Plan Review Details - Permit 15120814
Plan Review Stops For Permit 15120814
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-07 Cont ID  
Sent By ccole Date 2016-01-07 Time 08:47 Rev Time 0.00
Received By ccole Date 2016-01-06 Time 16:18 Sent To  
Notes
2016-01-06 16:18:10RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-30 Cont ID  
Sent By ccole Date 2015-12-30 Time 10:13 Rev Time 0.00
Received By ccole Date 2015-12-28 Time 10:32 Sent To  
Notes
2015-12-29 10:32:59CCOLE'S DESK

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-07 Cont ID  
Sent By ccole Date 2016-01-07 Time 08:46 Rev Time 0.00
Received By ccole Date 2016-01-07 Time 08:46 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By ccole Date 2015-12-30 Time 07:44 Rev Time 0.00
Received By ccole Date 2015-12-30 Time 07:44 Sent To  
Notes
2015-12-30 07:52:231ST REVIEW: FBC 2010 MECHANICAL
 PERMIT #15120814
 12/30/15
  
 1) THE ENERGY EFFICIENCY FORM 405-10 MUST BE SIGNED AND
 DATED BY THE PREPARER AND THE OWNER/AGENT. TWO FORMS
 FOR THE ENCLOSED PORCH CONVERSION WERE SUBMITTED
 WITHOUT SIGNATURE.
 2) THE REVISED MECHANICAL PLAN INDICATES A NEW
 MINI-SPLIT AC SYSTEM FOR THE ENCLOSED PORCH AREA.
 PLEASE PROVIDE A REVISED ELECTRICAL PLAN.
 3) TWO DIFFERENT AC PLANS HAVE BEEN SUBMITTED EACH
 HAVING M.1 SHEET NUMBERS. PLEASE GIVE ONE OF THESE
 SHEETS A DIFFERENT NUMBER TO AVOID CONFUSION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  