Plan Review Details - Permit 15120875
Plan Review Stops For Permit 15120875
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-03-10 Cont ID  
Sent By jwitmer Date 2016-03-10 Time 07:44 Rev Time 0.00
Received By jwitmer Date 2016-03-10 Time 06:56 Sent To  
Notes
2016-03-10 07:44:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120875
 ADD: 2 HARVARD CIRCLE SUITE 500
 CONT: FISHER CONTRACTING
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 13RD REVIEW
 DATE: THURS. MARCH 10/2016
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A-1:
 1A) DOOR AT RECEPTION DESK REVISION REQUIRED TO SHOW
 COMPLIANCE WITH 2014 FBC-ACCESSIBILITY CODE 404.2.4
 MANEUVERING CLEARANCES AND FIGURE 404.2.4.1(A).
  
 1B) THE EAST DOOR OF THE LAB LABELED C, REVISION
 REQUIRED TO SHOW COMPLIANCE WITH 2014 FBC-ACCESSIBILITY
 CODE 404.2.4
 MANEUVERING CLEARANCES AND FIGURE 404.2.4.1(A).
  
 1C) DOORS TO ACCESSIBLE RESTROOMS DO NOT HAVE THE 18
 INCHES MANEUVERING CLEARANCES 2014 FBC- ACCESS. CODE
 404.2.4./ FIGURE 404.2.4.1(A). SEE SECTION:
 603.2.3 DOOR SWING. 2. WHERE THE TOILET ROOM OR BATHING
 ROOM IS FOR INDIVIDUAL USE AND A CLEAR FLOOR SPACE
 COMPLYING WITH 305.3 IS PROVIDED WITHIN THE ROOM BEYOND
 THE ARC OF THE DOOR SWING, DOORS SHALL BE PERMITTED TO
 SWING INTO THE CLEAR FLOOR SPACE OR CLEARANCE REQUIRED
 FOR ANY FIXTURE.
  
 2) NO HAZARDOUS CHEMICALS TO BE STORED OR USED ON SITE
 WITHOUT THE USE OF A CONTROL AREA, WITH 1 HOUR FIRE
 SEPARATION AND SEPARATE MECHANICAL UNIT. PLEASE SEE
 ATTACHED LIST OF CHEMICALS TO BE STORED ARE
 NON-HAZARDOUS, ALL ARE LIQUID IN STATE.
  
 CHEMICALS ON SITE: ALL ARE NON-HAZARDOUS, ALL ARE IN
 THE LIQUID STATE. A100 ML (0,2205 LBS.) QUANTITY OF
 EACH WILL BE ON SITE TO PERFORM DAILY ACTIVITIES. MSDS
 FOR EACH CHEMICAL HAS BEEN INCLUDED FOR REVIEW.
  
 PHENCYCLIDINE METABOLITE ENZYME IMMUNOASSAY
  
 COCAINE METABOLITE ENZYME IMMUNOASSAY
  
 AMPHETAMINES ENZYME IMMUNOASSAY
  
 METHADONE METABOLITE CALIBRATORS
  
 PROPOXYPHENE ENZYME IMMUNOASSAY
  
 NITROGEN GENERATOR: DUE TO INDUSTRY CHANGES, PHR WILL
 NOT BE INSTALLING A NITROGEN GENERATOR.
  
 LC/MS TOXICOLOGY ANALYZER: DUE TO INDUSTRY CHANGES, PHR
 WILL NOT BE INSTALLING A LC/MS TOXICOLOGY ANALYZER.
  
 AU400 IS A SELF-CONTAINED CHEMISTRY ANALYZER. NO SITE
 PREPARATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-24 Cont ID  
Sent By jwitmer Date 2016-02-24 Time 15:53 Rev Time 0.00
Received By jwitmer Date 2016-02-24 Time 15:00 Sent To  
Notes
2016-02-24 15:53:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120875
 ADD: 2 HARVARD CIRCLE SUITE 500
 CONT: FISHER CONTRACTING
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 09/2014
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) COMPLIED.
  
 3) NEW COMMENT. ONE SET OF PLANS ARE SIGNED, DATED BUT
 NOT SEALED. PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-09 Cont ID  
Sent By jwitmer Date 2016-01-09 Time 11:00 Rev Time  
Received By jwitmer Date 2016-01-09 Time 09:00 Sent To  
Notes
2016-01-09 10:57:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120875
 ADD: 2 HARVARD CIRCLE SUITE 500
 CONT: FISHER CONTRACTING
 TEL: 561-691-4716
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. JAN. 09/2014
 ACTION: DENIED
  
 1) SHEET A-1 UNDER THE HEADING OF USE AND OCCUPANCY
 LIST THIS TENANT SPACE AS A BUSINESS OCCUPANCY.
  
 1A) IT WOULD APPEAR THE USE OF THIS TENANT SPACE WOULD
 BE A LABORATORY OR TEACHING FACILITY WITH THE TYPE OF
 EQUIPMENT THAT IS ILLUSTRATED ON THE ELECTRICAL SHEETS.
 PLEASE DEFINE THE TYPE OF USAGE UNDER THE BUSINESS
 OCCUPANCY? 2014 FBC-B 304.1.
  
 1B) THE PLANS SHOW THE INSTALLATION OF A NITROGEN
 GENERATOR, A LC/MS TOXICOLOGY ANALYZER FOR CLINICAL
 RESEARCH & FOR FORENSIC TOXICOLOGY APPLICATIONS, AND A
 AU400 UNIT USED FOR CHEMISTRY ANALYZER. ADDITIONAL
 INFORMATION WILL BE REQUIRED TO DETERMINE IF THIS USAGE
 WILL REMAIN A BUSINESS OCCUPANCY, OR POSSIBLY A
 BUSINESS OCCUPANCY WITH CONTROLLED (1 HR. SEPARATION)
 AREAS, OR CONSIDERED A HAZARDOUS OCCUPANCY. PLEASE ALSO
 SUPPLY A LIST OF ALL CHEMICALS TO BE USED IN THE
 VARIOUS APPLICATIONS, THE CHEMICAL NAME, IF SOLID,
 LIQUID OR GAS, THE AMOUNTS IN EITHER POUNDS, LIQUIDS OR
 IF GAS CUBIC FEET TO BE STORED AT THE SITE AS WELL AS
 IF THEY ARE STORED IN CLOSED SYSTEMS OR IN AN OPEN
 SYSTEM .
 PLEASE REFER TO THE 2014 FBC-B TABLE 307.1(1). MAXIMUM
 ALLOWABLE QUANTITY PER CONTROL AREA OF HAZARDOUS
 MATERIALS POSING A PHYSICAL HAZARD.
  
 1C) FOR THE CHEMICALS TO BE STORED AND OR USED ON SITE
 PLEASE PROVIDE THEIR MSDS SHEETS (MATERIAL SAFETY DATA
 SHEETS), THESE DOCUMENTS WILL HELP TO CLASSIFY THE
 CHEMICALS AS IF HAZARDOUS AND TO IF THIS REMAINS A
 BUSINESS OCCUPANCY, A BUSINESS OCCUPANCY W/ CONTROL
 AREAS AND OR AS A HAZARDOUS OCCUPANCY.
  
 2A) SHEET E-1 INDICATES THE USE OF A NITROGEN
 GENERATOR. PLEASE PROVIDE HOW MUCH NITROGEN WILL THIS
 SYSTEM, GENERATE, WILL IT BE STORED ON SITE AND TO WHAT
 QUANTITIES, AND IN WHAT TYPE OF CONTAINERS, AND TO WHAT
 PRESSURE WILL THE NITROGEN BE STORED. 2014 FBC-B TABLE
 307.1(1).
  
 2B) NOT HAVING ANY LITERATURE ON THE NITROGEN GENERATOR
 NOR AS TO WHAT PRESSURE THE SYSTEM WILL OPERATE, (NOT
 SHOWN ON PLANS, NO PIPING, VALVES, BACK FLOW PREVENTION
 NOR CROSS OVER PREVENTION) WHAT SAFETY EQUIPMENT OR
 DEVICES WILL BE PROVIDED TO NOTIFY THE OCCUPANTS OF AN
 OXYGEN-DEFICIENT ATMOSPHERE? 2014 FBC-B TABLE 307.1(1).
 MAXIMUM ALLOWABLE QUANTITY PER CONTROL AREA OF
 HAZARDOUS MATERIALS POSING A PHYSICAL HAZARD.
  
 3) A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2016-03-10 Cont ID  
Sent By vperez Date 2016-03-10 Time 10:38 Rev Time 0.00
Received By vperez Date 2016-03-10 Time 10:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2016-02-24 Cont ID  
Sent By vperez Date 2016-02-24 Time 13:39 Rev Time 0.00
Received By vperez Date 2016-02-24 Time 13:17 Sent To  
Notes
2016-02-24 13:45:352ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1.PLEASE NOTE THAT 2ND SET OF CONSTRUCTION DOCUMENTS
 ARE NOT SEALED BY DESIGNER OF RECORD. 61GI-16.003 FAC
 2.NEW SHEET E-1 REFLECTING COMMENTS ADDRESSED WAS NOT
 INSERTED INTO REVISED SETS SUBMITTED. PLEASE
 INCORPORATE SIGN AND SEALED REVISED SHEETS AND DELETE
 OLD FROM SET.
 3.PLEASE FEEL FREE TO CONTACT ME SHOULD YOU HAVE ANY
 QUESTIONS REGARDING THIS PROJECT.
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 13:28 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 13:04 Sent To  
Notes
2016-02-10 13:28:02INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS:
  
 1. PLEASE CLARIFY WHAT TYPE OF HEALTH FACILITY THIS IS.
 LAB TYPE. FBC 107
 2. PROVIDE DATA CUT SHEETS FOR THE NITROGEN GENERATOR
 SHOWN. FBC 107
 3. LABEL DRINKING FOUNTAIN TO BE GFCI PROTECTED PER NEC
 422.52
 4. FURTHER COMMENTS MAY FOLLOW UPON RE-REVIEW.
  
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2016-03-09 Cont ID  
Sent By pleduc Date 2016-03-09 Time   Rev Time 0.00
Received By pleduc Date 2016-03-09 Time 10:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-02-17 Cont ID  
Sent By pleduc Date 2016-02-17 Time   Rev Time 0.00
Received By pleduc Date 2016-02-17 Time 12:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2016-01-06 Cont ID  
Sent By pleduc Date 2016-01-06 Time   Rev Time 0.00
Received By pleduc Date 2016-01-06 Time 15:28 Sent To  
Notes
2016-01-06 16:03:46THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE DOCUMENTATION ON WHAT THE BUSINESS
 PRODUCES/MANUFACTURE'S/ PROCESSES. WHAT TAKES PLACE IN
 THE LAB?
  
 2. PROVIDE DOCUMENTATION ON THE NITROGEN GENERATOR AND
 WHAT IT IS USED FOR. PROVIDE THE MANUFACTURES SPEC'S
 INCLUDING INSTALLATION RECOMMENDATIONS/PRECAUTIONS.
  
 3. EXIT DOOR HARDWARE IS NOT PROVIDED. EXIT DOOR
 LOCKING/LATCHING SHALL COMPLY WITH NFPA 101, 5TH
 EDITION, CHAPTER 7.
  
 4. EXIT SIGNAGE SHALL BE PROVIDED FOR FROM THE LAB
 AREA.
  
 5. EMERGENCY LIGHTS SHALL BE PROVIDED FOR IN THE LAB
 AREA.
  
 6. PROVIDE AN EQUIPMENT PLAN FOR THE LAB.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2016-03-22 Cont ID  
Sent By ccole Date 2016-03-22 Time 09:48 Rev Time 0.00
Received By ccole Date 2016-03-21 Time 15:19 Sent To  
Notes
2016-03-21 15:19:50RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-03-17 Cont ID  
Sent By tklarge Date 2016-03-17 Time 14:56 Rev Time 0.00
Received By tklarge Date 2016-03-07 Time 10:14 Sent To  
Notes
2016-03-10 10:38:333/10 TO B30
2016-03-08 10:14:46B30

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-24 Cont ID  
Sent By jwitmer Date 2016-02-24 Time 15:53 Rev Time 0.00
Received By jwitmer Date 2016-02-12 Time 09:58 Sent To  
Notes
2016-02-24 13:46:012/24 TO JIM
2016-02-16 10:00:30B18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-10 Cont ID  
Sent By vperez Date 2016-02-10 Time 13:28 Rev Time 0.00
Received By vperez Date 2016-02-10 Time 13:28 Sent To  
Notes
2016-02-10 13:28:38TO CAROLINE/LAURA
2015-12-30 14:02:04B18

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2016-03-22 Cont ID  
Sent By ccole Date 2016-03-22 Time 09:48 Rev Time 0.00
Received By ccole Date 2016-03-22 Time 08:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2016-03-14 Cont ID  
Sent By ccole Date 2016-03-14 Time 08:49 Rev Time 0.00
Received By ccole Date 2016-03-14 Time 08:49 Sent To  
Notes
2016-03-14 09:53:183RD REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120875
 3/14/16
  
 1) SHEET M1: THE 95,000 BTU TRANE ROOFTOP AC MUST BE
 RATED AT A MINIMUM 11.4 EER: THE SCHEDULE IS INDICATING
 10.3- SEE TABLE C403.2.3(1) FBC-14 ENERGY CONSERVATION.
 2) M1: THE MINIMUM VENTILATION RATE FOR THE LAB
 ACCORDING TO TABLE 403.3 IS BASED ON AN OCCUPANT
 DENSITY OF 25 PEOPLE PER 1000 SF., HOWEVER THE RATE ON
 THE PLAN IS INDICATING ONLY 10 PPL FOR 958 SF.- PLEASE
 CORRECT.
 3) M1: REFER TO SECTION 501.3.1(2) AND PROVIDE
 CLEARANCE DISTANCE MEASUREMENTS ON THE PLAN FOR THE
 EXHAUST OUTLET.
 4) SUBMIT A MIAMI-DADE NOA OR FLORIDA PRODUCT APPROVAL
 FOR THE EXHAUST LOUVER REVIEWED AND APPROVED WITH
 SIGNATURE BY THE DESIGN PROFESSIONAL OF RECORD.
 5) INDICATE THE TYPE AND GAGE OF EXHAUST DUCT MATERIAL,
 AND PROVIDE DUCT HANGING AND CONNECTION DETAILS FOR
 BOTH THE EXHAUST AND SUPPLY DUCTS.
 6) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE NEW
 RTU TO THE EXISTING CURB- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-19 Cont ID  
Sent By ccole Date 2016-02-19 Time 16:08 Rev Time 0.00
Received By ccole Date 2016-02-19 Time 16:08 Sent To  
Notes
2016-02-19 16:19:572ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120875
 2/19/16
  
 1) AN EXHAUST SYSTEM AT A RATE 1.0 CFM PER SQUARE FOOT
 IS REQUIRED FOR THE LAB AREA AND THE RECIRCULATION OF
 AIR FROM THE SPACE IS PROHIBITED- SEE TABLE 403.3 AND
 FOOTNOTE G. IN ADDITION, TABLE 403.3 REQUIRES OUTDOOR
 AIR FOR OCCUPANTS OF THE LAB AT 10 CFM PER PERSON AND
 .18 CFM PER SQUARE FOOT OF THE SPACE. PLEASE REFER TO
 SECTION 403.3 WHERE IT STATES THAT "VENTILATION RATES
 FOR OCCUPANCIES NOT REPRESENTED IN TABLE 403.3 SHALL BE
 THOSE FOR A LISTED OCCUPANCY CLASSIFICATION THAT IS
 MOST SIMILAR IN TERMS OF OCCUPANT DENSITY, ACTIVITIES
 AND BUILDING CONSTRUCTION; OR SHALL BE DETERMINED BY AN
 APPROVED ENGINEERING ANALYSIS." THE VENTILATION RATES
 LISTED ABOVE ARE DERIVED FROM THE "SCIENCE
 LABORATORIES" LISTING IN TABLE 403.3. PLEASE REVISE THE
 PLAN ACCORDINGLY.
 2) THE BUILLDING RESPONSE NARRATIVE INDICATES THE
 NITROGEN GENERATOR SHALL NOT BE INSTALLED. PLEASE NOTE
 THAT IF TO BE INSTALLED A LATER DATE, EITHER A REVISION
 TO THIS PERMIT OR SEPARATE PERMIT WILL BE REQUIRED AT
 WHICH TIME A COMPLETE REVIEW OF THE GENERATOR
 SPECIFICATIONS AND EXHAUST SYSTEM MUST BE CONDUCTED AND
 COMPLIANCES IN ACCORDANCE WITH HAZARDOUS EXHAUST
 SYSTEMS MAY BE ENFORCED.
 3) PLEASE PROVIDE ON THE PLAN A NARRATIVE TO CLARIFY
 THE PROCESSES THAT WILL OCCUR IN THE LAB INCLUDING AN
 ITEMIZED LIST OF CHEMICALS AND THEIR QUANTITIES, AND
 HOW THE CHEMICALS WILL BE DISPENSED AND STORED- REFER
 TO SECTIONS 502.8 AND 510.1 FBC-14 MECHANCIAL.
 4) THE ARCHITECT OF RECORD JAMES C PAINE JR. DID NOT
 PROVIDE VALID SIGNATURES AND SEALS ON ONE OF THE TWO
 NEW PLAN SETS SUBMITTED- SEE SECTION 61G1-16.003
 FLORIDA ADMINISTRATIVE CODE.
 5) TWO RTU-1 RETURN DUCTS DO NOT HAVE SIZES- ONE FROM
 THE CORRIDOR AND ONE FROM SHIPPING/RECEIVING.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-31 Cont ID  
Sent By ccole Date 2015-12-31 Time 09:40 Rev Time 0.00
Received By ccole Date 2015-12-31 Time 09:40 Sent To  
Notes
2015-12-31 09:52:211ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120875
 12/31/15
  
 1) VENTILATION CALCULATIONS ARE REQUIRED WHEN AC
 SYSTEMS ARE ALTERED- SEE SECTION 809.2 FBC-14 EXISTING
 BUILDING AND SHOW COMPLIANCE.
 2) THE PLAN SHOWS THE CORRIDOR RUNNING BETWEEN THE
 STAFF LOUNGE AND THE DIRECTOR/CONFERENCE ROOM BEING
 USED AS A RETURN AIR DUCT- SEE SECTION 601.2 FBC-14
 MECHANICAL AND CORRECT.
 3) THE PLAN INDICATES UNDERSIZED RETURN AIR TRANSFER
 DUCTS FROM ALL OF THE ROOMS- SEE SECTION 601.5 AND
 CORRECT.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2016-03-17 Cont ID  
Sent By tklarge Date 2016-03-17 Time 14:56 Rev Time 0.00
Received By tklarge Date 2016-03-17 Time 10:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-02-20 Cont ID  
Sent By tklarge Date 2016-02-20 Time 07:49 Rev Time 0.00
Received By tklarge Date 2016-02-20 Time 06:25 Sent To  
Notes
2016-02-20 06:55:381) SHT.P1 - THE SHEET IS REQUIRED TO BE SEALED BY THE
 DESIGN PROFESSIONAL OF RECORD. FAC RULE 61G1-16.001.
 2) THE LAB SINKS SHALL BE STACKED & VENTED. 2014 FPC
 SEC.901.2.
 3) SHOW ON THE PLANS THAT THE HEIGHT OF THE STAFF
 LOUNGE SINK COMPLIES WITH THE FL. ACCESS. CODE SEC.
 212.2 & 804.( MAX. 34 INCHES HIGH)
 4) SHOW ON THE PLANS THAT THE DRINKING FOUNTAINS ARE
 ARRANGED FOR A FORWARD APPROACH PER THE 2014 FAC
 SEC.602.2.
 5) CLEARLY SHOW THE WIDTH OF THE TOILET ROOMS ON THE
 PLANS. THE TOILET ROOMS SHALL BE A MINIMUM WIDTH OF 85
 INCHES WHEN THE TOILET AND LAVATORY ARE LOCATED ON THE
 SAME WALL.
 6) THE HIGH SIDE DRINKING FOUNTAIN SHALL COMPLY WITH
 THE 2014 FAC SEC. 307 FOR PROTRUDING OBJECTS. AN
 OPTIONAL SKIRT MAY BE REQUIRED TO KEEP THE LEADING EDGE
 BELOW 27 INCHES.2014 FAC SEC. 307.2.
 7) THE RESPONSE FROM THE ARCHITECT REFERS TO A SIDE
 APPROACH FOR THE STAFF LOUNGE SINK BUT A FORWARD
 APPROACH IS SHOWN ON THE PLANS. CLARIFY.
 8) THE VENT FOR THE LAVS SHALL BE MIN. OF 2 INCH. 2014
 FPC SEC.906.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-07 Cont ID  
Sent By gjohnson Date 2016-01-07 Time 15:54 Rev Time 0.00
Received By gjohnson Date 2016-01-07 Time 15:54 Sent To  
Notes
2016-01-15 09:17:011ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1.PLEASE PROVIDE A LIST OF CHEMICALS BEING USED AT THIS
 FACILITY.
 2. WHAT STATE ARE THE CHEMICALS IN ,SOLID ,LIQUID, OR
 GAS.
 3. HOW THE CHEMICALS ARE BEING STORED AND IN WHAT
 AMOUNTS.
 4. PLEASE PROVIDE MSDS SHEETS FOR ALL THE CHEMICALS
 BEING USED AND STORED.
 PER WPB AMEND TO FBC 107.2.1
 5. HOW WILL USED CHEMICALS BE DISPOSED OF WILL ANY BE
 GOING INTO THE SANITARY SYSTEM, SHALL COMPLY WITH FBC
 PL SEC 803
 6. PLEASE PROVIDE A BREAK DOWN OF COST TO SHOW
 COMPLIANCE TO FBC ACC SEC 202.4.1-202.4.2
 7. PROVIDE WATER RISER DIAGRAM. PER WPB AMEND TO FBC
 SEC 107.3.5.1.3(13)
 8. SHOW ALL PIPE SIZES ON RISER DIAGRAM. PER WPB AMEND
 TO FBC 107.2.1
 9. WASTE ARMS FOR LAV SHALL COMPLY WITH FBC PL TABLE
 909.1
 10. IS SINK IN STAFF LOUNGE EXISTING.
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved