Plan Review Details - Permit 16010199
Plan Review Stops For Permit 16010199
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-23 Cont ID  
Sent By rlecky Date 2016-02-23 Time 06:55 Rev Time 0.00
Received By jwitmer Date 2016-02-23 Time 05:56 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-19 Cont ID  
Sent By jwitmer Date 2016-01-19 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2016-01-19 Time 06:31 Sent To  
Notes
2016-01-19 08:32:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010199
 ADD: 651 OKEECHOBEE BLVD. SUITE # 150
 CONT: CHANDLIER CONSTRUCTION
 TEL: 561-791-6934
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. JAN. 19/ 2016
 ACTION: DENIED
  
 1) SHEET A0.0 UNDER THE HEDING OF BUILDING NFORMATION
 LIST THIS AS A 14 STORY BUILDING, TYPE IB. PLEASE NOTE
 FOR EITHER A BUSINESS OR R2 OCCUPANCY THE BUILDING TYPE
 WOULD BE A TYPE 1A NOT A 1B. SEE 2014 FBC-B TABLE 503.
  
 2) SHEET A-1.0 INDICATES THERE ARE 278 OCCUPANTS WHERE
 DINING SURFACES ARE PROVIDED FOR THE CONSUMPTION OF
 FOOD OR DRINK, AT LEAST 5 PERCENT OF THE SEATING SPACES
 AND STANDING SPACES AT THE DINING SURFACES SHALL COMPLY
 WITH 902. THE PLANS INDICATE WHERE 13 ACCESSIBLE
 OCCUPANT LOCATIONS ON THE PLANS. THE 2014
 FBC-ACCESSIBILITY CODE SECTION 226.1 REQUIRING 5
 PERCENT OF 278 OCCUPANTS (278 X 0.5%= 13.9) OR 14
 ACCESSIBLE SPACES.
  
 3) SHEET A-1.0 INDICATES (2) BARS THE TOTAL OCCUPANT
 LOAD OF BOTH BARS IS 26. 26 X 0.5%= 1.3 OR 2 ACCESSIBLE
 SPACES SHOULD BE OFFERED AT THE BARS, THEY SHOULD BE
 DISPERSED. 2014 FBC-ACCESSIBILITY CODE 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4) NONE OF THE PLANS SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESSIBILITY CODE FOR 902.3 HEIGHT. THE TOPS OF
 DINING SURFACES AND WORK SURFACES SHALL BE 28 INCHES
 (710 MM) MINIMUM AND 34 INCHES (865 MM) MAXIMUM ABOVE
 THE FINISH FLOOR OR GROUND.
  
 5) SHEET A5.1 PLEASE PROVIDE THE CALCULATIONS FOR THE
 WEIGHT OF THE DROPPED WINE BARREL CEILING, AND PROVIDE
 CALCULATIONS FOR THE FASTENERS ULTAMATE LOADS THEY CAN
 HOLD ALLOWABLE LOADS FOR TAP CONS THAT WERE NOT
 INSPECTED AND THE DERATING TO BE TAKEN, LIST THE TYPE
 OF FASTENER, & MANUFACTURER.
  
 6) SHEET A5.1 THE DROPPED WINE BARREL CEILING, PLEASE
 PROVIDE COMPLIANCE WITH THE 2014 FBC-B SECTION 803.11.2
 SET-OUT CONSTRUCTION.
 WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF
 FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION
 AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES
 GREATER THAN SPECIFIED IN SECTION 803.11.1, CLASS A
 FINISH MATERIALS, IN ACCORDANCE WITH SECTION 803.1.1 OR
 803.1.2, SHALL BE USED.
 EXCEPTIONS:
 1. WHERE INTERIOR FINISH MATERIALS ARE PROTECTED ON
 BOTH SIDES BY AN AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-22 Cont ID  
Sent By rlecky Date 2016-02-18 Time 11:39 Rev Time 0.00
Received By rlecky Date 2016-02-18 Time 11:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-27 Cont ID  
Sent By rlecky Date 2016-01-27 Time 13:17 Rev Time 0.00
Received By rlecky Date 2016-01-27 Time 12:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-02 Cont ID  
Sent By pleduc Date 2016-03-02 Time   Rev Time 0.00
Received By pleduc Date 2016-02-29 Time 16:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-01-11 Cont ID  
Sent By scaldero Date 2016-01-11 Time 15:52 Rev Time 0.00
Received By scaldero Date 2016-01-11 Time 15:47 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2016-02-18 Cont ID  
Sent By gjohnson Date 2016-02-18 Time 08:33 Rev Time 0.00
Received By gjohnson Date 2016-02-18 Time 08:33 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2016-01-16 Cont ID  
Sent By gjohnson Date 2016-01-16 Time 08:55 Rev Time 0.00
Received By gjohnson Date 2016-01-16 Time 08:55 Sent To  
Notes
2016-01-16 09:06:121ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR ALL GAS
 APPLIANCES PER THE FBC-2014 FUEL GAS CODE SEC. 304.
 2. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
 3. SHOW PIPE SIZING ON EVER Y SECTION OF PIPE ON RISER
 DIAGRAM INCLUDING ALL EXISTING. PER WPB AMENDMENTS TO
 FBC SEC. 107.2.1.
 4. SHOW REGULATORS ON RISER DIAGRAM. PER WPB AMENDMENTS
 TO FBC SEC. 107.2.1.
 5. VENTS AND FRESH AIR INTAKES FOR WATER HEATERS ON SHT
 M-1 DO NOT MATCH SHT P-3 PLEASE CLARIFY. PER WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-04 Cont ID  
Sent By skennedy Date 2016-03-04 Time 11:52 Rev Time 0.00
Received By skennedy Date 2016-03-03 Time 12:54 Sent To  
Notes
2016-03-03 12:54:31C37

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-03-03 Cont ID  
Sent By lmarchan Date 2016-03-03 Time 12:50 Rev Time 0.00
Received By lmarchan Date 2016-02-12 Time 09:20 Sent To  
Notes
2016-02-16 09:20:28C37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-28 Cont ID  
Sent By cpuell Date 2016-01-28 Time 12:46 Rev Time 0.00
Received By cpuell Date 2016-01-08 Time 10:51 Sent To  
Notes
2016-01-08 10:52:09C35

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2016-01-19 Cont ID  
Sent By jwitmer Date 2016-01-19 Time 10:30 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-02-19 Cont ID  
Sent By ccole Date 2016-02-19 Time 12:39 Rev Time 0.00
Received By ccole Date 2016-02-19 Time 12:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-12 Cont ID  
Sent By ccole Date 2016-01-12 Time 10:51 Rev Time 0.00
Received By ccole Date 2016-01-12 Time 10:51 Sent To  
Notes
2016-01-12 11:01:481ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010199
 1/12/16
  
 1) THE REFECTIVE CEILING PLAN INDICATES RELOCATIONS OF
 AC DIFFUSERS AT THE NEW WINE BARREL CEILING. PLEASE
 SHOW THESE RELOCATIONS AND DETAILS ON SHEET M1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW
 GAS-FIRED WATER HEATER AND COOKING APPLIANCES. PLEASE
 NOTE THE GWH DETAIL ON SHEET P-3 DOES NOT APPEAR TO
 MATCH THE TYPE OF UNIT SHOWN ON M-1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-03-04 Cont ID  
Sent By tklarge Date 2016-03-04 Time 06:46 Rev Time 0.00
Received By tklarge Date 2016-03-04 Time 06:16 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-18 Cont ID  
Sent By gjohnson Date 2016-02-18 Time 08:33 Rev Time 0.00
Received By gjohnson Date 2016-02-18 Time 08:33 Sent To  
Notes
2016-02-18 08:40:46 
 2ND REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
  
  
  
  
  
  
  
 (1). AAV ARE NOT ALLOWED BELOW THE FORTH FLOOR FROM
 THE ROOF WITH OUT A RELIEF VENT ON THE BRANCH AND SHALL
 COMPLY WITH FBC PL. SEC
 918.3.1 HORIZONTAL BRANCHES.
 INDIVIDUAL AND BRANCH-TYPE AIR ADMITTANCE VALVES SHALL
 VENT ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND
 CONNECT TO A HORIZONTAL BRANCH DRAIN. WHERE THE
 HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL CONNECT
 TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE STACK AND
 THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED TO THE
 HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL BE SIZED
 IN ACCORDANCE WITH SECTION 906.2 AND INSTALLED IN
 ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL BE
 PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. THIS
 IS THE SECOND REQUEST.

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-16 Cont ID  
Sent By gjohnson Date 2016-01-16 Time 07:47 Rev Time 0.00
Received By gjohnson Date 2016-01-16 Time 07:47 Sent To  
Notes
2016-01-16 08:05:521ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PROVIDE A HOT WATER RECIRC SYSTEM TO COMPLY WITH.
 FBC PL SEC 607.2 HOT OR TEMPERED WATER SUPPLY TO
 FIXTURES.
 THE DEVELOPED LENGTH OF HOT OR TEMPERED WATER PIPING,
 FROM THE SOURCE OF HOT WATER TO THE FIXTURES THAT
 REQUIRE HOT OR TEMPERED WATER, SHALL NOT EXCEED 50 FEET
 (15 240 MM). RECIRCULATING SYSTEM PIPING AND
 HEAT-TRACED PIPING SHALL BE CONSIDERED TO BE SOURCES OF
 HOT OR TEMPERED WATER
 2.WATER HEATER NOTE SHOWS WH BEING SET AT 140 PROVIDE
 TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE 1070
 SET AT 120 TO HAND WASHING SINKS AND 110 FOR PUBLIC
 RESTROOMS. PER FBC ENERGY. C404.3 TEMPERATURE CONTROLS.
 SERVICE WATER-HEATING EQUIPMENT SHALL BE PROVIDED WITH
 CONTROLS TO ALLOW A SETPOINT OF 110F (43C) FOR
 EQUIPMENT SERVING DWELLING UNITS AND 90F (32C) FOR
 EQUIPMENT SERVING OTHER OCCUPANCIES. THE OUTLET
 TEMPERATURE OF LAVATORIES IN PUBLIC FACILITY REST ROOMS
 SHALL BE LIMITED TO 110F (43C).
 3. WHAT TEMPERATURE WILL THE WATER BE DRAINING FROM THE
 HOT WELL #19 ON KIT SCHEDULE IT SHALL COMPLY WITH FBC
 PL. SEC 701.7 WASTE WATER WHERE DISCHARGED INTO THE
 BUILDING DRAINAGE SYSTEM SHALL BE AT A TEMPERATURE NOT
 GREATER THAN 140?
 4. SHEET INDEX INDICATES DEMO PLAN BUT IT IS NOT IN
 PLAN SET PLEASE PROVIDE. PER WPB AMEND. TO FBC SEC.
 107.2.1
 5. PROVIDE MANUFACTURE SPECS ON SUB WATER MATER.PER WPB
 AMEND. TO FBC SEC. 107.2.1
 6. LIST MANUFACTURE AND MODEL OF BACKFLOW DEVICES. PER
 WPB AMEND. TO FBC SEC. 107.2.1
 7. ADDRESS ON PLANS IS WRONG PLEASE CORRECT. PER WPB
 AMEND. TO FBC SEC. 107.2.1
 8. AAV ARE NOT ALLOWED ON THE FIRST FLOOR OF THIS
 BUILDING. PER FBC PL. SEC
 918.3.1 HORIZONTAL BRANCHES.
 INDIVIDUAL AND BRANCH-TYPE AIR ADMITTANCE VALVES SHALL
 VENT ONLY FIXTURES THAT ARE ON THE SAME FLOOR LEVEL AND
 CONNECT TO A HORIZONTAL BRANCH DRAIN. WHERE THE
 HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR BRANCH
 INTERVALS FROM THE TOP OF THE STACK, THE HORIZONTAL
 BRANCH SHALL BE PROVIDED WITH A RELIEF VENT THAT SHALL
 CONNECT TO A VENT STACK OR STACK VENT, OR EXTEND
 OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL CONNECT
 TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE STACK AND
 THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED TO THE
 HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL BE SIZED
 IN ACCORDANCE WITH SECTION 906.2 AND INSTALLED IN
 ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL BE
 PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.

Review Stop Z ZONING
Rev No 2 Status P Date 2016-02-29 Cont ID  
Sent By eschneid Date 2016-02-29 Time 10:23 Rev Time 0.25
Received By eschneid Date 2016-02-29 Time 10:23 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2016-01-28 Cont ID  
Sent By eschneid Date 2016-01-28 Time 11:52 Rev Time 0.00
Received By eschneid Date 2016-01-28 Time 11:52 Sent To  
Notes
***NONE***