Plan Review Details - Permit 16010225
Plan Review Stops For Permit 16010225
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2018-04-09 Cont ID  
Sent By jgomez Date 2018-04-06 Time 18:17 Rev Time 0.00
Received By jgomez Date 2018-04-06 Time 18:14 Sent To  
Notes
2018-04-06 18:18:13 
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- REVISE ENERGY CALCULATIONS SUBMITTED TO MATCH
 PLANS.; A) CONDITIONED FLOOR AREA. B) FLOOR AREAS. C)
 ROOF MATERIAL. D) TAKING CEILING FAN CREDIT. PROVIDE
 FANS SIZES REQ'D BY SEC. R405.7.6 FBC ENERGY
 CONSERVATION. E) REVISE ATTIC VENT RATIO OF 1/300. SEE
 SEC. R806.2 OF THE FBC-RESIDENTIAL.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED.
2018-04-06 18:17:4304/06/18 MET WITH MR. ERNEST (OWNER). HE WANTS PERMIT
 TO BE ISSUED WITH PROVISO. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2018-03-29 Cont ID  
Sent By jgomez Date 2018-03-29 Time 12:16 Rev Time 0.00
Received By jgomez Date 2018-03-29 Time 08:28 Sent To  
Notes
2018-03-29 08:34:23NEW SINGLE FAMILY RESIDENCE (R3) SIXTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 IMPORTANT:
 NEED OWNER TO SIGN THE ENERGY CALCULATIONS FOR PROVISO
 OPTION. PERMIT CAN NOT BE ISSUED WITHOUT THE OWNER'S
 CERTIFICATION.
  
  
 1-ENERGY CALCULATIONS SUBMITTED:
 A) THE OWNER OR OWNER'S AUTHORIZED AGENT NEEDS TO
 CERTIFY AND DATE THE ENERGY CALCULATIONS AT THE BOTTOM
 OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC- ENERGY
 CONSERVATION. THE FORM SUBMITTED ONLY HAVE THE NAME OF
 THE PERSON PREPARING THE ENERGY CALCULATIONS. NEED THE
 OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY
 COMPLIANCE. PERMIT CAN NOT BE ISSUED WITHOUT THE
 OWNER'S CERTIFICATION.
  
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 B) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 WAS REVISED.
 NOW, IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED.
 (NOTE: REVISE THE AREAS SHOWN ON ITEM #8 ACCORDINGLY).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 C) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 WAS REVISED. NOW
 IT DOESN'T MATCH MATERIAL SPECIFIED ON PLANS. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 D) THERE ARE TWO NEW INSULATED DOORS SHOWN ON PAGE 3 OF
 5. THERE ARE NOT INSULATED DOORS SPECIFIED ON PLANS OR
 PRODUCT APPROVALS SUBMITTED. WHERE ARE THESE DOORS.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 E) ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PREPARER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE HOUSE COMPLIES WITH THE
 CEILING FAN CREDIT AS REQUIRED BY SEC. R405.7.6 FBC
 ENERGY CONSERVATION. SHOW ALL CEILING FAN SIZES AND
 LOCATION.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 F) ENERGY CALCULATIONS SHOW AN ATTIC VENT RATIO OF
 1/300 ON PAGE 2 OF 5. SEC. R806.2 OF THE
 FBC-RESIDENTIAL REQUIRES 1/150 RATIO. PLANS DON'T SEEM
 TO HAVE THE HOUSE DESIGNED FOR 1/300 VENT RATIO.
 PREPARER TO PROVIDE COMPLETE DETAILS AND SPECIFICATIONS
 SHOWING HOW THE HOUSE COMPLIES WITH THE 1/300 RATIO AS
 REQUIRED BY EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL.
 REPEAT COMMENT. NOT ADDRESSED AT ALL.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2018-03-20 Cont ID  
Sent By jgomez Date 2018-03-19 Time 08:10 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 08:10 Sent To  
Notes
2018-03-20 08:11:19EXPIRED?

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2016-09-28 Cont ID  
Sent By jgomez Date 2016-09-28 Time 12:49 Rev Time 0.00
Received By jgomez Date 2016-09-28 Time 12:47 Sent To  
Notes
2016-09-28 12:56:08NEW SINGLE FAMILY RESIDENCE (R3) FIFTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 NOTE:
 MISSING ONE SET OF DRAWINGS
  
  
  
 1-ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE:
 THE INFORMATION IS INCOMPLETE. BUILDER DIDN'T WROTE THE
 ADDRESS OF THE NEW HOME.
  
 ORIGINAL COMMENT:
 B) THE OWNER OR OWNER'S AUTHORIZED AGENT NEEDS TO
 CERTIFY AND DATE THE ENERGY CALCULATIONS AT THE BOTTOM
 OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC- ENERGY
 CONSERVATION. ENERGY CALCULATIONS SUBMITTED SHOW THE
 NAME OF THE OWNER ONLY. THIS IS NOT CERTIFICATION THAT
 THE OWNER IS COMPLYING WITH THE ENERGY CODE. HE/SHE MAY
 NOT EVEN BE AWARE OF THIS CERTIFICATION. NEED THE OWNER
 OR AGENT TO SPECIFICALLY CERTIFY COMPLIANCE.
  
 RESPONSE:
 THE ENERGY CALCULATIONS SUBMITTED NOW ARE DONE BY
 ANOTHER PERSON. THIS SAME PERSON IS CERTIFYING ON THE
 OWNER/AGENT LINE. PROVIDE PROOF THAT THE PERSON
 CERTIFYING CODE COMPLIANCE IS LEGALLY DESIGNATED BY THE
 OWNER AS REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). PERMIT CAN NOT BE
 ISSUED WITHOUT THE OWNER'S CERTIFICATION. SEC.
 R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 C) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 WAS REVISED.
 NOW, IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED.
 (NOTE: REVISE THE AREAS SHOWN ON ITEM #8 ACCORDINGLY).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 D) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 WAS REVISED. NOW
 IT DOESN'T MATCH MATERIAL SPECIFIED ON PLANS. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 E) THERE ARE TWO NEW INSULATED DOORS SHOWN ON PAGE 3 OF
 5. THERE ARE NOT INSULATED DOORS SPECIFIED ON PLANS OR
 PRODUCT APPROVALS SUBMITTED. WHERE ARE THESE DOORS.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 F) ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. PREPARER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE HOUSE COMPLIES WITH THE
 CEILING FAN CREDIT AS REQUIRED BY SEC. R405.7.6 FBC
 ENERGY CONSERVATION.
  
 G) ENERGY CALCULATIONS SHOW AN ATTIC VENT RATIO OF
 1/300 ON PAGE 2 OF 5. SEC. R806.2 OF THE
 FBC-RESIDENTIAL REQUIRES 1/150 RATIO. PREPARER TO
 PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW
 THE HOUSE COMPLIES WITH THE 1/300 RATIO AS REQUIRED BY
 EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL.
  
  
 ORIGINAL COMMENT:
 2- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN AND
 CROSS VENTILATION CREDITS ON ITEM #15 OF PAGE 1 OF 5.
 DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS ON THE CONSTRUCTION DRAWINGS SHOWING
 FULL COMPLIANCE WITH SEC. R405.7.6 AND SEC. R405.7.4 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED. ENERGY CALCULATIONS ARE
 STILL TAKING THE CEILING FAN CREDIT. DESIGNER OF RECORD
 NEEDS TO SHOW IN PLANS COMPLIANCE WITH THE CEILING FAN
 REQUIREMENTS. PROVIDE ALL THE INFORMATION REQUIRED BY
 SEC. R405.7.6 FBC-ENERGY CONSERVATION.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2016-08-17 Cont ID  
Sent By jgomez Date 2016-08-17 Time 08:55 Rev Time 0.00
Received By jgomez Date 2016-08-16 Time 19:21 Sent To  
Notes
2016-08-17 08:55:58NEW SINGLE FAMILY RESIDENCE (R3) FOURTH BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ***NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO ONCE THE
 ENERGY CALCULATIONS ARE CERTIFIED BY THE OWNER. PROVISO
 MEANS THAT PERMIT MAY BE ISSUED AFTER THE IMPACT FEES
 AND RECEIPT ARE SUBMITTED. THE REQUIRED INFORMATION MAY
 BE SUBMITTED AFTER THE PERMIT IS ISSUED. REVISION FEES
 MAY APPLY EXCEPT FOR THE ENTRY DOOR PRODUCT APPROVAL.
 REQUIRED INFORMATION TO BE SUBMITTED PRIOR TO
 INSPECTIONS TO AVOID CONFLICTS OR DELAYS. CONTRACTOR TO
 ADVICE IN WRITING IF PROVISO OPTION IS PREFERRED AT
 THIS TIME.
  
  
  
 ORIGINAL COMMENT:
 1-ENERGY CALCULATIONS SUBMITTED:
 ORIGINAL COMMENT:
 A) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE:
 REPEAT COMMENT. FOUR TIMES.
  
 ORIGINAL COMMENT:
 B) THE OWNER OR OWNER'S AUTHORIZED AGENT NEEDS TO
 CERTIFY AND DATE THE ENERGY CALCULATIONS AT THE BOTTOM
 OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC- ENERGY
 CONSERVATION. ENERGY CALCULATIONS SUBMITTED SHOW THE
 NAME OF THE OWNER ONLY. THIS IS NOT CERTIFICATION THAT
 THE OWNER IS COMPLYING WITH THE ENERGY CODE. HE/SHE MAY
 NOT EVEN BE AWARE OF THIS CERTIFICATION. NEED THE OWNER
 OR AGENT TO SPECIFICALLY CERTIFY COMPLIANCE.
  
 RESPONSE:
 REPEAT COMMENT. TWO TIMES. WRITING DOWN THE NAME OF THE
 OWNER IS NOT PROOF THAT THE OWNER IS CERTIFYING
 COMPLIANCE. PERMIT CAN NOT BE ISSUED WITHOUT THE
 OWNER'S CERTIFICATION. SEC. R103.1.1.2 FBC-ENERGY
 CONSERVATION.
  
 NEW COMMENT:
 C) CONDITIONED FLOOR AREA SHOWN ON ITEM #6 WAS REVISED.
 NOW, IT DOESN'T MATCH FLOOR PLANS. REVISE AS REQUIRED.
 (NOTE: REVISE THE AREAS SHOWN ON ITEM #8 ACCORDINGLY).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 NEW COMMENT:
 D) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 WAS REVISED. NOW
 IT DOESN'T MATCH MATERIAL SPECIFIED ON PLANS. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 NEW COMMENT:
 E) THERE ARE TWO NEW INSULATED DOORS SHOWN ON PAGE 3 OF
 5. THERE ARE NOT INSULATED DOORS SPECIFIED ON PLANS OR
 PRODUCT APPROVALS SUBMITTED. WHERE ARE THESE DOORS.
 REVISE AS REQUIRED TO MATCH PLANS. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
  
 ORIGINAL COMMENT:
 2- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN AND
 CROSS VENTILATION CREDITS ON ITEM #15 OF PAGE 1 OF 5.
 DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS ON THE CONSTRUCTION DRAWINGS SHOWING
 FULL COMPLIANCE WITH SEC. R405.7.6 AND SEC. R405.7.4 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE:
 REPEAT COMMENT. ENERGY CALCULATIONS ARE STILL TAKING
 THE CEILING FAN CREDIT. DESIGNER OF RECORD NEEDS TO
 SHOW IN PLANS COMPLIANCE WITH THE CEILING FAN
 REQUIREMENTS. PROVIDE ALL THE INFORMATION REQUIRED BY
 SEC. R405.7.6 FBC-ENERGY CONSERVATION.
  
 3- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2016-06-15 Cont ID  
Sent By jgomez Date 2016-06-15 Time 13:21 Rev Time 0.00
Received By jgomez Date 2016-06-15 Time 13:20 Sent To  
Notes
2016-06-15 13:43:38NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 OF FBC RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE: REPEAT COMMENT. 3 TIMES. STILL NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 OF FBC RESIDENTIAL, 5TH EDITION (2014).
  
 RESPONSE: REPEAT COMMENT. 3 TIMES. STILL NOT ADDRESSED.
  
 3- ENERGY CALCULATIONS SUBMITTED:
 A) WINDOWS INFORMATION, WHICH INCLUDES DOORS WITH
 GLAZING, DOESN'T MATCH PLANS. IT LOOKS LIKE THERE ARE
 MORE WINDOWS SHOWN ON THE ENERGY CALCULATIONS THAN
 THERE ARE ON PLANS. PLEASE NUMBER EACH WINDOW/DOOR ON
 THE EXTERIOR ELEVATIONS TO VERIFY THAT INFORMATION
 MATCHES. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 ORIGINAL COMMENT:
 B) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 RESPONSE: NOT DONE. REPEAT COMMENT.. 3 TIMES.
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF THE FORM
 INCLUDING: BUILDER NAME AND PERMIT OFFICE. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D) THE OWNER OR OWNER'S AUTHORIZED AGENT NEEDS TO
 CERTIFY AND DATE THE ENERGY CALCULATIONS AT THE BOTTOM
 OF FORM AS REQUIRED BY SEC. R103.1.1.2 FBC- ENERGY
 CONSERVATION. ENERGY CALCULATIONS SUBMITTED SHOW THE
 NAME OF THE OWNER ONLY. THIS IS NOT CERTIFICATION THAT
 THE OWNER IS COMPLYING WITH THE ENERGY CODE. HE/SHE MAY
 NOT BE EVEN AWARE OF THIS CERTIFICATION. NEED THE OWNER
 OR AGENT TO SPECIFICALLY CERTIFY COMPLIANCE.
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 NEW COMMENT:
 4- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN AND
 CROSS VENTILATION CREDITS ON ITEM #15 OF PAGE 1 OF 5.
 DESIGNER OF RECORD TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS ON THE CONSTRUCTION DRAWINGS SHOWING
 FULL COMPLIANCE WITH SEC. R405.7.6 AND SEC. R405.7.4 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: SEE COMMENT REGARDING THE ENERGY CALCULATIONS.
 MAY BE THAT'S WHY THE CREDITS WERE TAKEN. IT SEEMS THAT
 THE ENERGY CALCULATIONS ARE SHOWING MORE GLASS THAN
 THERE IS IN THE HOUSE.
  
 ORIGINAL COMMENT:
 5- SUBMITTAL PACKAGE IS MISSING ONE SET OF PRODUCT
 APPROVALS. PROVIDE THE SECOND SET.
  
 RESPONSE: THERE ARE SOME PRODUCT APPROVALS THAT ARE
 MISSING. REVIEW COMPLETE PACKAGE SUBMITTED AND PROVIDE
 TWO COMPLETE SETS OF PRODUCT APPROVALS REVIEWED BY THE
 ENGINEER OF RECORD.
  
 6- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-05-05 Cont ID  
Sent By jgomez Date 2016-05-05 Time 14:33 Rev Time 0.00
Received By jgomez Date 2016-05-05 Time 14:33 Sent To  
Notes
2016-05-05 14:40:20NEW SINGLE FAMILY RESIDENCE (R3) SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 OF FBC RESIDENTIAL, 5TH EDITION (2014).
 (REPEAT COMMENT. NOT ADDRESSED. NEED REPORT TO VERIFY
 PROPOSED DESIGN AND SOIL PREPARATION RECOMMENDATIONS.).
  
 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 OF FBC RESIDENTIAL, 5TH EDITION (2014). (REPEAT
 COMMENT. NOT ADDRESSED).
  
 3- ENERGY CALCULATIONS SUBMITTED;
 (NOTE: ENGINEER MAY BE CHARGED 4 TIMES THE PLAN REVIEW
 FEES AS REQUIRED BY FLORIDA STATUTE 553.80(2)(B) EACH
 TIME AFTER THE THIRD REVIEW IF THE PLANS ARE DENIED)
  
 A) TYPE OF ADJACENT WALL SHOWN ON ITEM #9 IS INCORRECT.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). (REPEAT
 COMMENT. NOTE: REVISE TYPE OF WALL AND INSULATION
 R-VALUE. SEE PLANS).
  
 B) PAGE 3 OF 5: WHERE IS THE NORTH INSULATED DOOR ON
 THE SECOND FLOOR SHOWN ON PLANS. THERE ARE NO INSULATED
 DOORS ON SECOND FLOOR. SEE PLANS AND PRODUCT APPROVALS
 AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT).
  
 C) WALLS INFORMATION ON PAGE 3 OF 5 FOR THE GARAGE WALL
 IS INCORRECT. REVISE THE WALL ORIENTATION AND WALL
 TYPE. SEE PLANS AND REVISE AS REQUIRED. THERE ARE NO
 GARAGE STEEL WALLS ON THE SECOND FLOOR. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014). (REPEAT COMMENT).
  
 D) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). (REPEAT COMMENT).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 4- SUBMITTAL PACKAGE IS MISSING ONE SET OF PRODUCT
 APPROVALS. PROVIDE THE SECOND SET.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By jgomez Date 2016-02-17 Time 09:35 Rev Time 0.00
Received By jgomez Date 2016-02-17 Time 09:32 Sent To  
Notes
2016-02-17 09:41:54NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  
 2- ACCORDING TO SEC. R301.2.1.4 OF FBC RESIDENTIAL, 5TH
 EDITION (2014) THIS HOUSE IS LOCATED IN EXPOSURE "D"
 NOT EXPOSURE "C". REVISE INFORMATION ON DESIGN CRITERIA
 AND STRUCTURAL NOTES ON SHEET S.1. ALSO, REVISE THE
 DESIGN PRESSURES ON SHEET S.2 AND S.7.
  
 3- GARAGE DOOR STRUCTURAL BUCK DETAIL ON SHEET S.1: (A)
 CLEARLY SPECIFY ANCHOR SPACING AT THE ENDS OF THE DOOR
 OPENING. INFORMATION ON DETAIL DOESN'T MATCH
 INFORMATION SHOWN ON GARAGE DOOR NOTES. ALSO,
 FOUNDATION PLAN SHOW FILLED CELLS AT THE ENDS OF THE
 GARAGE OPENINGS, NOT POURED CONCRETE. REVISE
 SPECIFICATIONS AS REQUIRED. PROVIDE CALCULATIONS
 SHOWING THAT THE PROPOSED ANCHOR SPACING IS ADEQUATE TO
 RESIST THE DESIGN PRESSURES. COORDINATE DESIGN
 PRESSURES WITH ITEM #2 ABOVE. SEC. R301 OF FBC
 RESIDENTIAL, 5TH EDITION (2014).
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $413,334. THE
 PERMIT FEE BALANCE IS $6305.17.
  
 5- STAIRWAY ON SHEET S.2: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE WINDER TREADS SHOWING COMPLIANCE
 WITH SEC. R311.7.5.2.1 OF FBC RESIDENTIAL, 5TH EDITION
 (2014). CLEARLY PROVIDE THE DIMENSION OF THE NARROWEST
 PART OF THE TREAD.
  
 6- REVISE TYPICAL STAIR & GUARDRAIL NOTES ON SHEET S.2.
 REVISE THE LIVE LOADS. SEE NOTES "D" , "F" AND "H" FROM
 TABLE R301.5 OF FBC RESIDENTIAL, 5TH EDITION (2014) AND
 REVISE AS REQUIRED.
  
 7- PROVIDE SPECIFICATIONS FOR THE DOOR LEADING FROM
 GARAGE TO THE INTERIOR OF THE HOUSE. SPECIFY FIRE
 RATING AND SELF CLOSING AS REQUIRED BY SEC. R302.5.1 OF
 FBC RESIDENTIAL, 5TH EDITION (2014).
  
 8- DIMENSION SHOWN ON THE BOTTOM TREAD OF THE REAR
 PORCH STAIRS IS TOO NARROW COMPARED TO THE OTHER ONES.
 REVISE AS REQUIRED BY SEC. R311.7.5.2. OF FBC
 RESIDENTIAL, 5TH EDITION (2014).
  
 9- ROOF DESIGN LOADS ON SHEET S.7: SPECIFY THE ATTIC
 LIVE LOAD AS REQUIRED BY NOTES "B" AND "G" OF TABLE
 R301.5 OF FBC RESIDENTIAL, 5TH EDITION (2014).
 NOTE: COORDINATE LOADS WITH LOADS SHOWN ON THE
 STRUCTURAL NOTES ON SHEET S.1.
  
 10- PROVIDE SOIL TEST REPORT (2 COPIES) AS REQUIRED BY
 SEC. R401.4 OF FBC RESIDENTIAL, 5TH EDITION (2014).
  
 11- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH SEC.
 R401.3 OF FBC RESIDENTIAL, 5TH EDITION (2014).
  
 12- PROVIDE SURVEY OR SITE PLAN AS REQUIRED BY SEC.
 107.3.5.3 CITY AMENDMENTS.
  
 13-ENERGY CALCULATIONS SUBMITTED;
 A) ENGINEER WHO PREPARED THE ENERGY CALCULATIONS TO
 PROVIDE HIS NAME AND ALL HIS INFORMATION AND TO PROVIDE
 ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471
 FL. ST.
  
 B) STREET ADDRESS IS INCORRECT. THE STREET IS MANGONIA
 DR. NOT MAGNOLIA DR. ALSO, THE NAME OF BUILDER IS
 INCORRECT. REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 C) NUMBER OF BEDROOMS SHOWN ON ITEM # 3 IS INCORRECT..
 SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) TYPE OF ADJACENT WALL SHOWN ON ITEM #9 IS INCORRECT.
 SEE PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) TYPE OF HOT WATER SYSTEM SHOWN ON ITEM #14 IS
 INCORRECT. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) ROOF MATERIAL SHOWN ON PAGE 2 OF 5 IS INCORRECT. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 G) WHERE IS THE NORTH WOOD DOOR SHOWN ON PAGE 3 OF 5?.
 THERE ARE NO WOOD DOORS ON SECOND OR FIRST FLOOR. SEE
 PLANS AND PRODUCT APPROVALS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 H) WALLS INFORMATION ON PAGE 3 OF 5 FOR THE GARAGE WALL
 IS INCORRECT. REVISE THE WALL ORIENTATION AND WALL
 TYPE. SEE PLANS AND REVISE AS REQUIRED. SEC.
 R101.5.1.1.2 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 I) WINDOWS ORIENTATION, AREA AND OVERHANG DEPTH AND
 SEPARATION SHOWN ON PAGE 3 OF 5 DON'T MATCH PLANS. SEE
 PLANS AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 OF
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 J) BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.3 OF FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014).
  
 K) PROVIDE DOORS AND WINDOWS DOCUMENTATION SHOWING THE
 U-FACTOR AND SHGC FACTOR SHOWN ON ITEM #7 AS REQUIRED
 BY SEC. R405.3 OF FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE: LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR
 AND SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS
 WILL BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT
 USING THE SOFTWARE DEFAULT FACTOR FOR GLAZING.
  
 14- CLARIFY DOORS #4 AND #5 ON THE EXTERIOR DOOR
 SCHEDULE ON SHEET S.2. WHAT'S (3)3'-0" X 8'-0"?. SEC.
 107.2.1 CITY AMENDMENTS.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ENTRY DOOR SIZE AND TYPE AS SHOWN ON PLANS. DOOR
 WITH SIDELITES. FLORIDA PRODUCT APPROVAL FL13540-R3
 SUBMITTED DOESN'T COVER 8'-0" HIGH DOORS.
  
 B) PRECAST LINTELS. NOA 14-0903.03 SUBMITTED WITH
 FLORIDA PRODUCT APPROVAL FL158-R7 IS FOR 4", 6" & 12"
 LINTELS. NEED NOA FOR 8" LINTELS AS SPECIFIED ON PLANS.
  
 C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR OR
 LIST THE FLORIDA 2014 CODE VERSION PRODUCT APPROVAL
 NEXT TO EACH SPECIFIED CONNECTOR.
  
 16- ENGINEER OF RECORD TO SPECIFY THE METAL ROOF
 FASTENING FOR ALL ROOF ZONES AS REQUIRED BY SEC.
 107.2.1.2 OF CITY AMENDMENTS.
 NOTE: CLEARLY IDENTIFY APPROVED ASSEMBLY ON METAL ROOF
 NOA 13-0114.03 SUBMITTED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES. ALSO, SEE LIMITATION #2 ON
 PAGE 7 OF 9 OF NOA SUBMITTED. COORDINATE WITH REVISED
 DESIGN PRESSURES REQUIRED BY ITEM #2 ABOVE.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-06-17 Cont ID  
Sent By vperez Date 2016-06-17 Time 11:59 Rev Time 0.00
Received By vperez Date 2016-06-17 Time 11:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By vperez Date 2016-04-07 Time 09:43 Rev Time 0.00
Received By vperez Date 2016-04-07 Time 09:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-11 Cont ID  
Sent By vperez Date 2016-02-11 Time 07:53 Rev Time 0.00
Received By vperez Date 2016-02-11 Time 07:53 Sent To B
Notes
2016-02-11 07:54:02INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE RESIDENTIAL 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE NOTE THAT THE RISER DIAGRAM SHOWN AT 250A
 WITH COMBINATION BREAKERS IS NOT TYPICAL AS TO DESIGN
 OR PRODUCT MANUFACTURING. REVISE RISER DIAGRAM TO SHOW
 ACTUAL FIELD INSTALLATION FOR THE LOAD CALCULATION
 SHOWN. FOR EXAMPLE A TYPICAL INSTALLATION WOULD BE A
 320A/400A CONTINUOUS METER CAN WITH MAIN BREAKERS SHOWN
 WIRED FROM METER CAN OR A 400AMP METER COMBO WITH TWO
 MAINS BREAKERS, FBC 107 MINIMUM PLAN REVIEW CRITERIA.
 2. NOTE THAT THE CONDUCTORS SELECTED (3/0) FOR THE
 100AMP PANEL IS ABOVE THE STANDARD CAPACITY OF THE
 TERMINATION LUGS MANUFACTURED FOR 100A PANEL BOARDS.
 TYPICALLY THESE PANELS HAVE LUGS TO HOLD FROM #6- TO
 #1/0 MAX. CONDUCTORS. EITHER SHOW SIZED WITH #3
 CONDUCTORS FOR 100AMPS OR INCREASE PANEL MAIN BREAKER
 AND PANEL BOARD ACCORDINGLY. NEC 110.3 FBC 107
 3. SHOW THE SIZE OF THE GROUNDING ELECTRODE CONDUCTOR
 AT THE SERVICE. PER NEC 250.66
 4. SHOW AN INTERSYSTEM BONDING TERMINAL AT THE SERVICE.
 A NOTE WILL SUFFICE. NEC 250.94
 5. SHOW CORRECT SIZE OF MCB ON PANEL SCHEDULE A AT 200A
 NOT 250A. FBC 107
 6. IDENTIFY THE AREAS LABELED AS RECESSED LIGHTING ON
 PANEL SCHEDULES TO INDICATE SPECIFICALLY THE AREAS
 SERVED. NEC 408.4
 7. SHOW COMBINATION SMOKE/CO AT BOTH LANDINGS OF THE
 STAIRS AREA. FBC RES 314
 8. IF THE COUNTERTOP SPACE TO THE LEFT OF RANGE SHOWN
 IS 12? OR MORE PLEASE SHOW A RECEPTACLE FOR THAT AREA
 PER NEC 210.52C1. LABEL GFCI
 9. PROVIDE A GENERAL NOTE TO PLANS TO INDICATE THE
 REQUIREMENTS FBC EC 405.1- NO LESS THAN 75% OF LAMPS TO
 BE HIGH EFFICACY LAMPS.
 10. SHOW LOCATION OF THE ELECTRICAL SERVICE ON THE
 FLOOR PLAN. FBC 107
 11. FURTHER COMMENTS MAY FOLLOW PENDING COMMENTS BEING
 ADDRESSED.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2018-04-09 Cont ID  
Sent By jgomez Date 2018-04-06 Time 19:24 Rev Time 0.00
Received By jgomez Date 2018-04-06 Time 18:14 Sent To I
Notes
2018-04-06 18:16:58MET WITH MR. ERNEST (OWNER). HE WANTS PERMIT TO BE
 ISSUED WITH PROVISO. JG.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2018-03-29 Cont ID  
Sent By jgomez Date 2018-03-29 Time 12:39 Rev Time 0.00
Received By jgomez Date 2018-03-22 Time 17:34 Sent To I
Notes
2018-03-22 17:34:42TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-03-19 Cont ID  
Sent By shill Date 2018-03-19 Time 12:39 Rev Time 0.00
Received By shill Date 2018-03-05 Time 10:30 Sent To  
Notes
2018-03-19 12:41:263/19/18 APPLICATION IS EXPIRED, SEE FRONT SCREEN.
 EMAILED CONTRACTOR AND CALLED OWNER. OWNER STATED THAT
 PLANS WERE DROPPED OFF AT PALM BEACH COUNTY IMPACT FEES
 9/16 AND NOT RETURNED UNTIL 3/18. OWNER WAS INSTRUCTED
 TO WRITE A LETTER EXPLAINING "ACTIVITY" ON THE PERMIT,
 EMAIL TO ME AS AN ATTACHMENT (TO [email protected]), FOR
 BUILDING OFFICIAL'S CONSIDERATION.
  
2018-03-06 10:30:23RESUB ROTUED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2016-09-28 Cont ID  
Sent By jgomez Date 2016-09-28 Time 16:48 Rev Time 0.00
Received By jgomez Date 2016-09-22 Time 10:29 Sent To  
Notes
2016-09-23 10:29:47RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-08-17 Cont ID  
Sent By jgomez Date 2016-08-17 Time 19:01 Rev Time 0.00
Received By jgomez Date 2016-08-09 Time 10:32 Sent To  
Notes
2016-08-10 10:32:19RESUB ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-06-17 Cont ID  
Sent By vperez Date 2016-06-17 Time 11:59 Rev Time 0.00
Received By vperez Date 2016-06-17 Time 11:59 Sent To  
Notes
2016-05-31 13:56:13R19

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-05-06 Cont ID  
Sent By jgomez Date 2016-05-06 Time 11:21 Rev Time 0.00
Received By jgomez Date 2016-04-05 Time 09:58 Sent To  
Notes
2016-04-06 09:58:31R30

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-18 Cont ID  
Sent By jgomez Date 2016-02-18 Time 13:42 Rev Time 0.00
Received By jgomez Date 2016-01-11 Time 11:29 Sent To  
Notes
2016-01-11 11:29:46R33

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 7 Status P Date 2018-03-29 Cont ID  
Sent By jgomez Date 2018-03-29 Time 10:12 Rev Time 0.00
Received By jgomez Date 2018-03-29 Time 10:12 Sent To  
Notes
2018-03-29 10:13:47$10,003.08 PAID. MU-2016-024060.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status F Date 2018-03-20 Cont ID  
Sent By jgomez Date 2018-03-19 Time 08:11 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 08:12 Sent To  
Notes
2018-03-20 08:11:59EXPIRED?

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date 2016-09-28 Cont ID  
Sent By jgomez Date 2016-09-28 Time 17:23 Rev Time 0.00
Received By jgomez Date 2016-09-28 Time 17:23 Sent To  
Notes
2016-09-28 17:24:121- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date 2016-08-17 Cont ID  
Sent By jgomez Date 2016-08-17 Time 16:16 Rev Time 0.00
Received By jgomez Date 2016-08-17 Time 16:16 Sent To  
Notes
2016-08-17 16:16:401- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 FOR IMPACT FEES ASSESSMENT. BRING BACK COUNTY STAMPED
 PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. COUNTY
 IMPACT FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT
 CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2016-06-15 Cont ID  
Sent By jgomez Date 2016-06-15 Time 14:59 Rev Time 0.00
Received By jgomez Date 2016-06-15 Time 14:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-05-05 Cont ID  
Sent By jgomez Date 2016-05-05 Time 15:17 Rev Time 0.00
Received By jgomez Date 2016-05-05 Time 15:17 Sent To  
Notes
2016-05-05 15:17:471- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-02-17 Cont ID  
Sent By jgomez Date 2016-02-17 Time 09:42 Rev Time 0.00
Received By jgomez Date 2016-02-17 Time 09:42 Sent To  
Notes
2016-02-17 09:42:391- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT.
 BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF
 THE UNIFIED LAND DEVELOPMENT CODE.
  

Review Stop M MECHANICAL (A/C)
Rev No 8 Status N Date 2018-04-09 Cont ID  
Sent By jgomez Date 2018-04-06 Time 18:18 Rev Time 0.00
Received By jgomez Date 2018-04-06 Time 18:18 Sent To  
Notes
2018-04-06 18:19:12PROVIDE COMPLETE AND CORRECT EQUIPMENT SIZING
 CALCULATIONS AND A/C PLANS UNDER A SEPARATE PERMIT.
2018-04-06 18:18:39MET WITH MR. ERNEST (OWNER). HE WANTS PERMIT TO BE
 ISSUED WITH PROVISO. JG.

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2018-03-29 Cont ID  
Sent By jgomez Date 2018-03-29 Time 12:22 Rev Time 0.00
Received By jgomez Date 2018-03-29 Time 12:22 Sent To  
Notes
2018-03-29 12:25:03NEW SINGLE FAMILY RESIDENCE (R3) SIXTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES APPLY. CONTRACTOR TO
 ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME OR
 IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
  
 1- IT LOOKS LIKE THE EQUIPMENT MAY BE OVERSIZED AGAIN.
 IT LOOKS LIKE THE EQUIPMENT WAS SIZED BASED ON A LARGE
 NUMBER OF PEOPLE. 35 PEOPLE IS A LARGE QUANTITY FOR A
 SINGLE FAMILY RESIDENCE. EQUIPMENT CAN NOT BE SIZED
 BASED ON OTHER FACTORS THAT MAY AFFECT THE EQUIPMENT
 SIZING. REVISE CALCULATIONS AS REQUIRED TO MATCH ACTUAL
 DESIGN CONDITIONS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE DRAWING M.1 WITH REVISED
 EQUIPMENT SIZING CALCULATIONS.
  
  
 2- EQUIPMENT SHOWN ON A/C PLAN DOESN'T MATCH EQUIPMENT
 SHOWN ON THE AHRI CERTIFICATES SUBMITTED. REVISE AS
 REQUIRED TO MATCH. NOTE: COORDINATE WITH ITEM #1 ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2018-03-20 Cont ID  
Sent By jgomez Date 2018-03-19 Time 08:12 Rev Time 0.00
Received By jgomez Date 2018-03-19 Time 08:12 Sent To  
Notes
2018-03-20 08:12:16EXPIRED?

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2016-09-29 Cont ID  
Sent By jgomez Date 2016-09-28 Time 16:47 Rev Time 0.00
Received By jgomez Date 2016-09-28 Time 16:47 Sent To  
Notes
2016-09-28 16:48:13NEW SINGLE FAMILY RESIDENCE (R3) FIFTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 1- IT LOOKS LIKE THE EQUIPMENT MAY BE OVERSIZED AGAIN.
 IT LOOKS LIKE THE EQUIPMENT WAS SIZED BASED ON A LARGE
 NUMBER OF PEOPLE. 35 PEOPLE IS A LARGE QUANTITY FOR A
 SINGLE FAMILY RESIDENCE. EQUIPMENT CAN NOT BE SIZED
 BASED ON OTHER FACTORS THAT MAY AFFECT THE EQUIPMENT
 SIZING. REVISE CALCULATIONS AS REQUIRED TO MATCH ACTUAL
 DESIGN CONDITIONS REQUIRED BY SEC. R403.6.1 FBC-ENERGY
 CONSERVATION. NOTE: COORDINATE DRAWING M.1 WITH REVISED
 EQUIPMENT SIZING CALCULATIONS.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2016-08-17 Cont ID  
Sent By jgomez Date 2016-08-17 Time 18:27 Rev Time 0.00
Received By jgomez Date 2016-08-17 Time 16:48 Sent To  
Notes
2016-08-17 18:26:32NEW SINGLE FAMILY RESIDENCE (R3) FOURTH MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
  
 ***NOTE:
 MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT PERMIT MAY BE ISSUED AND THE REQUIRED
 INFORMATION MAY BE SUBMITTED AFTER THE PERMIT IS
 ISSUED. REVISION FEES APPLY. REQUIRED INFORMATION TO BE
 SUBMITTED PRIOR TO INSPECTIONS TO AVOID CONFLICTS OR
 DELAYS. CONTRACTOR TO ADVICE IN WRITING IF PROVISO
 OPTION IS PREFERRED AT THIS TIME.
  
  
  
  
 ORIGINAL COMMENT:
 1- THE EQUIPMENT SIZE FOR UNITS 1 AND 2 IS OVERSIZED.
 ACCORDING TO SEC. R403.6.1.1 FBC-ENERGY CONSERVATION,
 THE EQUIPMENT CAN NOT BE MORE THAN 1.15 TIMES GREATER
 THAN THE TOTAL CALCULATED LOAD OR CLOSEST AVAILABLE
 SIZE. TOTAL COOLING LOADS ARE 27531 BTU'S AND 27192
 BTU'S. THE CLOSES SIZE IS 2-1/2 TON NOT 3 TON. REVISE
 AS REQUIRED INCLUDING SHEET M.1.
  
 RESPONSE:
 REPEAT COMMENT. TOTAL COOLING LOADS SUBMITTED NOW ARE
 26144 BTU'S AND 26736 BTU'S. THE CLOSES SIZE IS 2-1/2
 TON NOT 3 TON. REVISE AS REQUIRED INCLUDING SHEET M.1.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-06-15 Cont ID  
Sent By jgomez Date 2016-06-15 Time 15:52 Rev Time 0.00
Received By jgomez Date 2016-06-15 Time 15:00 Sent To  
Notes
2016-06-15 15:19:18NEW SINGLE FAMILY RESIDENCE (R3) THIRD MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT:
 1- EQUIPMENT SIZING CALCULATIONS NEED TO COMPLY WITH
 THE EQUIPMENT SIZING SECTION R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS NEED TO
 BE DONE USING AN APPROVED SOFTWARE (FOR EXAMPLE ELITE,
 WRIGHTSOFT, ETC). NEED CALCULATIONS BASED ON THE
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING. AND, NEED TO BE DONE BASED ON THE INTERIOR
 DESIGN DESIGN TEMPERATURE REQUIRED BY SEC. R302.1 OF
 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED.
 CALCULATIONS SUBMITTED ARE NOT DONE WITH AN APPROVED
 SOFTWARE AND THE INTERIOR DESIGN TEMPERATURE DOESN'T
 COMPLY WITH SEC. R302.1.
  
 RESPONSE:
 EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 A) CALCULATIONS NEED TO BE DONE BASE ON THE ACTUAL
 ORIENTATION OF THE BUILDING AS REQUIRED BY SEC.
 R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 CALCULATIONS SUBMITTED DON'T MATCH ACTUAL BUILDING
 ORIENTATION. REVISE AS REQUIRED. NOTE: COORDINATE WITH
 THE ENERGY CALCULATIONS ONCE THE ENERGY CALCULATIONS
 ARE REVISED. SEE BUILDING COMMENTS FOR ENERGY
 CALCULATIONS SUBMITTED.
  
 B) THE EQUIPMENT SIZE FOR UNITS 1 AND 2 IS OVERSIZED.
 ACCORDING TO SEC. R403.6.1.1 FBC-ENERGY CONSERVATION,
 THE EQUIPMENT CAN NOT BE MORE THAN 1.15 TIMES GREATER
 THAN THE TOTAL CALCULATED LOAD OR CLOSEST AVAILABLE
 SIZE. TOTAL COOLING LOADS ARE 27531 BTU'S AND 27192
 BTU'S. THE CLOSES SIZE IS 2-1/2 TON NOT 3 TON. REVISE
 AS REQUIRED INCLUDING SHEET M.1.
  
  
 ORIGINAL COMMENT:
 2- MECHANICAL PLAN M.1 SUBMITTED;
 A) SIZE OF "TRANSFER DUCTS" SHOWN ON THE SECOND FLOOR
 BEDROOMS DON'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). SHOW
 COMPLIANCE. (REPEAT COMMENT). THE TRANSFER DUCT SIZE
 WAS NOT REVISED. IN ADDITION THE CFM'S SHOWN ON PLANS
 DON'T MATCH CFM SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH.
 NOTE: INFORMATION WAS CHANGED ON THE FIRST FLOOR. THE
 TRANSFER DUCTS NEED TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4. ALSO, COORDINATE CFM'S WITH EQUIPMENT
 SIZING CALCULATIONS. REVISE AS REQUIRED.
  
 RESPONSE:
 SIZE OF MASTER BEDROOM #2 TRANSFER DUCT NEEDS TO BE
 REVISED TO COMPLY.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-05-06 Cont ID  
Sent By jgomez Date 2016-05-06 Time 09:30 Rev Time 0.00
Received By jgomez Date 2016-05-06 Time 09:30 Sent To  
Notes
2016-05-06 09:45:41NEW SINGLE FAMILY RESIDENCE (R3) SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS NEED TO COMPLY WITH
 THE EQUIPMENT SIZING SECTION R403.6.1 FBC-ENERGY
 CONSERVATION, 5TH EDITION (2014). CALCULATIONS NEED TO
 BE DONE USING AN APPROVED SOFTWARE (FOR EXAMPLE ELITE,
 WRIGHTSOFT, ETC). NEED CALCULATIONS BASED ON THE
 BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION OF THE
 BUILDING. AND, NEED TO BE DONE BASED ON THE INTERIOR
 DESIGN DESIGN TEMPERATURE REQUIRED BY SEC. R302.1 OF
 FBC-ENERGY CONSERVATION. REVISE AS REQUIRED.
 CALCULATIONS SUBMITTED ARE NOT DONE WITH AN APPROVED
 SOFTWARE AND THE INTERIOR DESIGN TEMPERATURE DOESN'T
 COMPLY WITH SEC. R302.1.
  
 2- MECHANICAL PLAN M.1 SUBMITTED;
 A) SIZE OF "TRANSFER DUCTS" SHOWN ON THE SECOND FLOOR
 BEDROOMS DON'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). SHOW
 COMPLIANCE. (REPEAT COMMENT). THE TRANSFER DUCT SIZE
 WAS NOT REVISED. IN ADDITION THE CFM'S SHOWN ON PLANS
 DON'T MATCH CFM SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRED TO MATCH.
 NOTE: INFORMATION WAS CHANGED ON THE FIRST FLOOR. THE
 TRANSFER DUCTS NEED TO COMPLY WITH THE BALANCED RETURN
 AIR SEC. M1602.4. ALSO, COORDINATE CFM'S WITH EQUIPMENT
 SIZING CALCULATIONS. REVISE AS REQUIRED.
  
 B) CLARIFY HOW THE RETURN AREA GRILLS SHOWN ON THE
 FIRST FLOOR BY THE DINING AREA AND ON THE SECOND FLOOR
 BY THE ATTIC ACCESS ARE CONNECTED TO THE AIR HANDLER
 UNIT. SEC. 107.2.1 CITY AMENDMENTS. (REPEAT COMMENT).
 THE MECHANICAL PLAN WAS NOT REVISED.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By jgomez Date 2016-02-18 Time 13:42 Rev Time 0.00
Received By jgomez Date 2016-02-18 Time 13:42 Sent To Z
Notes
2016-02-18 13:47:45NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 1- EQUIPMENT SIZING CALCULATIONS SUBMITTED:
 ENGINEER WHO PREPARED THE CALCULATIONS TO PROVIDE HIS
 NAME AND ALL HIS INFORMATION AND TO PROVIDE ORIGINAL
 SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 471 FL. ST.
  
 2- MECHANICAL PLAN M.1 SUBMITTED;
 A) SIZE OF "TRANSFER DUCTS" SHOWN ON THE SECOND FLOOR
 BEDROOMS DON'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 OF FBC-RESIDENTIAL, 5TH EDITION (2014). SHOW
 COMPLIANCE.
  
 B) CLARIFY HOW THE RETURN AREA GRILLS SHOWN ON THE
 FIRST FLOOR BY THE DINING AREA AND ON THE SECOND FLOOR
 BY THE ATTIC ACCESS ARE CONNECTED TO THE AIR HANDLER
 UNIT. SEC. 107.2.1 CITY AMENDMENTS.
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
 ***PLEASE REMOVE AND REPLACE ANY REVISED DRAWING. DON'T
 STAPLE OLD COPY TO THE PLANS. SUBMIT OLD COPIES FOR
 REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712

Review Stop P PLUMBING
Rev No 6 Status P Date 2018-03-07 Cont ID  
Sent By tklarge Date 2018-03-07 Time 11:57 Rev Time 0.00
Received By tklarge Date 2018-03-07 Time 11:44 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2016-09-26 Cont ID  
Sent By tklarge Date 2016-09-26 Time 02:13 Rev Time 0.00
Received By tklarge Date 2016-09-26 Time 01:49 Sent To  
Notes
2016-09-26 02:05:261) THERE WAS ONLY ONE SET OF PLANS IN THE RESUBMITTAL
 PACKAGE. SUBMIT TWO SETS OF PLANS FOR REVIEW. WPB
 AMEND. TO FBC SEC.107.1.
 2) THE WATER HEATER ON SHT. E.1 IS STILL SHOWN AS 50
 GALLONS. CORRECT IT TO READ 70 GALS.
 3) THE WATER HEATER DETAIL ON SHT. P.1 REFERS TO THE
 2010 FBC. REVISE NOTE TO READ 2014 FBC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 4 Status F Date 2016-08-11 Cont ID  
Sent By tklarge Date 2016-08-11 Time 12:14 Rev Time 0.00
Received By tklarge Date 2016-08-11 Time 11:27 Sent To  
Notes
2016-08-11 12:12:111) THE PLANS SHOW A 50 GALLON TANK TYPE WATER HEATER
 AND THE ENERGY CALCULATIONS CALL OUT A 70 GALLON WATER
 HEATER. A TANKLESS WATER HEATER IS ALSO SHOWN IN THE
 GARAGE. CLARIFY. SEE SHEETS S.2, E.1. ON SHT. P.1 I
 CANNOT TELL WHAT THE CAPACITY OF THE WATER HEATER
 IS.2ND REQUEST
 2) THE WATER HEATER SHALL MEET THE MINIMUM EFFICIENCIES
 OF TABLE C404.2 IN CHAPT. 4 OF THE FBC, ENERGY
 CONSERVATION FOR THE TYPE OF EQUIPMENT INSTALLED.
 SUBMIT THE CORRECT EF RATING.2ND REQUEST.
 3) CORRECT THE PLANS TO COMPLY WITH THE ENERGY
 CALCULATIONS.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status F Date 2016-06-16 Cont ID  
Sent By tklarge Date 2016-06-16 Time 11:58 Rev Time 0.00
Received By tklarge Date 2016-06-16 Time 10:36 Sent To  
Notes
2016-06-16 11:58:211) THE PLANS SHOW A 50 GALLON TANK TYPE WATER HEATER
 AND THE ENERGY CALCULATIONS CALL OUT A 70 GALLON WATER
 HEATER. A TANKLESS WATER HEATER IS ALSO SHOWN IN THE
 GARAGE. CLARIFY.
 2) THE WATER HEATER SHALL MEET THE MINIMUM EFFICIENCIES
 OF TABLE C404.2 IN CHAPT. 4 OF THE FBC, ENERGY
 CONSERVATION FOR THE TYPE OF EQUIPMENT INSTALLED.
 SUBMIT THE CORRECT EF RATING.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-04-27 Cont ID  
Sent By gjohnson Date 2016-04-27 Time 13:35 Rev Time 0.00
Received By gjohnson Date 2016-04-27 Time 13:27 Sent To  
Notes
2016-04-27 13:47:242ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
 1.MISSING P-1 IN PLAN SET WPB AMEND. TOFBC SEC. 107.2.1

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By tklarge Date 2016-01-19 Time 05:52 Rev Time 0.00
Received By tklarge Date 2016-01-19 Time 05:34 Sent To  
Notes
2016-01-19 05:52:111) THE PLANS SHOW A 50 GALLON TANK TYPE WATER HEATER
 AND THE ENERGY CALCULATIONS CALL OUT AN EXTERIOR GAS
 TANKLESS WATER HEATER. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By jgomez Date 2016-05-06 Time 09:29 Rev Time 0.00
Received By jgomez Date 2016-05-06 Time 09:29 Sent To  
Notes
2016-05-06 09:29:57METAL ROOF NOA 12-0814.10. JG.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2016-02-18 Cont ID  
Sent By jgomez Date 2016-02-18 Time 13:41 Rev Time 0.00
Received By jgomez Date 2016-02-18 Time 13:41 Sent To  
Notes
2016-02-18 13:41:571- ENGINEER OF RECORD TO SPECIFY THE METAL ROOF
 FASTENING FOR ALL ROOF ZONES AS REQUIRED BY SEC.
 107.2.1.2 OF CITY AMENDMENTS.
 NOTE: CLEARLY IDENTIFY APPROVED ASSEMBLY ON METAL ROOF
 NOA 13-0114.03 SUBMITTED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES. ALSO, SEE LIMITATION #2 ON
 PAGE 7 OF 9 OF NOA SUBMITTED. COORDINATE WITH REVISED
 DESIGN PRESSURES REQUIRED BY ITEM #2 ABOVE.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2016-06-13 Cont ID  
Sent By nwier Date 2016-06-13 Time 10:49 Rev Time 0.00
Received By njwira Date 2016-06-13 Time 10:49 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-05-06 Cont ID  
Sent By ajones Date 2016-05-06 Time 11:14 Rev Time 0.00
Received By ajones Date 2016-05-06 Time 11:14 Sent To  
Notes
2016-05-06 11:14:52LANDSCAPE PEMIT REQUIRED PRIOR TO CO

Review Stop Z ZONING
Rev No 1 Status F Date 2016-01-22 Cont ID  
Sent By sgraham Date 2016-01-22 Time 15:49 Rev Time 0.00
Received By sgraham Date 2016-01-22 Time 15:49 Sent To  
Notes
2016-01-22 15:58:181/22/16 ZONING FAILED
  
 1. SUBMIT TWO CERTIFIED UP TO DATE SURVEYS AND SITE
 PLANS.
 2. DRAWING MUST BE TO SCALE IN ORDER TO DETERMINE THE
 HEIGHT OF THE ROOF