Plan Review Stops For Permit 15120875 |
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
3 |
Status |
P |
Date |
2016-03-10 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-03-10 |
Time |
07:44 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-03-10 |
Time |
06:56 |
Sent To |
|
|
Notes |
2016-03-10 07:44:19 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15120875 | | ADD: 2 HARVARD CIRCLE SUITE 500 | | CONT: FISHER CONTRACTING | | TEL: 561-691-4716 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 13RD REVIEW | | DATE: THURS. MARCH 10/2016 | | ACTION: BUILDING PROVISO | | | | BUILDING APPROVED WITH EXCEPTION! | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | 1) SHEET A-1: | | 1A) DOOR AT RECEPTION DESK REVISION REQUIRED TO SHOW | | COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE 404.2.4 | | MANEUVERING CLEARANCES AND FIGURE 404.2.4.1(A). | | | | 1B) THE EAST DOOR OF THE LAB LABELED C, REVISION | | REQUIRED TO SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY | | CODE 404.2.4 | | MANEUVERING CLEARANCES AND FIGURE 404.2.4.1(A). | | | | 1C) DOORS TO ACCESSIBLE RESTROOMS DO NOT HAVE THE 18 | | INCHES MANEUVERING CLEARANCES 2014 FBC- ACCESS. CODE | | 404.2.4./ FIGURE 404.2.4.1(A). SEE SECTION: | | 603.2.3 DOOR SWING. 2. WHERE THE TOILET ROOM OR BATHING | | ROOM IS FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE | | COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND | | THE ARC OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO | | SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED | | FOR ANY FIXTURE. | | | | 2) NO HAZARDOUS CHEMICALS TO BE STORED OR USED ON SITE | | WITHOUT THE USE OF A CONTROL AREA, WITH 1 HOUR FIRE | | SEPARATION AND SEPARATE MECHANICAL UNIT. PLEASE SEE | | ATTACHED LIST OF CHEMICALS TO BE STORED ARE | | NON-HAZARDOUS, ALL ARE LIQUID IN STATE. | | | | CHEMICALS ON SITE: ALL ARE NON-HAZARDOUS, ALL ARE IN | | THE LIQUID STATE. A100 ML (0,2205 LBS.) QUANTITY OF | | EACH WILL BE ON SITE TO PERFORM DAILY ACTIVITIES. MSDS | | FOR EACH CHEMICAL HAS BEEN INCLUDED FOR REVIEW. | | | | PHENCYCLIDINE METABOLITE ENZYME IMMUNOASSAY | | | | COCAINE METABOLITE ENZYME IMMUNOASSAY | | | | AMPHETAMINES ENZYME IMMUNOASSAY | | | | METHADONE METABOLITE CALIBRATORS | | | | PROPOXYPHENE ENZYME IMMUNOASSAY | | | | NITROGEN GENERATOR: DUE TO INDUSTRY CHANGES, PHR WILL | | NOT BE INSTALLING A NITROGEN GENERATOR. | | | | LC/MS TOXICOLOGY ANALYZER: DUE TO INDUSTRY CHANGES, PHR | | WILL NOT BE INSTALLING A LC/MS TOXICOLOGY ANALYZER. | | | | AU400 IS A SELF-CONTAINED CHEMISTRY ANALYZER. NO SITE | | PREPARATION IS REQUIRED. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | CONSTRUCTION SERVICES DIVISION | | DEVELOPMENT SERVICES DEPARTMENT | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
2 |
Status |
F |
Date |
2016-02-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-02-24 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-02-24 |
Time |
15:00 |
Sent To |
|
|
Notes |
2016-02-24 15:53:20 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15120875 | | ADD: 2 HARVARD CIRCLE SUITE 500 | | CONT: FISHER CONTRACTING | | TEL: 561-691-4716 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: SAT. JAN. 09/2014 | | ACTION: DENIED | | | | 1) COMPLIED. | | | | 2) COMPLIED. | | | | 3) NEW COMMENT. ONE SET OF PLANS ARE SIGNED, DATED BUT | | NOT SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER | | DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING | | FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND | | SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE | | DOCUMENT. | | FL ADMIN CODE 61G16.003 ARCHITECTS | | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
B |
BUILDING (STRUCTURAL) |
Rev No |
1 |
Status |
F |
Date |
2016-01-09 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-01-09 |
Time |
11:00 |
Rev Time |
|
Received By |
jwitmer |
Date |
2016-01-09 |
Time |
09:00 |
Sent To |
|
|
Notes |
2016-01-09 10:57:37 | BUILDING PLAN REVIEW | | W. P. B. PERMIT: 15120875 | | ADD: 2 HARVARD CIRCLE SUITE 500 | | CONT: FISHER CONTRACTING | | TEL: 561-691-4716 | | E-MAIL: [email protected] | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | ADMINISTRATION | | | | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. | | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND | | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE | | FLORIDA BUILDING CODE, BUILDING. | | | | 1ST REVIEW | | DATE: SAT. JAN. 09/2014 | | ACTION: DENIED | | | | 1) SHEET A-1 UNDER THE HEADING OF USE AND OCCUPANCY | | LIST THIS TENANT SPACE AS A BUSINESS OCCUPANCY. | | | | 1A) IT WOULD APPEAR THE USE OF THIS TENANT SPACE WOULD | | BE A LABORATORY OR TEACHING FACILITY WITH THE TYPE OF | | EQUIPMENT THAT IS ILLUSTRATED ON THE ELECTRICAL SHEETS. | | PLEASE DEFINE THE TYPE OF USAGE UNDER THE BUSINESS | | OCCUPANCY? 2014 FBC-B 304.1. | | | | 1B) THE PLANS SHOW THE INSTALLATION OF A NITROGEN | | GENERATOR, A LC/MS TOXICOLOGY ANALYZER FOR CLINICAL | | RESEARCH & FOR FORENSIC TOXICOLOGY APPLICATIONS, AND A | | AU400 UNIT USED FOR CHEMISTRY ANALYZER. ADDITIONAL | | INFORMATION WILL BE REQUIRED TO DETERMINE IF THIS USAGE | | WILL REMAIN A BUSINESS OCCUPANCY, OR POSSIBLY A | | BUSINESS OCCUPANCY WITH CONTROLLED (1 HR. SEPARATION) | | AREAS, OR CONSIDERED A HAZARDOUS OCCUPANCY. PLEASE ALSO | | SUPPLY A LIST OF ALL CHEMICALS TO BE USED IN THE | | VARIOUS APPLICATIONS, THE CHEMICAL NAME, IF SOLID, | | LIQUID OR GAS, THE AMOUNTS IN EITHER POUNDS, LIQUIDS OR | | IF GAS CUBIC FEET TO BE STORED AT THE SITE AS WELL AS | | IF THEY ARE STORED IN CLOSED SYSTEMS OR IN AN OPEN | | SYSTEM . | | PLEASE REFER TO THE 2014 FBC-B TABLE 307.1(1). MAXIMUM | | ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS | | MATERIALS POSING A PHYSICAL HAZARD. | | | | 1C) FOR THE CHEMICALS TO BE STORED AND OR USED ON SITE | | PLEASE PROVIDE THEIR MSDS SHEETS (MATERIAL SAFETY DATA | | SHEETS), THESE DOCUMENTS WILL HELP TO CLASSIFY THE | | CHEMICALS AS IF HAZARDOUS AND TO IF THIS REMAINS A | | BUSINESS OCCUPANCY, A BUSINESS OCCUPANCY W/ CONTROL | | AREAS AND OR AS A HAZARDOUS OCCUPANCY. | | | | 2A) SHEET E-1 INDICATES THE USE OF A NITROGEN | | GENERATOR. PLEASE PROVIDE HOW MUCH NITROGEN WILL THIS | | SYSTEM, GENERATE, WILL IT BE STORED ON SITE AND TO WHAT | | QUANTITIES, AND IN WHAT TYPE OF CONTAINERS, AND TO WHAT | | PRESSURE WILL THE NITROGEN BE STORED. 2014 FBC-B TABLE | | 307.1(1). | | | | 2B) NOT HAVING ANY LITERATURE ON THE NITROGEN GENERATOR | | NOR AS TO WHAT PRESSURE THE SYSTEM WILL OPERATE, (NOT | | SHOWN ON PLANS, NO PIPING, VALVES, BACK FLOW PREVENTION | | NOR CROSS OVER PREVENTION) WHAT SAFETY EQUIPMENT OR | | DEVICES WILL BE PROVIDED TO NOTIFY THE OCCUPANTS OF AN | | OXYGEN-DEFICIENT ATMOSPHERE? 2014 FBC-B TABLE 307.1(1). | | MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF | | HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD. | | | | 3) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | THIS REVIEW. | | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | JAMES A. WITMER CBO | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | TEL: 561-805-6715 | | FAX: 561-805-6676 | | E-MAIL: [email protected] | | | | | | | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
3 |
Status |
P |
Date |
2016-03-10 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-03-10 |
Time |
10:38 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-03-10 |
Time |
10:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
2 |
Status |
F |
Date |
2016-02-24 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-02-24 |
Time |
13:39 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-02-24 |
Time |
13:17 |
Sent To |
|
|
Notes |
2016-02-24 13:45:35 | 2ND ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1.PLEASE NOTE THAT 2ND SET OF CONSTRUCTION DOCUMENTS | | ARE NOT SEALED BY DESIGNER OF RECORD. 61GI-16.003 FAC | | 2.NEW SHEET E-1 REFLECTING COMMENTS ADDRESSED WAS NOT | | INSERTED INTO REVISED SETS SUBMITTED. PLEASE | | INCORPORATE SIGN AND SEALED REVISED SHEETS AND DELETE | | OLD FROM SET. | | 3.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY | | QUESTIONS REGARDING THIS PROJECT. | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
E |
ELECTRICAL |
Rev No |
1 |
Status |
F |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-02-10 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-02-10 |
Time |
13:04 |
Sent To |
|
|
Notes |
2016-02-10 13:28:02 | INITIAL ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS: | | | | 1. PLEASE CLARIFY WHAT TYPE OF HEALTH FACILITY THIS IS. | | LAB TYPE. FBC 107 | | 2. PROVIDE DATA CUT SHEETS FOR THE NITROGEN GENERATOR | | SHOWN. FBC 107 | | 3. LABEL DRINKING FOUNTAIN TO BE GFCI PROTECTED PER NEC | | 422.52 | | 4. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW. | | | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
3 |
Status |
P |
Date |
2016-03-09 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-03-09 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-03-09 |
Time |
10:52 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
2 |
Status |
P |
Date |
2016-02-17 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-02-17 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-02-17 |
Time |
12:32 |
Sent To |
|
|
Notes |
|
|
Review Stop |
FIRE |
FIRE DEPARTMENT |
Rev No |
1 |
Status |
F |
Date |
2016-01-06 |
|
|
Cont ID |
|
Sent By |
pleduc |
Date |
2016-01-06 |
Time |
|
Rev Time |
0.00 |
Received By |
pleduc |
Date |
2016-01-06 |
Time |
15:28 |
Sent To |
|
|
Notes |
2016-01-06 16:03:46 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1. PLEASE PROVIDE DOCUMENTATION ON WHAT THE BUSINESS | | PRODUCES/MANUFACTURE'S/ PROCESSES. WHAT TAKES PLACE IN | | THE LAB? | | | | 2. PROVIDE DOCUMENTATION ON THE NITROGEN GENERATOR AND | | WHAT IT IS USED FOR. PROVIDE THE MANUFACTURES SPEC'S | | INCLUDING INSTALLATION RECOMMENDATIONS/PRECAUTIONS. | | | | 3. EXIT DOOR HARDWARE IS NOT PROVIDED. EXIT DOOR | | LOCKING/LATCHING SHALL COMPLY WITH NFPA 101, 5TH | | EDITION, CHAPTER 7. | | | | 4. EXIT SIGNAGE SHALL BE PROVIDED FOR FROM THE LAB | | AREA. | | | | 5. EMERGENCY LIGHTS SHALL BE PROVIDED FOR IN THE LAB | | AREA. | | | | 6. PROVIDE AN EQUIPMENT PLAN FOR THE LAB. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
4 |
Status |
N |
Date |
2016-03-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-03-22 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-03-21 |
Time |
15:19 |
Sent To |
|
|
Notes |
2016-03-21 15:19:50 | RESUB ROUTED TO CCOLE |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
3 |
Status |
N |
Date |
2016-03-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-17 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-07 |
Time |
10:14 |
Sent To |
|
|
Notes |
2016-03-10 10:38:33 | 3/10 TO B30 | 2016-03-08 10:14:46 | B30 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2016-02-24 |
|
|
Cont ID |
|
Sent By |
jwitmer |
Date |
2016-02-24 |
Time |
15:53 |
Rev Time |
0.00 |
Received By |
jwitmer |
Date |
2016-02-12 |
Time |
09:58 |
Sent To |
|
|
Notes |
2016-02-24 13:46:01 | 2/24 TO JIM | 2016-02-16 10:00:30 | B18 |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2016-02-10 |
|
|
Cont ID |
|
Sent By |
vperez |
Date |
2016-02-10 |
Time |
13:28 |
Rev Time |
0.00 |
Received By |
vperez |
Date |
2016-02-10 |
Time |
13:28 |
Sent To |
|
|
Notes |
2016-02-10 13:28:38 | TO CAROLINE/LAURA | 2015-12-30 14:02:04 | B18 |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
4 |
Status |
P |
Date |
2016-03-22 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-03-22 |
Time |
09:48 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-03-22 |
Time |
08:41 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
F |
Date |
2016-03-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-03-14 |
Time |
08:49 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-03-14 |
Time |
08:49 |
Sent To |
|
|
Notes |
2016-03-14 09:53:18 | 3RD REVIEW: FBC 2014 MECHANICAL | | PERMIT #15120875 | | 3/14/16 | | | | 1) SHEET M1: THE 95,000 BTU TRANE ROOFTOP AC MUST BE | | RATED AT A MINIMUM 11.4 EER: THE SCHEDULE IS INDICATING | | 10.3- SEE TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION. | | 2) M1: THE MINIMUM VENTILATION RATE FOR THE LAB | | ACCORDING TO TABLE 403.3 IS BASED ON AN OCCUPANT | | DENSITY OF 25 PEOPLE PER 1000 SF., HOWEVER THE RATE ON | | THE PLAN IS INDICATING ONLY 10 PPL FOR 958 SF.- PLEASE | | CORRECT. | | 3) M1: REFER TO SECTION 501.3.1(2) AND PROVIDE | | CLEARANCE DISTANCE MEASUREMENTS ON THE PLAN FOR THE | | EXHAUST OUTLET. | | 4) SUBMIT A MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL | | FOR THE EXHAUST LOUVER REVIEWED AND APPROVED WITH | | SIGNATURE BY THE DESIGN PROFESSIONAL OF RECORD. | | 5) INDICATE THE TYPE AND GAGE OF EXHAUST DUCT MATERIAL, | | AND PROVIDE DUCT HANGING AND CONNECTION DETAILS FOR | | BOTH THE EXHAUST AND SUPPLY DUCTS. | | 6) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE NEW | | RTU TO THE EXISTING CURB- SECTION 301.15. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2016-02-19 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2016-02-19 |
Time |
16:08 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2016-02-19 |
Time |
16:08 |
Sent To |
|
|
Notes |
2016-02-19 16:19:57 | 2ND REVIEW: FBC 2014 MECHANICAL | | PERMIT #15120875 | | 2/19/16 | | | | 1) AN EXHAUST SYSTEM AT A RATE 1.0 CFM PER SQUARE FOOT | | IS REQUIRED FOR THE LAB AREA AND THE RECIRCULATION OF | | AIR FROM THE SPACE IS PROHIBITED- SEE TABLE 403.3 AND | | FOOTNOTE G. IN ADDITION, TABLE 403.3 REQUIRES OUTDOOR | | AIR FOR OCCUPANTS OF THE LAB AT 10 CFM PER PERSON AND | | .18 CFM PER SQUARE FOOT OF THE SPACE. PLEASE REFER TO | | SECTION 403.3 WHERE IT STATES THAT "VENTILATION RATES | | FOR OCCUPANCIES NOT REPRESENTED IN TABLE 403.3 SHALL BE | | THOSE FOR A LISTED OCCUPANCY CLASSIFICATION THAT IS | | MOST SIMILAR IN TERMS OF OCCUPANT DENSITY, ACTIVITIES | | AND BUILDING CONSTRUCTION; OR SHALL BE DETERMINED BY AN | | APPROVED ENGINEERING ANALYSIS." THE VENTILATION RATES | | LISTED ABOVE ARE DERIVED FROM THE "SCIENCE | | LABORATORIES" LISTING IN TABLE 403.3. PLEASE REVISE THE | | PLAN ACCORDINGLY. | | 2) THE BUILLDING RESPONSE NARRATIVE INDICATES THE | | NITROGEN GENERATOR SHALL NOT BE INSTALLED. PLEASE NOTE | | THAT IF TO BE INSTALLED A LATER DATE, EITHER A REVISION | | TO THIS PERMIT OR SEPARATE PERMIT WILL BE REQUIRED AT | | WHICH TIME A COMPLETE REVIEW OF THE GENERATOR | | SPECIFICATIONS AND EXHAUST SYSTEM MUST BE CONDUCTED AND | | COMPLIANCES IN ACCORDANCE WITH HAZARDOUS EXHAUST | | SYSTEMS MAY BE ENFORCED. | | 3) PLEASE PROVIDE ON THE PLAN A NARRATIVE TO CLARIFY | | THE PROCESSES THAT WILL OCCUR IN THE LAB INCLUDING AN | | ITEMIZED LIST OF CHEMICALS AND THEIR QUANTITIES, AND | | HOW THE CHEMICALS WILL BE DISPENSED AND STORED- REFER | | TO SECTIONS 502.8 AND 510.1 FBC-14 MECHANCIAL. | | 4) THE ARCHITECT OF RECORD JAMES C PAINE JR. DID NOT | | PROVIDE VALID SIGNATURES AND SEALS ON ONE OF THE TWO | | NEW PLAN SETS SUBMITTED- SEE SECTION 61G1-16.003 | | FLORIDA ADMINISTRATIVE CODE. | | 5) TWO RTU-1 RETURN DUCTS DO NOT HAVE SIZES- ONE FROM | | THE CORRIDOR AND ONE FROM SHIPPING/RECEIVING. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-12-31 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-31 |
Time |
09:40 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-31 |
Time |
09:40 |
Sent To |
|
|
Notes |
2015-12-31 09:52:21 | 1ST REVIEW: FBC 2014 MECHANICAL | | PERMIT #15120875 | | 12/31/15 | | | | 1) VENTILATION CALCULATIONS ARE REQUIRED WHEN AC | | SYSTEMS ARE ALTERED- SEE SECTION 809.2 FBC-14 EXISTING | | BUILDING AND SHOW COMPLIANCE. | | 2) THE PLAN SHOWS THE CORRIDOR RUNNING BETWEEN THE | | STAFF LOUNGE AND THE DIRECTOR/CONFERENCE ROOM BEING | | USED AS A RETURN AIR DUCT- SEE SECTION 601.2 FBC-14 | | MECHANICAL AND CORRECT. | | 3) THE PLAN INDICATES UNDERSIZED RETURN AIR TRANSFER | | DUCTS FROM ALL OF THE ROOMS- SEE SECTION 601.5 AND | | CORRECT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
3 |
Status |
P |
Date |
2016-03-17 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-03-17 |
Time |
14:56 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-03-17 |
Time |
10:38 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
F |
Date |
2016-02-20 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2016-02-20 |
Time |
07:49 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2016-02-20 |
Time |
06:25 |
Sent To |
|
|
Notes |
2016-02-20 06:55:38 | 1) SHT.P1 - THE SHEET IS REQUIRED TO BE SEALED BY THE | | DESIGN PROFESSIONAL OF RECORD. FAC RULE 61G1-16.001. | | 2) THE LAB SINKS SHALL BE STACKED & VENTED. 2014 FPC | | SEC.901.2. | | 3) SHOW ON THE PLANS THAT THE HEIGHT OF THE STAFF | | LOUNGE SINK COMPLIES WITH THE FL. ACCESS. CODE SEC. | | 212.2 & 804.( MAX. 34 INCHES HIGH) | | 4) SHOW ON THE PLANS THAT THE DRINKING FOUNTAINS ARE | | ARRANGED FOR A FORWARD APPROACH PER THE 2014 FAC | | SEC.602.2. | | 5) CLEARLY SHOW THE WIDTH OF THE TOILET ROOMS ON THE | | PLANS. THE TOILET ROOMS SHALL BE A MINIMUM WIDTH OF 85 | | INCHES WHEN THE TOILET AND LAVATORY ARE LOCATED ON THE | | SAME WALL. | | 6) THE HIGH SIDE DRINKING FOUNTAIN SHALL COMPLY WITH | | THE 2014 FAC SEC. 307 FOR PROTRUDING OBJECTS. AN | | OPTIONAL SKIRT MAY BE REQUIRED TO KEEP THE LEADING EDGE | | BELOW 27 INCHES.2014 FAC SEC. 307.2. | | 7) THE RESPONSE FROM THE ARCHITECT REFERS TO A SIDE | | APPROACH FOR THE STAFF LOUNGE SINK BUT A FORWARD | | APPROACH IS SHOWN ON THE PLANS. CLARIFY. | | 8) THE VENT FOR THE LAVS SHALL BE MIN. OF 2 INCH. 2014 | | FPC SEC.906.1. | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | | | |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2016-01-07 |
|
|
Cont ID |
|
Sent By |
gjohnson |
Date |
2016-01-07 |
Time |
15:54 |
Rev Time |
0.00 |
Received By |
gjohnson |
Date |
2016-01-07 |
Time |
15:54 |
Sent To |
|
|
Notes |
2016-01-15 09:17:01 | 1ST REVIEW: FBC 2014 | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1.PLEASE PROVIDE A LIST OF CHEMICALS BEING USED AT THIS | | FACILITY. | | 2. WHAT STATE ARE THE CHEMICALS IN ,SOLID ,LIQUID, OR | | GAS. | | 3. HOW THE CHEMICALS ARE BEING STORED AND IN WHAT | | AMOUNTS. | | 4. PLEASE PROVIDE MSDS SHEETS FOR ALL THE CHEMICALS | | BEING USED AND STORED. | | PER WPB AMEND TO FBC 107.2.1 | | 5. HOW WILL USED CHEMICALS BE DISPOSED OF WILL ANY BE | | GOING INTO THE SANITARY SYSTEM, SHALL COMPLY WITH FBC | | PL SEC 803 | | 6. PLEASE PROVIDE A BREAK DOWN OF COST TO SHOW | | COMPLIANCE TO FBC ACC SEC 202.4.1-202.4.2 | | 7. PROVIDE WATER RISER DIAGRAM. PER WPB AMEND TO FBC | | SEC 107.3.5.1.3(13) | | 8. SHOW ALL PIPE SIZES ON RISER DIAGRAM. PER WPB AMEND | | TO FBC 107.2.1 | | 9. WASTE ARMS FOR LAV SHALL COMPLY WITH FBC PL TABLE | | 909.1 | | 10. IS SINK IN STAFF LOUNGE EXISTING. | | | | |
|
|