Plan Review Details - Permit 15120804
Plan Review Stops For Permit 15120804 |
Review Stop |
G |
GAS REVIEW |
Rev No |
2 |
Status |
P |
Date |
2015-12-31 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-31 |
Time |
14:18 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-31 |
Time |
14:18 |
Sent To |
|
|
Notes |
|
|
Review Stop |
G |
GAS REVIEW |
Rev No |
1 |
Status |
F |
Date |
2015-12-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-29 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-29 |
Time |
14:37 |
Sent To |
|
|
Notes |
2015-12-29 14:44:36 | 1) SHOW THE BTU OF THE TANKLESS WATER HEATER. THE | | MANUF. SPECS. SHOW A RANGE OF A BTU LOAD. IT APPEARS | | THESE ARE 199,000 BTU LOAD WATER HEATERS. CLARIFY. | | 2) TABLE 402.4 (5) IS FOR A 2 PSI SYSYTEM BUT THE PSI | | SHOWN ON THE RISER DIAGRAM IS 5 PSI. CLARIFY. | | 3) INDICATE ON THE PLANS HOW THE PIPING IS GOING TO BE | | SUPPORTED. COMPLY WITH 2014 FGC SEC.415 & TABLE 415.1. | | 4) |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
2 |
Status |
N |
Date |
2015-12-31 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-31 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-31 |
Time |
14:13 |
Sent To |
|
|
Notes |
|
|
Review Stop |
I |
INCOMING/PROCESSING |
Rev No |
1 |
Status |
N |
Date |
2015-12-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-29 |
Time |
14:46 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-28 |
Time |
13:52 |
Sent To |
P |
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
2 |
Status |
P |
Date |
2015-12-31 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-31 |
Time |
14:19 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-31 |
Time |
14:19 |
Sent To |
|
|
Notes |
|
|
Review Stop |
P |
PLUMBING |
Rev No |
1 |
Status |
F |
Date |
2015-12-29 |
|
|
Cont ID |
|
Sent By |
tklarge |
Date |
2015-12-29 |
Time |
14:47 |
Rev Time |
0.00 |
Received By |
tklarge |
Date |
2015-12-29 |
Time |
06:16 |
Sent To |
|
|
Notes |
2015-12-29 14:32:13 | 1) SUBMIT A WATER RISER DIAGRAM FOR THE 3" HOT AND COLD | | WATER FEEDS AND ALL OTHER WATER PIPING THAT WILL BE | | ALTERED OR INSTALLED. SHOW ALL VALVES, PUMP,TANKS AND | | PIPE SIZES.WPB AMEND. TO FBC SEC. 107.2.1. | | 2) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE | | TANKLESS WATER HEATERS & STORAGE TANKS. WPB AMEND. TO | | FBC SEC. 107.2.1. | | | | | | | | PLUMBING PLAN REVIEW | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | 561-805-6692 | | [email protected] | | |
|
|
|