Plan Review Details - Permit 16010117
Plan Review Stops For Permit 16010117
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 18:35 Rev Time 0.00
Received By shill Date 2018-08-11 Time 18:35 Sent To  
Notes
2018-08-11 18:36:00****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A. A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  
 B. COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 11:23 Rev Time 0.00
Received By shill Date 2018-06-30 Time 11:23 Sent To  
Notes
2018-06-30 11:23:49SEE PLUMBING & FIRE COMMENTS; APPLICABLE FOR BUILDING
 REVIEW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2018-02-27 Cont ID  
Sent By jwitmer Date 2018-02-27 Time 06:45 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 06:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2018-02-08 Cont ID  
Sent By jwitmer Date 2018-02-08 Time 08:02 Rev Time 0.00
Received By jwitmer Date 2018-02-07 Time 17:03 Sent To  
Notes
2018-02-08 07:56:32BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 5TH REVIEW
 DATE: THURS. FEB. 08/ 2018
 ACTION: DENIED
  
  
 1) DISCREPANCY IN PLANS. IN THE NEW ADDITION SHEETS
 A-201. P1 & E1 ALL SHOW A SET OF DOUBLE DOORS ON THE
 WEST WALL THAT COMMUNICATES WITH THE BUILDING TO THE
 WEST ABOUT 3/4 OF THE WAY FROM THE FRONT OF THE
 BUILDING. THE REMAINDER OF THE PLANS DOES NOT SHOW A
 DOOR IN THIS WALL. DISCREPANCY IN PLANS. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2017-12-15 Cont ID  
Sent By jwitmer Date 2017-12-15 Time 13:20 Rev Time 0.00
Received By jwitmer Date 2017-12-15 Time 09:44 Sent To  
Notes
2017-12-15 13:34:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 4TH REVIEW
 DATE: FRI. DEC. 15/ 2017
 ACTION: BUILDING PROVISO
  
 1) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.3.4.2 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31(D) ROOFING PRODUCTS AND ASSEMBLIES.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST., WEST PALM BEACH. FL 33402
 TEL: 561-805-6715 / FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2017-04-14 Cont ID  
Sent By jwitmer Date 2017-04-14 Time 16:19 Rev Time 0.00
Received By jwitmer Date 2017-04-14 Time 10:24 Sent To  
Notes
2017-04-14 16:19:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 3RD REVIEW
 DATE: FRI. APRIL 14/ 2017
 ACTION: DENIED
  
 1A) 3ND REQUEST. THE SUBMITTED PAPERWORK IS FOR TAX
 PURPOSES ONLY, IT IS NOT A UNITY OF TITLE, IT HAS BEEN
 REVIEWED BY BOTH MANUEL GONZALEZ AND VINCENT J NOEL.
 1B) COMPLIED. THE PERMIT APPLICATION INDICATES WORK
 UNDER THIS PERMIT WILL BE LOCATED AT 431 BUNKER BY THE
 PCN 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARS
 THIS INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE
 LOT JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT
 417 BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCREPANCY
 IN INFORMATION. ADDITIONAL INFORMATION
 REQUIRED.107.2.1.3.
  
 2) COMPLIED. THE COVERSHEET, A-000 INDICATES THE PLANS
 UNDER THE HEADING APPLICABLE CODES IS DESIGNED TO THE
 2014 FBC-B BUT UNDER THE GENERAL NOTES THE PLANS
 INDICATE THE DESIGN IS UNDER THE 2007 FBC EDITION.
 PLEASE UPDATE ALL REFERENCES TO THE 2007 FBC. THE 2014
 FBC OR THE 5TH EDITION OF THE FLORIDA BUILDING CODE WAS
 ADOPTED STATEWIDE ON JUNE 30/2015.
  
 3A) 3RD REQUEST.431 BUNKER RD. THE COVERSHEET, A-000
 INDICATES WITH THE PROPOSED 1,680 SQ. FT. ADDITION TO
 AN EXISTING 7909 SQ. FOOTAGE EXISTING BUILDING TOTALING
 9,589 SQ. FT. W/ MEZZANINE INCLUDED. THE ADDITION
 TRANSGRESSES THE PROPERTY LINE AND THAT WILL REQUIRE
 THE UNITY OF TITLE. THE OTHER BUILDING LOCATED AT 417
 BUNKER WILL BECOME A SEPARATE BUILDING WITH A 3 HOUR
 FIRE WALL THAT WILL MEET ALL OF THE FIRE WALL
 REQUIREMENTS. TO BE DISCUSSED LATER ON IN THIS REVIEW.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 3B) THE SECOND ISSUE THAT WILL NEED TO BE ADDRESSED IS
 THE 431 BUNKER RD. BUILDING BEING DECLARED BUILDING
 TYPE VB AND A S1 STORAGE OCCUPANCY OF 9,589 SQ. FT.
 NON-SPRINKLERED BUILDING(BUILDING # 1). IN THE 2014
 FBC-B TABLE 503 ALLOWS FOR THIS OCCUPANCY AND BUILDING
 TYPE AN ALLOWABLE 9,000 SQ. FT. PLEASE PROVIDE HOW
 COMPLIANCE WITH TABLE FBC-B 503 AND BUILDING AREA
 MODIFICATIONS FOR THIS BUILDING AS WELL THE BUILDING AT
 417 BUNKER RD. WITH AN AREA OF 9805 SQ. FT. (BUILDING #
 2).
  
 4) NEW COMMENT. SHEET A-201 THERE IS A DISCREPANCY IN
 THE PLANS. THE BUILDING AT 431 BUNKER RD. ON THE
 EXISTING BUILDING SHOW A DOOR THROUGH INTO THE NEW
 ADDITION (PROPOSED PLAN) EAST SIDE OF THE EXISTING
 BUILDING. UNDER THE ISSUED PERMIT 14090842 ON THE EAST
 WALL THERE WAS NO DOOR. PLEASE PROVIDE ADDITIONAL
 INFORMATION ABOUT THIS OPENING. 107.2.1.3.
  
 5) 2ND REQUEST. THE SUBMITTED ROOFING PRODUCT APPROVAL
 REPORT FL 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION
 EVERGUARD PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF
 34 HAS CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF
 THE SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE
 APPENDIX AS TO WHICH WILL BE USED IN THE ROOF
 APPLICATION. NOTE IDENTIFY THE SUB-SYSTEM AND NOT THE
 POUNDS PER SQUARE FOOT AND IF THERE IS A ASTERISK OR
 NOT. PAGE 4 OF 5 LIMITATION 5.8 SYSTEMS MARKED WITH A
 ASTERISK ENHANCED FASTENING IS NOT ALLOWED.
 SHEET A-401 INDICATES THE USE OF ROOF TOP INSULATION OF
 R-30/ METAL B DECK.
  
 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-03-29 Cont ID  
Sent By   Date 2016-03-29 Time 15:33 Rev Time 0.00
Received By   Date 2016-03-29 Time 13:22 Sent To  
Notes
2016-03-29 15:25:22BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 NOTICE!!!!!!!!!!!!! CHAPTER 553.80(2)(B) FLORIDA
 STATUTES STATES THAT A LOCAL GOVERNMENT SHALL IMPOSE A
 FEE OF FOUR TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE
 REJECTED (3) OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.
  
 2ND REVIEW
 DATE: TUES. MARCH 29/ 2016
 ACTION: DENIED
  
 1) 2ND REQUEST. THE SUBMITTED PAPERWORK IS FOR TAX
 PURPOSES ONLY, IT IS NOT A UNITY OF TITLE, IT HAS BEEN
 REVIEWED BY BOTH MANUEL GONZALEZ AND VINCENT J NOEL.
 THE PERMIT APPLICATION INDICATES WORK UNDER THIS PERMIT
 WILL BE LOCATED AT 431 BUNKER BY THE PCN
 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARS THIS
 INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE LOT
 JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT 417
 BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCREPANCY IN
 INFORMATION. ADDITIONAL INFORMATION REQUIRED.107.2.1.3.
  
 2) COMPLIED. THE COVERSHEET, A-000 INDICATES THE PLANS
 UNDER THE HEADING APPLICABLE CODES IS DESIGNED TO THE
 2014 FBC-B BUT UNDER THE GENERAL NOTES THE PLANS
 INDICATE THE DESIGN IS UNDER THE 2007 FBC EDITION.
 PLEASE UPDATE ALL REFERENCES TO THE 2007 FBC. THE 2014
 FBC OR THE 5TH EDITION OF THE FLORIDA BUILDING CODE WAS
 ADOPTED STATEWIDE ON JUNE 30/2015.
  
 3)2ND REQUEST. THE COVERSHEET, A-000 INDICATES WITH THE
 PROPOSED 1,6778 SQ. FT. ADDITION THE TOTAL SQ. FOOTAGE
 OF THE BUILDING IS 19,389 SQ. FT. THE 431 BUNKER RD.
 BUILDING WITH MEZZANINE SQ. FOOTAGE IS 7912 SQ, FT. THE
 417 BUNKER RD. BUILDING FROM THE PROPERTY APPRAISERS
 SITE IS 9780 SQ. FT. PLUS THE NEW PROPOSED ADDITION OF
 1,680 SQ. FT. IS 19,372 SQ. FT. THIS MEANS THE
 BUILDINGS ARE CROSSING OVER PROPERTY LINES AND WILL
 REQUIRE A UNITY OF TITLE. THE OTHER ISSUE SHEET A-202
 SHOWS NEW OPENINGS IN THE PROPERTY LINE WALL.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 4) THE COVERSHEET, A-000 INDICATES THE TOTAL SQUARE
 FOOT AREA OF THE COMBINED BUILDINGS TO ENCOMPASS 19,389
 SQUARE FEET. PLEASE SEE THE 2014 FBC-EXISTING BUILDING
 SECTION 1101.2 CREATION OR EXTENSION OF NONCONFORMITY.
 AN ADDITION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL
 SYSTEMS.
  
 4A) 2ND REQUEST. THE PLANS INDICATE THE COMBINED SQ.
 FT. AREA OF THE 2 BUILDINGS ARE OVER 19,000 SQUARE
 FEET. THE AREA LIMITATION OF TABLE 503 IS 9,000 SQ. FT.
 AND ONLY ONE STORY FOR A S1 OCCUPANCY/ NON-SPRINKLERED.
 .
 1ST REVIEW COMMENT. PLEASE PROVIDE WITH THE TOTAL
 COMBINED AREA OF THE 2 BUILDINGS (417 & 431 BUNKER) OF
 19,389 SQ. FT. THE MINIMUM BUILDING TYPE SEE 2014 FBC-B
 503.
 1102.2 AREA LIMITATIONS. NO ADDITION SHALL INCREASE THE
 AREA OF AN EXISTING BUILDING BEYOND THAT PERMITTED
 UNDER THE APPLICABLE PROVISIONS OF CHAPTER 5 OF THE
 FLORIDA BUILDING CODE, BUILDING FOR NEW BUILDINGS
 UNLESS FIRE SEPARATION AS REQUIRED BY THE FLORIDA
 BUILDING CODE, BUILDING IS PROVIDED.
  
 4B) 2ND REQUEST. NON-SPRINKLERED BUILDING TO COMPLY
 WITH:
 PLEASE SEE THE 2014 EXISTING BUILDING CODE SECTION
 1102.3 FIRE PROTECTION SYSTEMS. EXISTING FIRE AREAS
 INCREASED BY THE ADDITION SHALL COMPLY WITH CHAPTER 9
 OF THE FLORIDA BUILDING CODE, BUILDING. NOT ONLY IS
 THERE AN ADDITION BUT A UNITY OF TITLE INCREASING THE
 SIZE OF THE BUILDING TO OVER 19,000 SQUARE FEET.
  
 2014 FBC-B [F] 903.2.9 GROUP S-1. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL
 BUILDINGS CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF
 THE FOLLOWING CONDITIONS EXISTS:
 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEE.
 5. A GROUP S-1 OCCUPANCY USED FOR THE STORAGE OF
 UPHOLSTERED FURNITURE OR MATTRESSES EXCEEDS 2,500
 SQUARE FEET.
  
 5) THE SUBMITTED ROOFING PRODUCT APPROVAL REPORT FL
 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION EVERGUARD
 PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF 34 HAS
 CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF THE
 SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE APPENDIX
 AS TO WHICH WILL BE USED IN THE ROOF APPLICATION. NOTE
 IDENTIFY THE SUB-SYSTEM AND NOT THE POUNDS PER SQUARE
 FOOT AND IF THERE IS A ASTERISK OR NOT. PAGE 4 OF 5
 LIMITATION 5.8 SYSTEMS MARKED WITH A ASTERISK ENHANCED
 FASTENING IS NOT ALLOWED.
 SHEET A-401 INDICATES THE USE OF ROOF TOP INSULATION OF
 R-30/ METAL B DECK.
  
 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-22 Cont ID  
Sent By jwitmer Date 2016-01-22 Time 16:48 Rev Time  
Received By jwitmer Date 2016-01-21 Time 16:45 Sent To  
Notes
2016-01-22 15:46:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI. JAN. 22/ 2016
 ACTION: DENIED
  
 1) THE PERMIT APPLICATION INDICATES WORK UNDER THIS
 PERMIT WILL BE LOCATED AT 431 BUNKER BY THE PCN
 73-43-44-04-05-000-0110. SHEET A-100 IT APPEARSTHIS
 INFILL OF A BUILDING IS ACTUALLY LOCATED ON THE LOT
 JUST EAST OF THE PROPERTY LOCATED AT 431 BUNKER, AT 417
 BUNKER RD, PCN 74-43-44-04-05-000-0070. DISCRPANCY IN
 INFORMATION. ADDITIONAL INFORMATION REQUIRED.107.2.1.3.
  
 2) THE COVERSHEET, A-000 INDICATES THE PLANS UNDER THE
 HEADING APPLICABLE CODES IS DESIGNED TO THE 2014 FBC-B
 BUT UNDER THE GENERAL NOTES THE PLANS INDICATE THE
 DESIGN IS UNDER THE 2007 FBC EDITION. PLEASE UPDATE ALL
 REFERENCES TO THE 2007 FBC. THE 2014 FBC OR THE 5TH
 EDITION OF THE FLORIDA BUILDING CODE WAS ADOPTED
 STATEWIDE ON JUNE 30/2015.
  
 3) THE COVERSHEET, A-000 INDICATES WITH THE PROPOSED
 1,6778 SQ. FT. ADDITION THE TOTAL SQ. FOOTAGE OF THE
 BUILDING IS 19,389 SQ. FT. THE 431 BUNKER RD. BUILDING
 WITH MEZZANINE SQ. FOOTAGE IS 7912 SQ, FT. THE 417
 BUNKER RD. BUILDING FROM THE PROPERTY APPRAISERS SITE
 IS 9780 SQ. FT. PLUS THE NEW PROPOSED ADDTION OF 1,680
 SQ. FT. IS 19,372 SQ. FT. THIS MEANS THE BUILDINGS ARE
 CROSSING OVER PROPERTY LINES AND WILL REQUIRE A UNITITY
 OF TITLE. THE OTHER ISSUE SHEET A-202 SHOWS NEW
 OPENJNGS IN THE PROPERTY LINE WALL.
  
 UNITY OF TITLE.
 THE PROPOSED BUILDING STRUCTURE TRANSGRESSES LEGAL
 BOUNDARY LINES BETWEEN THE LOTS WHICH COMBINE TO FORM
 'THE SITE'. A 'UNITY OF TITLE' SHALL BE
 RECORDED AT THE COUNTY COURTHOUSE. SUBMIT A COPY OF THE
 RECORDED 'UNITY OF TITLE' DOCUMENT SO THAT FBC TABLE
 601 BOUNDARY LINE REQUIREMENTS MAY BE DEEMED NOT
 APPLICABLE.
 SEE WEBSITE FOR APPLICATION:
 HTTP://WWW.WPB.ORG/ENGINEERING/ENG_FORMS.PHP
 "APPLICATION FOR UNITY OF TITLE"
 HTTP://WWW.WPB.ORG/ENGINEERING/UPLOADS/2010-10-12-14-45
 -38-UNITYOFTITLE3.PDF
 VINCENT J NOEL
 SURVEYOR/REAL ESTATE SUPERVISOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 PHONE: 494-1040 EXT: 1096
 FAX: 494-1116
 E-MAIL: [email protected]
 *********************************************
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 4) THE COVERSHEET, A-000 INDICATES THE TOTAL SQUARE
 FOOT AREA OF THE COMBINED BUILDINGS TO ENCOMPASS 19,389
 SQUARE FEET. PLEASE SEE THE 2014 FBC-EXISITNG BUILDING
 SECTION 1101.2 CREATION OR EXTENSION OF NONCONFORMITY.
 AN ADDITION SHALL NOT CREATE OR EXTEND ANY
 NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE
 ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY,
 STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR
 THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL
 SYSTEMS.
  
 4A) PLEASE PROVIDE WITH THE TOTAL COMBINED AREA OF THE
 2 BUILDINGS (417 & 431 BUNKER) OF 19,389 SQ. FT. THE
 MINIMUM BUILDING TYPE SEE 2014 FBC-B 503.
 1102.2 AREA LIMITATIONS. NO ADDITION SHALL INCREASE THE
 AREA OF AN EXISTING BUILDING BEYOND THAT PERMITTED
 UNDER THE APPLICABLE PROVISIONS OF CHAPTER 5 OF THE
 FLORIDA BUILDING CODE, BUILDING FOR NEW BUILDINGS
 UNLESS FIRE SEPARATION AS REQUIRED BY THE FLORIDA
 BUILDING CODE, BUILDING IS PROVIDED.
  
 4B) UNKNOWN IF BUILDING ADDRESSED 417 BUNKER IS FIRE
 SPRINKLERED? THE BUILDING AT 431 BUNKER IS
 NON-SPRINKLERED CURRENTLY. PLEASE SEE THE 2014 EXISITNG
 BUILDING CODE SECTION 1102.3 FIRE PROTECTION SYSTEMS.
 EXISTING FIRE AREAS INCREASED BY THE ADDITION SHALL
 COMPLY WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE,
 BUILDING. NOT ONLY IS THERE AN ADDITION BUT A UNITITY
 OF TITLE INCREASING THE SIZE OF THE BUILDING TO OVER
 19,000 SQUARE FEET.
  
 2014 FBC-B [F] 903.2.9 GROUP S-1. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT ALL
 BUILDINGS CONTAINING A GROUP S-1 OCCUPANCY WHERE ONE OF
 THE FOLLOWING CONDITIONS EXISTS:
 1. A GROUP S-1 FIRE AREA EXCEEDS 12,000 SQUARE FEE.
 5. A GROUP S-1 OCCUPANCY USED FOR THE STORAGE OF
 UPHOLSTERED FURNITURE OR MATTRESSES EXCEEDS 2,500
 SQUARE FEET.
  
 5) THE SUBMITTED ROOFING PRODUCT APPROVAL REPORT FL
 16739-R7 SHEET 4OF 5 PRODUCT DESCRIPTION EVERGUARD
 PVC-60 IS UNDERLINED. APPENDIX1, ON PAGE 1 OF 34 HAS
 CIRCLED THE DECK TYPE STEEL DECK. NOTE NONE OF THE
 SUB-SYSTEMS ARE IDENTIFIED IN THE REST OF THE APPENDIX
 AS TO WHICH WILL BE USED IN THE ROOF APPLICATION. NOTE
 IDENTIFY THE SUB-SYSTEM AND NOT THE POUNDS PER SQUARE
 FOOT AND IF THERE IS A ASTERISK OR NOT. PAGE 4 OF 5
 LIMITATION 5.8 SYSTEMS MARKED WITH A ASTERISK ENHANCED
 FASTENING IS NOT ALLOWED.
  
 6) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2018-06-28 Cont ID  
Sent By jpearson Date 2018-06-28 Time 11:31 Rev Time 0.00
Received By jpearson Date 2018-06-28 Time 10:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2018-03-14 Cont ID  
Sent By jpearson Date 2018-03-14 Time 10:48 Rev Time 0.00
Received By jpearson Date 2018-03-14 Time 09:41 Sent To  
Notes
2018-03-14 10:48:32APPROVED WITH EXCEPTIONS, WHICH ARE NOTED ON PLAN:
  
 1) PROVIDE ACCURATE LOAD CALCULATION FOR PANEL AND
 SERVICE TO SHOW CAPACITY IS ADEQUATE. NEC 220
 2) EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE FED
 FROM THE GENERAL LIGHTING CIRCUIT IN THE AREA. PROVIDE
 CORRECTION. NEC 700.12(F)
 3) CIRCUIT NUMBER B-11 IS SHOWN FOR RECEPTACLE OUTLETS
 AND FOR AHU-3. CLARIFY AND/OR CORRECT. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2017-04-06 Cont ID  
Sent By rlecky Date 2017-04-06 Time 11:25 Rev Time 0.00
Received By rlecky Date 2017-04-06 Time 10:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-17 Cont ID  
Sent By rlecky Date 2016-03-17 Time 13:50 Rev Time 0.00
Received By rlecky Date 2016-03-17 Time 13:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-02 Cont ID  
Sent By rlecky Date 2016-02-02 Time 14:00 Rev Time 0.00
Received By rlecky Date 2016-02-02 Time 13:44 Sent To  
Notes
2016-02-02 13:59:53PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL PLAN WITH THE FOLLOWING:
  ELECTRICAL RISER PLAN SHOWING ALL FEEDERS, DISCONNECTS
 AND PANEL BOARDS
  LOCATION OF THE ELECTRICAL SERVICE AND MAIN
 DISCONNECTS
  LOCATION OF ALL ELECTRICAL PANELBOARDS
 SAFE WORKING SPACE AT ELECTRICAL DISCONNECTS AND
 PANELBOARDS
  EXIT AND EMERGENCY ILLUMINATION
  
 PROVIDE ELECTRIC NOTES ON THE PLAN INDICATING THE
 FOLLOWING:
  GENERAL PURPOSE RECEPTACLES INSTALLED IN THE
 BATHROOMS, KITCHENS, ROOFTOPS, OUTDOORS, WITHIN SIX
 FEET OF SINKS,AT ELECTRIC DRINKING FOUNTAINS, AND
 VENDING MACHINES ARE GFCI PROTECTED.
  ALL DISCONNECTS SHALL BE LEGIBLY MARKED TO INDICATE
 THEIR PURPOSE.
  
 PROVIDE LIGHTING CONTROLS FOR ENERGY CONSERVATION SO
 THAT THE INTERIOR AND EXTERIOR LIGHTING CONTROLS
 PROVIDED FUNCTION IN ACCORDANCE WITH THE FLORIDA ENERGY
 CODE. EXTERIOR AUTOMATIC CONTROLS SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 VERIFY THE LIGHTING AND SIGN TIME CLOCKS HAVE BATTERY
 BACKUP. FBC ENERGY CONSERVATION 505.2
  
 PROVIDE A LIGHTING DENSITY SUMMARY ON THE ELECTRIC PLAN
 WHICH SHOWS COMPLIANCE WITH THE FLORIDA BUILDING ENERGY
 CODE REQUIREMENTS. FBC ENERGY CONSERVATION 505.5;
 505.5.3; T. 505.5.3
  
 CODE REFERENCES:
  FBC EXISTING BUILDING 908.2, 908.3, 908.4
  NEC 110.22, 110.26, 210. 8, 215.5, 422.51, 422.52
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status N Date 2018-01-30 Cont ID  
Sent By shill Date 2018-01-30 Time   Rev Time 1.00
Received By mgonzale Date 2018-01-30 Time   Sent To I
Notes
2018-01-30 16:24:06PLANS ARE UNDER REVIEW THRU A SEPARATE PLAN REVIEW
 SUBMITTAL TO ENGINEERING SERVICES DEPARTMENT.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2017-05-15 Cont ID  
Sent By shill Date 2017-05-15 Time 11:16 Rev Time 0.00
Received By shill Date 2017-05-15 Time 11:16 Sent To  
Notes
2017-05-15 11:17:31ENGINEERING APPROVAL VIA FORMAL SUBMITTAL TO
 ENGINEERING DEPARTMENT REQUIRED
 PRIOR TO PERMIT ISSUANCE THIS WILL BE VERIFIED WITH
 ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2016-06-14 Cont ID  
Sent By mgonzale Date 2016-06-14 Time   Rev Time 0.25
Received By mgonzale Date 2016-06-14 Time   Sent To  
Notes
2016-06-14 15:53:04FORMAL SITE PLAN APPROVAL REQUIRED.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2016-03-02 Cont ID  
Sent By mgonzale Date 2016-03-02 Time   Rev Time 0.50
Received By mgonzale Date 2016-03-02 Time 13:36 Sent To Z
Notes
2016-03-02 13:39:14ADDRESS PLANNING'S COMMENTS. THANKS!

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2018-07-13 Cont ID  
Sent By pleduc Date 2018-07-13 Time   Rev Time 0.00
Received By pleduc Date 2018-07-13 Time 13:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status F Date 2018-06-15 Cont ID  
Sent By pleduc Date 2018-06-15 Time   Rev Time 0.00
Received By pleduc Date 2018-06-14 Time 15:26 Sent To  
Notes
2018-06-15 12:36:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.1 - THE DOUBLE WALL SEPARATING THE
 EXISTING OCCUPANY DOES NOT INDICATE A FIRE RATING OR
 LISTING. IS IT THE INTENT TO HAVE THIS WALL NONRATED?
  
 PER NFPA 101, CHAPTER 6
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE-RESISTIVE
 ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3,
 TABLE 6.1.14.4.1(A),
 AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED
 BY APPROVED
 EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY
 6.1.14.4.6.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE JUSTIFICATION WITH
 SPECIFIC CODE REFERENCES.
  
  
 2) SHEET A 1.1 - TWO SETS OF DOUBLE DOORS ARE INDICATED
 ON THE OTHER EXISTING OCCUPANCY THAT DOES NOT INDICATE
 A FIRE RATING. IS IT THE INTENT TO CONNECT THESE SPACES
 AS ONE OCCUPANCY? IS IT THE INTENT TO SEPARATED THESE
 TWO SPACES AT SOME TIME IN THE FUTURE? IF FUTURE
 SEPARATION IS INTEND, THIS WALL SHOULD CARRY A FIRE
 RATING.
  
 PLEASE REVIEW AND ADDRESS.
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2018-02-06 Cont ID  
Sent By pleduc Date 2018-02-06 Time   Rev Time 0.00
Received By pleduc Date 2018-02-06 Time 09:18 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2017-12-06 Cont ID  
Sent By pleduc Date 2017-12-06 Time   Rev Time 0.00
Received By pleduc Date 2017-12-06 Time 10:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2017-04-11 Cont ID  
Sent By pleduc Date 2017-04-11 Time   Rev Time 0.00
Received By pleduc Date 2017-04-10 Time 16:21 Sent To  
Notes
2017-04-10 16:51:47THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) SHEET A 100 - ANY PLANNED RACK STORAGE SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS FOR APPROVAL.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-16 Cont ID  
Sent By pleduc Date 2016-03-16 Time   Rev Time 0.00
Received By pleduc Date 2016-03-16 Time 15:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-01-15 Cont ID  
Sent By pleduc Date 2016-01-15 Time   Rev Time 0.00
Received By pleduc Date 2016-01-15 Time 14:10 Sent To  
Notes
2016-01-15 14:47:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. SHEET - 201 - ON THE DOOR SCHEDULE UNDER HARDWARE
 SET THE NUMBER 1 IS PROVIDED. THERE IS NO INDICATION OF
 WHAT THAT # 1 REPRESENTS. PLEASE PROVIDE THE HARDWARE
 SET TYPE AND LOCKING MECHANISM THAT COMPLIES WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS.
  
 2. SHEET - 201 - THERE IS NOT INDICATION OF AN EXIT
 SIGN AT THE NEW INSTALLED DOOR COMPLYING WITH NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 3. SHEET - 201 - THERE IS NO INDICATION OF EMERGENCY
 LIGHTING ALONG THE PATH OF EGRESS COMPLYIING WITH NFPA
 101, CHAPTER 7, MEANS OF EGRESS.
  
 4. SHEET 202 - PER FLORIDA 69A-60.0081; NOTICE SIGNAGE
 IS REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 A. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 B. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 C. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2018-08-13 Cont ID  
Sent By lmarchan Date 2018-08-13 Time 11:11 Rev Time 0.00
Received By lmarchan Date 2018-07-11 Time 16:36 Sent To  
Notes
2018-07-12 16:36:58C19

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2018-06-30 Cont ID  
Sent By shill Date 2018-06-30 Time 11:23 Rev Time 0.00
Received By shill Date 2018-06-11 Time 16:04 Sent To  
Notes
2018-06-12 16:05:12C19

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date   Cont ID  
Sent By   Date 2018-03-23 Time   Rev Time 0.00
Received By lmarchan Date 2018-03-21 Time 15:53 Sent To  
Notes
2018-03-22 15:53:40IMPACT FEES ROUTED TO JWITMER

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2018-03-14 Cont ID  
Sent By eschneid Date 2018-03-14 Time 16:03 Rev Time 0.00
Received By eschneid Date 2018-02-21 Time 15:44 Sent To  
Notes
2018-02-22 15:45:05C21

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2018-02-20 Time   Rev Time 0.00
Received By lmarchan Date 2018-01-31 Time 09:53 Sent To  
Notes
2018-02-02 09:53:23C15

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2018-01-31 Cont ID  
Sent By shill Date 2018-01-31 Time 09:20 Rev Time 0.00
Received By cpuell Date 2017-12-04 Time 15:25 Sent To  
Notes
2017-12-05 15:25:43C15

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 13:45 Rev Time 0.00
Received By gjohnson Date 2017-04-03 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-06-24 Cont ID  
Sent By skennedy Date 2016-06-24 Time 09:48 Rev Time 0.00
Received By skennedy Date 2016-03-14 Time 09:23 Sent To  
Notes
2016-03-15 09:25:53C08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-03-09 Cont ID  
Sent By lmarchan Date 2016-03-09 Time 13:59 Rev Time 0.00
Received By lmarchan Date 2016-01-06 Time 13:17 Sent To  
Notes
2016-01-13 13:17:59C07

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 7 Status P Date 2018-03-23 Cont ID  
Sent By jwitmer Date 2018-03-23 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2018-03-23 Time 07:15 Sent To  
Notes
2018-03-23 07:27:13PALM BEACH COUNTY IMPACT FEES;
 RECEIPT NUMBER 2018-0321-125
 MU-2018-008846-0000
 FEES PAID: $403.76
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 6 Status F Date 2018-02-27 Cont ID  
Sent By jwitmer Date 2018-02-27 Time 06:43 Rev Time 0.00
Received By jwitmer Date 2018-02-27 Time 06:43 Sent To  
Notes
2018-02-27 06:44:07IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 5 Status F Date   Cont ID  
Sent By   Date 2018-02-07 Time   Rev Time 0.00
Received By   Date 2018-02-07 Time   Sent To  
Notes
2018-02-27 06:44:30IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status F Date   Cont ID  
Sent By   Date 2017-12-15 Time   Rev Time 0.00
Received By   Date 2017-12-15 Time   Sent To  
Notes
2018-02-27 06:45:05IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2017-12-15 Cont ID  
Sent By jwitmer Date 2017-12-15 Time 13:19 Rev Time 0.00
Received By jwitmer Date 2017-12-15 Time 13:18 Sent To  
Notes
2017-12-15 13:19:23IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-03-29 Cont ID  
Sent By jwitmer Date 2016-03-29 Time 15:26 Rev Time 0.00
Received By jwitmer Date 2016-03-29 Time 15:26 Sent To  
Notes
2016-03-29 15:27:25BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16010117
 ADD: 431 BUNKER RD.
 CONT: TBD
 TEL: 561-603-0434
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MARCH 29/ 2016
 ACTION: DENIED
  
 1) IMPACT FEES. BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-22 Cont ID  
Sent By jwitmer Date 2016-01-22 Time 15:46 Rev Time 0.00
Received By jwitmer Date 2016-01-22 Time 15:46 Sent To  
Notes
2016-01-22 15:46:56IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2018-07-26 Cont ID  
Sent By ccole Date 2018-07-26 Time 14:27 Rev Time 0.00
Received By ccole Date 2018-07-26 Time 14:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status F Date 2018-06-25 Cont ID  
Sent By ccole Date 2018-06-25 Time 09:22 Rev Time 0.00
Received By ccole Date 2018-06-25 Time 09:21 Sent To  
Notes
2018-06-25 09:55:391ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16010117
 6/25/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE FIFTH EDITION 2014
 FBC M- FLORIDA MECHANICAL CODE FIFTH EDITION 2014
 FBC EC- FLORIDA ENERGY CONSERVATION CODE FIFTH EDITION
 2014
 FBC EX- FLORIDA EXISTING BUILDING CODE FIFTH EDITION
 2014
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE VALUE OF THE PROJECT HAS INCREASED DUE TO THE
 ADDITION OF TWO NEW 5-TON RTU'S, AND THE MODIFIED AIR
 DISTRIBUTION SYSTEMS. THE ORIGINAL APPROVED PLANS WERE
 FOR ONE 3-TON SYSTEM AND ONE DUCT TRUNK LINE. THE
 ADJUSTED VALUE SHALL INCLUDE THE MECHANICAL LABOR,
 MATERIALS, EQUIPMENT, AND THE STRUCTURAL AND ELECTRICAL
 WORK REQUIRED FOR INSTALLATION OF THE NEW SYSTEMS.
  
 2) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF RTU'S PER SECTION 606.2.1 FBC M. PLEASE NOTE
 THAT THE PLANS ARE UNDER THE FBC M FIFTH EDITION 2014.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
 HTTPS://WWW.SURVEYMONKEY.COM/R/WESTPALMBEACHCONSTRUCTIO
 NSERVICES
  

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2018-03-13 Cont ID  
Sent By ccole Date 2018-03-13 Time 17:14 Rev Time 0.00
Received By ccole Date 2018-03-13 Time 17:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2018-02-20 Cont ID  
Sent By ccole Date 2018-02-20 Time 12:29 Rev Time 0.00
Received By ccole Date 2018-02-20 Time 12:26 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2017-12-27 Cont ID  
Sent By ccole Date 2017-12-27 Time 09:41 Rev Time 0.00
Received By ccole Date 2017-12-27 Time 09:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2017-04-07 Cont ID  
Sent By ccole Date 2017-04-07 Time 12:35 Rev Time 0.00
Received By ccole Date 2017-04-07 Time 12:35 Sent To  
Notes
2017-04-07 12:39:503RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16010117
 4/7/17
  
 1) SHEET M-1: THE REVISED PLAN IS NOW SHOWING A NEW
 BATH EXHAUST FAN WITH NO DETAILS. PLEASE PROVIDE AN
 EQUIPMENT SCHEDULE FOR THE FAN, AND AN EXHAUST PLAN
 THAT SHOWS THE TYPE AND SIZE OF DUCT, THE DUCT RUN AND
 TERMINATION LOCATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-22 Cont ID  
Sent By ccole Date 2016-03-22 Time 11:56 Rev Time 0.00
Received By ccole Date 2016-03-22 Time 11:56 Sent To  
Notes
2016-03-22 12:07:382ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #16010117
 3/22/16
  
 1) PLEASE CLARIFY WHY THE PROPOSED ADDITION PROJECT HAS
 BEEN CLASSIFIED AS A "RENOVATION TO EXISTING BUILDING"
 IN THE PROJECT SUMMARY DATA SHOWN ON PAGE 2 OF THE
 ENERGYGAUGE SUBMITTAL.
 2) PROVIDE ENGINEERED DETAILS FOR INSTALLATION OF THE
 NEW CONDENSER PAD AND TIE DOWN OF THE NEW CU TO THE
 PAD- SECTION 301.15.
 3) THERE IS A DETAIL ON SHEET A-202 SHOWING AN OPENING
 INTO THE MAIN BUILDING FROM THE PROPOSED ADDITION:
 PLEASE NOTE A FIRE SPRINKLER MAY BE REQUIRED FOR THE
 BUILDING PER SECTION 903.2.9 FBC-14 BUILDING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-15 Cont ID  
Sent By ccole Date 2016-01-15 Time 11:27 Rev Time 0.00
Received By ccole Date 2016-01-15 Time 11:27 Sent To  
Notes
2016-01-15 12:09:491ST REVIEW: FBC 2014 MECHANICAL
 PERMIT 16010117
 01/15/16
  
 1) NATURAL OR MECHANICAL VENTILATION IS REQUIRED FOR
 THE NEW STORAGE ADDITION. INDICATE ON THE PLANS WHICH
 METHOD WILL BE USED AND PROVIDE DETAILS AND
 CALCULATIONS, IF MECHANICAL VENTILATION WILL BE
 INSTALLED SEE TABLE 403.3 FBC-14 MECHANICAL FOR THE
 MINIMUM VOLUME OF OUTDOOR AIR REQUIRED.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 6 Status P Date 2018-08-07 Cont ID  
Sent By gjohnson Date 2018-08-07 Time 08:05 Rev Time 0.00
Received By gjohnson Date 2018-08-07 Time 08:05 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 5 Status F Date 2018-06-29 Cont ID  
Sent By gjohnson Date 2018-06-29 Time 07:03 Rev Time 0.00
Received By gjohnson Date 2018-06-28 Time 18:21 Sent To  
Notes
2018-06-28 18:38:411ST REVIEW: FBC 2017 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE REAR GRAB BAR SHALL COMPLY WITH FBC ACC 604.5.2
 REAR WALL.THE REAR WALL GRAB BAR SHALL BE 36 INCHES
 LONG MINIMUM AND EXTEND FROM THE CENTERLINE OF THE
 WATER CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24
 INCHES MINIMUM ON THE OTHER SIDE.
  
 2. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE IF MEASURED AT 36" TO THE CENTER OF
 THE BAR IT CREATES A CODE VIOLATION. PER FBC ACC 609.4
  
 3. ON THE ORIGINAL PLAN THAT I APPROVED HAD NEW ROOF
 DRAINS PLEASE PROVIDE STORM WATER ISOMETRIC DRAWING
 WITH SIZING CALCULATIONS. PER WPB AMEND TO FBC
 107.3.5.1.3(13)
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2018-01-04 Cont ID  
Sent By gjohnson Date 2018-01-04 Time 11:37 Rev Time 0.00
Received By gjohnson Date 2018-01-04 Time 11:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2017-04-28 Cont ID  
Sent By gjohnson Date 2017-04-28 Time 11:47 Rev Time 0.00
Received By gjohnson Date 2017-04-28 Time 09:11 Sent To  
Notes
2017-04-28 11:46:353RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING
 ACCESSIBILITY. FBC ACC 604.5.1 SIDE WALL.
 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES (1065 MM)
 LONG MINIMUM, LOCATED 12 INCHES (305 MM) MAXIMUM FROM
 THE REAR WALL AND EXTENDING 54 INCHES (1370 MM) MINIMUM
 FROM THE REAR WALL.
  
 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS. DISPENSERS SHALL
 NOT BE OF A TYPE THAT CONTROLS DELIVERY OR THAT DOES
 NOT ALLOW CONTINUOUS PAPER FLOW.
  
 604.4 SEATS.
 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT. SEATS
 SHALL NOT BE SPRUNG TO RETURN TO A LIFTED POSITION.
  
 606.3 HEIGHT.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
  
 2. HOT OR TEMPERED WATER IS REQUIRED AT THE NEW
 LAVATORY. PER FBC PL 607.1
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-03-27 Cont ID  
Sent By tklarge Date 2016-03-27 Time 09:10 Rev Time 0.00
Received By tklarge Date 2016-03-27 Time 08:32 Sent To  
Notes
2016-03-27 08:32:011) SUBMIT A STORMWATER RISER FOR THE PRIMARY ROOF
 DRAINAGE AND FOR THE OVERFLOW DRAINS.THE SIZING OF THE
 HORIZONTAL DRAINS SHALL COMPLY WITH 2014 FBC-PLUMBING
 TABLE 1106.3. THE DESIGN SHALL BE BASED ON A 5 INCH
 RAINFALL RATE PER HOUR.SHOW THE SQUARE FOOTAGE DRAINED
 BY EACH DRAIN. 2ND REQUEST.FBC 107.3.5. THIS HAS NOT
 BEEN SUBMITTED NOR HAS A STORM DRAIN RISER BEEN
 SUBMITTED AS PREVIOUSLY REQUESTED. INDICATE THE SLOPE
 OF THE HORIZONTAL STORM DRAIN.
 2) RAINWATER LEADERS SHALL DISCHARGE A MINIMUM OF ONE
 FOOT FROM THE BUILDING EXTERIOR WALL. 2014 FBC SEC.
 1503.7.
 3) CLEANOUTS ARE REQUIRED IN THE STORM DRAINAGE SYSTEM
 PER 2014 FBC-PLUMBING SEC. 1101.8.
 4) SHOW THE TERMINATION / DISCHARGE POINTS OF THE
 PRIMARY AND OVERFLOW ROOF DRAINS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) INDICATE ON THE PLANS HOW THE NEW LANDSCAPED AREAS
 WILL BE IRRIGATED. PLEASE NOTE THIS ON THE PLANS AS
 YOUR RESPONSE TO THE COMMENTS USUALLY DOES NOT MAKE IT
 TO THE FIELD, WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-09 Cont ID  
Sent By tklarge Date 2016-01-09 Time 07:03 Rev Time 0.00
Received By tklarge Date 2016-01-09 Time 06:15 Sent To  
Notes
2016-01-09 07:03:081) SUBMIT A STORMWATER RISER FOR THE PRIMARY ROOF
 DRAINAGE AND FOR THE OVERFLOW DRAINS.THE SIZING OF THE
 VERTICAL LEADERS AND HORIZONTAL DRAINS SHALL COMPLY
 WITH 2014 FBC-PLUMBING, TABLES 1106.2.1 & 1106.3
 RESPECTIVELY. THE DESIGN SHALL BE BASED ON A 5 INCH
 RAINFALL RATE PER HOUR.SHOW THE SQUARE FOOTAGE DRAINED
 BY EACH DRAIN. WPB AMEND. TO FBC SEC. 107.2.1.
 2) VERTICAL WALLS - IN SIZING ROOF DRAINS AND STORM
 DRAINAGE PIPING, ONE-HALF OF THE AREA OF ANY VERTICAL
 WALL THAT DIVERTS RAINWATER TO THE ROOF SHALL BE ADDED
 TO THE PROJECTED ROOF AREA FOR INCLUSION IN CALCULATING
 THE REQUIRED SIZE OF VERTICAL CONDUCTORS, LEADERS AND
 HORIZONTAL STORM DRAINAGE PIPING.
 3) CLEANOUTS ARE REQUIRED IN THE STORM DRAINAGE SYSTEM
 PER 2014 FBC-PLUMBING SEC. 1101.8.
 4) SHOW THE TERMINATION / DISCHARGE POINTS OF THE
 PRIMARY AND OVERFLOW ROOF DRAINS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 5) SUPPLY THE NUMBER OF EXISTING SANITARY FACILITIES TO
 ENSURE THAT THEY WILL BE ADEQUATE FOR THE ADDED
 OCCUPANT LOAD.REFER TO 2014 FBC-PLUMBING TABLE 403.1.
 6) INDICATE ON THE PLANS HOW THE NEW LANDSCAPED AREAS
 WILL BE IRRIGATED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2018-08-11 Cont ID  
Sent By shill Date 2018-08-11 Time 18:33 Rev Time 0.00
Received By shill Date 2018-08-11 Time 18:33 Sent To  
Notes
2018-08-11 18:35:08A SEPARATE ROOF PERMIT IS REQUIRED. PRIOR TO
 INSTALLATION, SUBMIT ROOF PERMIT APPLICATION WITH
 PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD AND
 ENGINEERING (IF APPLICABLE).
  

Review Stop Z ZONING
Rev No 8 Status P Date 2018-07-24 Cont ID  
Sent By eschneid Date 2018-07-24 Time 15:27 Rev Time 0.50
Received By eschneid Date 2018-07-24 Time 13:52 Sent To  
Notes
2018-07-24 15:24:47PASSED W/PROVISOS
  
 1) PRIOR TO THE FINAL INSPECTION (104) FOR THIS PERMIT,
 A MINOR SITE PLAN AMENDMENT NEEDS TO BE SUBMITTED TO
 THE PLANNING DIVISION FOR THE CHANGES TO THE SITE AND
 LANDSCAPE PLANS.
  
 2) SINCE THIS PERMIT INCLUDES THE PARTIAL DEMOLITION OF
 THE SECOND FLOOR OF 431 BUNKER ROAD, PRIOR TO THE FIRST
 INSPECTION FOR ANY WORK ASSOCIATED WITH THE NEW 1,680
 SQUARE FOOT ADDITION, DEMOLITION MUST HAVE BEGUN TO
 REMOVE THE 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431
 BUNKER ROAD.
  
 3) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. RIGHT-OF-WAY IMPROVEMENTS
 B. BICYCLE RACK
 C. LANDSCAPE
 D. DRIVEWAYS
  
 4) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY FOR THE NEW 1,680 SQUARE FOOT ADDITION, THE
 APPLICANT MUST HAVE COMPLETED THE DEMOLITION OF THE
 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431 BUNKER
 ROAD AND CLOSED THE BUILDING PERMIT(S).
  
 5) PLEASE REMEMBER THAT THE CONSTRUCTION NEEDS TO START
 BY SEPTEMBER 2, 2018, OR THE VARIANCE APPROVING THE
 DEVELOPMENT WILL EXPIRE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 7 Status F Date 2018-06-27 Cont ID  
Sent By eschneid Date 2018-06-27 Time 08:44 Rev Time 1.00
Received By eschneid Date 2018-06-26 Time 12:01 Sent To  
Notes
2018-06-27 10:07:42FAILED
  
 PLEASE PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) SHEET A-1.2 SHOWS THE PROPOSED SECOND FLOOR PLAN.
 WHILE THE NOTES CORRECTLY SHOW THAT THE FLOOR IS BEING
 REMOVED, IT FAILS TO SHOW THE REMOVAL OF THE BATHROOM.
 ALL THE BATHROOM (NOT PREVIOUSLY SHOWN ON ANY PLANS)
 FIXTURES NEED TO BE REMOVED TO COMPLY WITH THE
 REQUIREMENT THAT THE AREA IS VACATED.
  
 2) WALL SECTION 02 ON SHEET A-2 FAILS TO SHOW THAT THE
 REMOVAL OF THE FLOORING IN THE SECOND LEVEL ABANDONED
 AREA.
  
 3) PRIOR TO THE FINAL INSPECTION (104) FOR THIS PERMIT,
 A MINOR SITE PLAN AMENDMENT NEEDS TO BE SUBMITTED TO
 THE PLANNING DIVISION FOR THE CHANGES TO THE SITE PLAN.
  
 4) SINCE THIS PERMIT INCLUDES THE PARTIAL DEMOLITION OF
 THE SECOND FLOOR OF 431 BUNKER ROAD, PRIOR TO THE FIRST
 INSPECTION FOR ANY WORK ASSOCIATED WITH THE NEW 1,680
 SQUARE FOOT ADDITION, DEMOLITION MUST HAVE BEGUN TO
 REMOVE THE 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431
 BUNKER ROAD.
  
 5) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. RIGHT-OF-WAY IMPROVEMENTS
 B. BICYCLE RACK
 C. LANDSCAPE
 D. DRIVEWAYS
  
 6) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY FOR THE NEW 1,680 SQUARE FOOT ADDITION, THE
 APPLICANT MUST HAVE COMPLETED THE DEMOLITION OF THE
 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431 BUNKER
 ROAD AND CLOSED THE BUILDING PERMIT(S).
  
 7) PLEASE REMEMBER THAT THE CONSTRUCTION NEEDS TO START
 BY SEPTEMBER 2, 2018, OR THE VARIANCE APPROVING THE
 DEVELOPMENT WILL EXPIRE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]
  
  

Review Stop Z ZONING
Rev No 6 Status P Date 2018-03-14 Cont ID  
Sent By eschneid Date 2018-03-14 Time 15:40 Rev Time 0.75
Received By eschneid Date 2018-03-14 Time 12:34 Sent To PC
Notes
2018-03-14 16:00:30PASSED W/PROVISOS
  
 1) SINCE THIS PERMIT INCLUDES THE PARTIAL DEMOLITION OF
 THE SECOND FLOOR OF 431 BUNKER ROAD, PRIOR TO THE FIRST
 INSPECTION FOR ANY WORK ASSOCIATED WITH THE NEW 1,680
 SQUARE FOOT ADDITION, DEMOLITION MUST HAVE BEGUN TO
 REMOVE THE 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431
 BUNKER ROAD.
  
 2) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. RIGHT-OF-WAY IMPROVEMENTS
 B. BICYCLE RACK
 C. LANDSCAPE
 D. DRIVEWAYS
  
 3) PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF
 OCCUPANCY FOR THE NEW 1,680 SQUARE FOOT ADDITION, THE
 APPLICANT MUST HAVE COMPLETED THE DEMOLITION OF THE
 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431 BUNKER
 ROAD AND CLOSED THE BUILDING PERMIT(S).
  
  

Review Stop Z ZONING
Rev No 5 Status F Date 2018-02-09 Cont ID  
Sent By eschneid Date 2018-02-09 Time 16:47 Rev Time 0.50
Received By eschneid Date 2018-02-09 Time 16:20 Sent To  
Notes
2018-02-09 16:47:23FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) REVISED COMMENT: THANK YOU FOR PROVIDING THE NEW A/C
 UNIT ON THE SITE, FLOOR AND LIFE SAFETY PLANS; HOWEVER,
 THE A/C EQUIPMENT IS SHOWN IN DIFFERENT LOCATIONS AND
 AT DIFFERENT SIZES ON THE VARIOUS PLANS. THE SIZE AND
 LOCATION DIFFERENCES AFFECT THE PAD THAT THE A/C IS
 REQUIRED TO SIT ON, AS WELL AS SETBACKS TO THE NORTHERN
 PROPERTY LINE AND IMPERVIOUS SURFACE CALCULATIONS. ALL
 PLANS MUST SHOW THE SAME CONDITIONS. PROVIDE THE
 DIMENSIONS FOR THE A/C EQUIPMENT ON EACH SHEET.
  
 2) SINCE THIS PERMIT INCLUDES THE PARTIAL DEMOLITION OF
 THE SECOND FLOOR OF 431 BUNKER ROAD, PRIOR TO THE FIRST
 INSPECTION FOR ANY WORK ASSOCIATED WITH THE NEW 1,680
 SQUARE FOOT ADDITION, DEMOLITION MUST HAVE BEGUN TO
 REMOVE THE 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431
 BUNKER ROAD (BUILDING #1).
  
 3) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. RIGHT-OF-WAY IMPROVEMENTS
 B. BICYCLE RACK
 C. LANDSCAPE
 D. DRIVEWAYS
  
 4) PLEASE REMEMBER THAT, PRIOR TO THE ISSUANCE OF THE
 CERTIFICATE OF OCCUPANCY FOR THE NEW 1,680 SQUARE FOOT
 ADDITION, THE APPLICANT MUST HAVE COMPLETED THE
 DEMOLITION OF THE 1,427 SQUARE FEET OF THE SECOND FLOOR
 OF BUILDING #1 (OPENING THE SPACE TO THE FIRST FLOOR
 BELOW) AND CLOSED THE BUILDING PERMIT(S).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 4 Status F Date 2018-01-19 Cont ID  
Sent By eschneid Date 2018-01-19 Time 16:38 Rev Time 1.00
Received By eschneid Date 2018-01-09 Time 12:29 Sent To ENG
Notes
2018-01-19 16:46:55FAILED
  
 PROVIDE WRITTEN RESPONSE TO COMMENTS.
  
 1) SHEETS E-1 AND M-1 SHOW A NEW A/C UNIT ON THE GROUND
 FLOOR ON THE NORTH SIDE OF THE ADDITION WHICH IS NOT
 SHOWN ON THE SITE, FLOOR OR LIFE SAFETY PLANS. SHEET
 M-1 DOES NOT SHOW THE NORTHERN SET OF DOORS AND LOCATES
 THE A/C WITHIN THE DOOR LOCATION. ALL PLANS MUST SHOW
 THE SAME CONDITIONS.
  
 2) SINCE THIS PERMIT INCLUDES THE PARTIAL DEMOLITION OF
 THE SECOND FLOOR OF 431 BUNKER ROAD, PRIOR TO THE FIRST
 INSPECTION FOR ANY WORK ASSOCIATED WITH THE NEW 1,680
 SQUARE FOOT ADDITION, DEMOLITION MUST HAVE BEGUN TO
 REMOVE THE 1,427 SQUARE FEET OF THE SECOND FLOOR OF 431
 BUNKER ROAD (BUILDING #1).
  
 3) SEPARATE PERMITS ARE REQUIRED FOR:
  
 A. RIGHT-OF-WAY IMPROVEMENTS
 B. BICYCLE RACK
 C. LANDSCAPE
 D. DRIVEWAYS
  
 4) PLEASE REMEMBER THAT, PRIOR TO THE ISSUANCE OF THE
 CERTIFICATE OF OCCUPANCY FOR THE NEW 1,680 SQUARE FOOT
 ADDITION, THE APPLICANT MUST HAVE COMPLETED THE
 DEMOLITION OF THE 1,427 SQUARE FEET OF THE SECOND FLOOR
 OF BUILDING #1 (OPENING THE SPACE TO THE FIRST FLOOR
 BELOW) AND CLOSED THE BUILDING PERMIT(S).
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2017-04-10 Cont ID  
Sent By eschneid Date 2017-04-10 Time 17:10 Rev Time 0.25
Received By eschneid Date 2017-04-10 Time 17:10 Sent To  
Notes
2017-04-10 17:13:08FAILED
  
 THIS APPLICATION REQUIRES THE APPROVAL OF A SITE PLAN
 THROUGH THE PPRC PROCESS PRIOR TO THE ISSUANCE OF THE
 PERMIT. THERE IS CURRENTLY A PENDING APPLICATION.
  
 THE ALLEY ABANDONMENT REQUIRED AS PART OF THIS
 EXPANSION HAS NOT BEEN APPROVED BY THE CITY COMMISSION,
 NOR HAS THE LAND BEEN CONVEYED TO THE OWNER.
  
 ZONING WILL NOT REVIEW UNTIL THE SITE PLAN AMENDMENT
 AND THE ABANDOMENT ARE APPROVED AND THE ABANDONED
 RIGHT-OF-WAY HAS BEEN CONVEYED TO THE OWNER.
  
 THIS DOES NOT COUNT AS A REVIEW CYCLE.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 2 Status F Date 2016-03-24 Cont ID  
Sent By eschneid Date 2016-03-24 Time 14:47 Rev Time 0.25
Received By eschneid Date 2016-03-24 Time 14:47 Sent To  
Notes
2016-03-24 14:47:16FAILED
  
 THIS APPLICATION REQUIRES THE APPROVAL OF A SITE PLAN
 THROUGH THE PPRC PROCESS PRIOR TO THE ISSUANCE OF THE
 PERMIT. THERE IS CURRENTLY A PENDING APPLICATION.
  
 ZONING WILL NOT REVIEW UNTIL THE SITE PLAN AMENDMENT IS
 APPROVED.
  
 THIS DOES NOT COUNT AS A REVIEW CYCLE.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.

Review Stop Z ZONING
Rev No 1 Status F Date 2016-02-16 Cont ID  
Sent By eschneid Date 2016-02-16 Time 10:31 Rev Time 0.25
Received By eschneid Date 2016-02-16 Time 10:31 Sent To  
Notes
2016-02-16 10:35:00FAILED
  
 THIS APPLICATION REQUIRES THE APPROVAL OF A SITE PLAN
 THROUGH THE PPRC PROCESS PRIOR TO THE ISSUANCE OF THE
 PERMIT. THERE IS CURRENTLY A PENDING APPLICATION.
  
 ZONING WILL NOT REVIEW UNTIL THE SITE PLAN AMENDMENT IS
 APPROVED.
  
 THIS DOES NOT COUNT AS A REVIEW CYCLE.
  
 CONTACT ERIC SCHNEIDER (561) 822-1446.