Plan Review Details - Permit 16010207
Plan Review Stops For Permit 16010207
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-03-02 Cont ID  
Sent By jwitmer Date 2016-03-02 Time 06:31 Rev Time 0.00
Received By jwitmer Date 2016-03-02 Time 06:01 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-15 Cont ID  
Sent By jwitmer Date 2016-01-15 Time 09:22 Rev Time  
Received By jwitmer Date 2016-01-15 Time 07:30 Sent To  
Notes
2016-01-15 07:59:00BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010207
 ADD: 4047 OKEECHOBEE BLVD SUITE # 126
 CONT: THE AREA GROUP CBC050008/ FL0131
 TEL: 561-603-4531
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 15/2016
 ACTION: DENIED
  
 1) THE DESIGNER OF RECORD FOR THE DRAWINGS HAS NOT
 TAKEN OWNERSHIP OF THE PLANS, THEY NEED TO PRINT THEIR
 NAME, SIGN THEIR NAME AND LICENSE NUMBER.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS
 AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO
 SECTION 107.3.5).
  
 2) IT WOULD APPEAR WHOEVER DREW THE SUBMITTED PLANS IS
 LICENSED AS A ELECTRICAL CONTRACTOR AS WELL AS EITHER A
 CGC, OR A CBC SINCE BOTH TRADES ARE SHOWN ON THE PLANS.
 A CONTRACTOR CAN ONLY DRAW PLANS FOR THE TRADE THEY ARE
 LICENSED IN UNDER THE DOLLAR AMOUNT OF $125,000.00 AND
 (ELEC) (B) COMMERCIAL 800 AMPERES OR LESS. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 105.3.1.2.
  
 3) THE PERMIT PLANS ARE DEFICIENT, THE DESIGNER OF
 RECORD DOES NOT INCLUDE WITH THE SUB-DIVIDING OF A
 TENANT SPACE, WHAT IS THE OCCUPANCY, FOR BOTH TENANT
 SPACES. THE DESIGNER OF RECORD HAS NOT MADE IT CLEAR TO
 WHICH TENANT SPACE THE PERMIT IS FOR SINCE THE TENANT
 SEPARATION WALL SHOWS ELECTRICAL FOR BOTH TENANT
 SPACES, AND DRYWALL WORK FOR BOTH TENANT SPACES BUT
 ONLY LIST WORK FOR UNIT 126.2014 FLORIDA BUILDING CODE
 W 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) THE PERMIT PLANS ARE DEFICIENT, THE DESIGNER OF
 RECORD DOES NOT INCLUDE:
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS.
 107.3.5.1.1. COMMERCIAL BUILDINGS:
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED.
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED (SEE
 TABLE 503).
 FIRE SPRIKLERS OR NOT REQUIRED?
 LIFE SAFETY SYSTEMS SHALL BE DETERMINED AND SHALL
 INCLUDE THE FOLLOWING REQUIREMENTS:
 OCCUPANT LOAD AND EGRESS CAPACITIES
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 ACCESSIBLE ROUTE
 TOILET FACILITIES
 DRINKING FOUNTAINS
  
 5) THE PLAN STATES THE TENANT SEPARATION WALL IS A NEW
 WALL BUT DOES NOT PROVIDE ACUT SECTION THROUGH THE WALL
 INDICATING THE WALL HEIGHT, IF THE DESIGNER IS
 REQUIRING THE WALL TO BE FIRE RATED, TYPE OF CONNECTION
 TO THE TOP OF THE WALL. 708.3 FIRE-RESISTANCE RATING.
 FIRE PARTITIONS SHALL HAVE A FIRERESISTANCE RATING OF
 NOT LESS THAN 1 HOUR.
  
 6) THE DESIGNER OF RECORD ALSO NEEDS TO SHOW COMPLIANCE
 OF HOW THEY ARE GOING TO ACHIEVE CODE COMPLIANCE WITH
 2014 FBC-B 1607.14 INTERIOR WALLS AND PARTITIONS THAT
 EXCEED 6 FEET (1829 MM) IN HEIGHT, INCLUDING THEIR
 FINISH MATERIALS, SHALL HAVE ADEQUATE STRENGTH TO
 RESIST THE LOADS TO WHICH THEY ARE SUBJECTED.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-03 Cont ID  
Sent By vperez Date 2016-03-03 Time 09:08 Rev Time 0.00
Received By vperez Date 2016-03-03 Time 07:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 15:10 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 15:10 Sent To  
Notes
2016-02-10 15:19:40INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE NOTE THAT THE SHEET SUBMITTED IS INSUFFICIENT
 TO PERFORM A THOROUGH REVIEW PER FBC 107 MINIMUM PLAN
 REVIEW CRITERIA. ALL NEW LOADS REQUIRE A REVISED PANEL
 LOAD CALCULATION. FLOOR PLAN MUST BE IDENTIFIED WITH
 THE CIRCUIT DESIGNATIONS. SEE BUILDING PLAN REVIEWER
 COMMENTS REGARDING TENANT SEPARATION AND DESIGNER OF
 RECORD REQUIREMENTS.
 2. FURTHER COMMENTS MAY FOLLOW PENDING COMMENTS BEING
 ADDRESSED.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-07 Cont ID  
Sent By scaldero Date 2016-03-07 Time 11:58 Rev Time 0.00
Received By scaldero Date 2016-03-07 Time 11:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-01-26 Cont ID  
Sent By scaldero Date 2016-01-26 Time 11:55 Rev Time 0.00
Received By scaldero Date 2016-01-26 Time 11:55 Sent To  
Notes
2016-01-26 11:58:54PERMIT #16010207
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
  
 1) SEE BUILDING PLAN REVIEWER COMMENTS.
  
 2) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY
 TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL ETC.
  
 3) PLANS DO NOT INDICATE WHETHER THE BUILDING/SUITES
 HAVE A FIRE ALARM SYSTEM AND/OR A FIRE SPRINKLER
 SYSTEM.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-07 Cont ID  
Sent By scaldero Date 2016-03-07 Time 11:59 Rev Time 0.00
Received By scaldero Date 2016-02-26 Time 14:30 Sent To  
Notes
2016-03-03 09:09:453/3 TO CAROLINE
2016-02-26 14:30:41B23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 15:20 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 15:20 Sent To  
Notes
2016-02-10 15:20:41TO CAROLINE/LAURA
2016-01-11 10:52:53B23