES.WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-02 Cont ID  
Sent By tklarge Date 2016-02-02 Time 09:03 Rev Time 0.00
Received By tklarge Date 2016-02-02 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-14 Cont ID  
Sent By tklarge Date 2016-01-14 Time 06:37 Rev Time 0.00
Received By tklarge Date 2016-01-11 Time 10:11 Sent To  
Notes
2016-01-12 10:11:26PLUMB <5K