Plan Review Details - Permit 15120804
Plan Review Stops For Permit 15120804
Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-12-31 Cont ID  
Sent By tklarge Date 2015-12-31 Time 14:18 Rev Time 0.00
Received By tklarge Date 2015-12-31 Time 14:18 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By tklarge Date 2015-12-29 Time 14:46 Rev Time 0.00
Received By tklarge Date 2015-12-29 Time 14:37 Sent To  
Notes
2015-12-29 14:44:361) SHOW THE BTU OF THE TANKLESS WATER HEATER. THE
 MANUF. SPECS. SHOW A RANGE OF A BTU LOAD. IT APPEARS
 THESE ARE 199,000 BTU LOAD WATER HEATERS. CLARIFY.
 2) TABLE 402.4 (5) IS FOR A 2 PSI SYSYTEM BUT THE PSI
 SHOWN ON THE RISER DIAGRAM IS 5 PSI. CLARIFY.
 3) INDICATE ON THE PLANS HOW THE PIPING IS GOING TO BE
 SUPPORTED. COMPLY WITH 2014 FGC SEC.415 & TABLE 415.1.
 4)

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-31 Cont ID  
Sent By tklarge Date 2015-12-31 Time 14:19 Rev Time 0.00
Received By tklarge Date 2015-12-31 Time 14:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-29 Cont ID  
Sent By tklarge Date 2015-12-29 Time 14:46 Rev Time 0.00
Received By tklarge Date 2015-12-28 Time 13:52 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-12-31 Cont ID  
Sent By tklarge Date 2015-12-31 Time 14:19 Rev Time 0.00
Received By tklarge Date 2015-12-31 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By tklarge Date 2015-12-29 Time 14:47 Rev Time 0.00
Received By tklarge Date 2015-12-29 Time 06:16 Sent To  
Notes
2015-12-29 14:32:131) SUBMIT A WATER RISER DIAGRAM FOR THE 3" HOT AND COLD
 WATER FEEDS AND ALL OTHER WATER PIPING THAT WILL BE
 ALTERED OR INSTALLED. SHOW ALL VALVES, PUMP,TANKS AND
 PIPE SIZES.WPB AMEND. TO FBC SEC. 107.2.1.
 2) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE
 TANKLESS WATER HEATERS & STORAGE TANKS. WPB AMEND. TO
 FBC SEC. 107.2.1.
  
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  