Plan Review Details - Permit 15120860
Plan Review Stops For Permit 15120860
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2016-01-11 Cont ID  
Sent By tklarge Date 2016-01-11 Time 11:22 Rev Time 0.00
Received By tklarge Date 2016-01-11 Time 11:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-09 Cont ID  
Sent By tklarge Date 2016-01-09 Time 04:36 Rev Time 0.00
Received By tklarge Date 2016-01-08 Time 12:47 Sent To  
Notes
2016-01-08 12:47:50ROUTED TO TKLARGE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-30 Cont ID  
Sent By tklarge Date 2015-12-30 Time 06:30 Rev Time 0.00
Received By tklarge Date 2015-12-29 Time 15:00 Sent To  
Notes
2015-12-29 15:00:59TLARGE'S DESK

Review Stop P PLUMBING
Rev No 3 Status N Date 2016-01-14 Cont ID  
Sent By skennedy Date 2016-01-14 Time 16:17 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2016-01-09 Cont ID  
Sent By tklarge Date 2016-01-09 Time 03:31 Rev Time 0.00
Received By tklarge Date 2016-01-09 Time 02:33 Sent To  
Notes
2016-01-09 03:59:201) VOID/REMOVE THE OLD PLANS FROM THE SET.SUBMIT ONLY 2
 SETS OF PLANS FOR REVIEW. ATTACH THE 8 1/2 X11 DRAWING
 TO THE LARGE PLANS.WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE REVISED GAS PLAN HAS THE ARCHITECT'S NAME & TILE
 BLOCK ON THE PLANS. FLORIDA ADMINISTRATIVE CODE RULE
 61G1-16.001 REQUIRES THAT THE PLANS BE SIGNED AND
 SEALED BY THE ARCHITECT OF RECORD.
 3) IS THE BBQ LOCATED IN AN OPEN AREA? IT IS DIFFICULT
 TO TELL FROM THE SUBMITTED FLOOR PLAN. CLARIFY.
 4) THE PLANS SHOW THE COPPER LINE FOR THE BBQ TO BE
 INSTALLED BELOW GROUND IN A SLEEVE.THE INSTALLATION FOR
 THE PIPE AND SLEEVE SHALL COMPLY WITH 2014 FGC
 SEC.404.14.1.
 5) THE USE OF COPPER TUBING FOR GAS PIPING HAS
 LIMITATIONS PER FGC SEC.403.4.3 - COPPER AND BRASS.
 COPPER AND BRASS PIPE SHALL NOT BE USED IF THE GAS
 CONTAINS MORE THAN AN AVERAGE OF 0.3 GRAINS OF HYDROGEN
 SULFIDE PER 100 STANDARD CUBIC FEET OF GAS (0.7
 MILLIGRAMS PER 100 LITERS). THREADED COPPER, BRASS AND
 ALUMINUM-ALLOY PIPE SHALL NOT BE USED WITH GASES
 CORROSIVE TO SUCH MATERIALS. -SUBMIT VERIFICATION FROM
 THE GAS PURVEYOR THAT THE GAS DOES NOT CONTAIN MORE
 THAN 0.3 GRAINS OF HYDROGEN SULFIDE PER 100 STANDARD
 CUBIC FEET OF GAS.
 6) THE FIREPLACE SHALL BE EQUIPPED WITH A FLAME
 SAFEGUARD DEVICE PER 2014 FGC SEC.602.2 UNLESS THE THE
 FIREPLACE HAS BEEN TESTED IN ACCORDANCE WITH ANSI
 Z21.84. I COULD NOT FIND ANYTHING IN THE FIREPLACE
 SPECIFICATIONS THAT NOTES IT HAS BEEN TESTED WITH
 Z21.84.
 7) A YELLOW INSULATED TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO THE UNDERGROUND NONMETALLIC PIPING.2014 FGC
 SEC.404.17.3.
 8) THE SUBMITTED PLAN HAS AN AREA SHOWN AS "2ND FLOOR
 GAS PLAN" BUT THERE IS NO PIPNG SHOWN. IF GAS PIPE IS
 NOT BEING RUN TO THIS AREA, NOTE THIS ON THE PLAN.WPB
 AMEND. TO FBC SEC. 107.2.1.
  
 NOTE: PRIOR TO RESUBMITTING CORRECTIONS, PLEASE ARRANGE
 AN APPOINTMENT WITH ME SO WE CAN REVIEW THE CORRECTED
 PLANS AND ENSURE ALL COMMENTS HAVE BEEN ADDRESSED. THIS
 WILL HELP EXPEDITE YOUR PERMIT.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By tklarge Date 2015-12-30 Time 06:30 Rev Time 0.00
Received By tklarge Date 2015-12-30 Time 06:02 Sent To  
Notes
2015-12-30 06:22:511. SHOW THE TYPE OF PIPE MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE CORRESPONDING EHD NUMBER OF THE
 CORRUGATED STAINLESS STEEL TUBING FOR EACH PIPE SIZE
 (IF APPLICABLE). WPB AMENDMENTS TO FBC SEC.107.2.1. THE
 PLAN ONLY SHOWS THAT THE DROPS ARE GALVANIZED, WHAT
 TYPE OF PIPING IS THE REST OF THE ABOVEGROUND AND
 UNDERGROUND SYSTEMS?
  
 2. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (METER
 OR MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND / OR SYSTEM PER THE 2014 FBC-FUEL GAS
 SEC.402.4.1 OR 2014 FBC-RES. SEC. G 2413.3.
  
 3. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2014 FBC-FUEL GAS SEC.402.2 OR FBC RES.
 SEC. G2413.2. .
  
 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY
 COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2014
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED.
  
 5) SHOW THE LOCATION OF ALL STEP DOWN REGULATORS ( IF
 APPLICABLE). WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 6) NOTE ON THE PLAN THE APPLICABLE SIZING TABLE(S) USED
 IN THE DESIGN OF THE GAS SYSYTEM FOR THE APPLICABLE
 PRESSURES. WPB AMENDMENTS TO FBC SEC.107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  