Plan Review Details - Permit 15120750
Plan Review Stops For Permit 15120750
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-04-01 Cont ID  
Sent By jwitmer Date 2016-04-01 Time 14:46 Rev Time 0.00
Received By jwitmer Date 2016-04-01 Time 13:20 Sent To  
Notes
2016-04-01 14:44:38BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120750
 ADD: 811A BELVEDERE RD.
 CONT: TBD
 TEL: 305-710-7178
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI., APRIL 01/2016
 ACTION: BUILDING PROVISO
  
 1) THIS TENANT SPACE BEING USED AS A MIXED USE
 OCCUPANCY, A1 OCCUPANCY(THEATER), A3 (PLACE OF WORSHIP)
 AND BUSINESS OCCUPANCY WILL BE LIMITED WITH PLACARD TO
 A OCCUPANT LOAD NOT TO EXCEED 49 OCCUPANTS PER :
 2014 FBC-B 1004.3. POSTING OF OCCUPANT LOAD.
 EVERY ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL
 HAVE THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE
 OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE
 MAINTAINED BY THE OWNER OR AUTHORIZED AGENT.
  
 2) AT TIME OF INSPECTION PLEASE PROVIDE COMPLIANCE WITH
 THE HUNG CURTAINS SEPARATING THE PRE-FUNCTION AND
 THEATER AREAS. SHOW COMPLIANCE WITH:
 2014 FBC-B 806.1 IN OCCUPANCIES IN GROUPS A, E, I AND
 R-1 AND DORMITORIES IN GROUP R-2, CURTAINS, DRAPERIES,
 HANGINGS AND OTHER DECORATIVE MATERIALS SUSPENDED FROM
 WALLS OR CEILINGS SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 IN ACCORDANCE WITH
 SECTION 806.2 OR BE NONCOMBUSTIBLE.
  
 2014 FBC-B 806.2 ACCEPTANCE CRITERIA AND REPORTS. WHERE
 REQUIRED BY SECTION 806.1, DECORATIVE MATERIALS SHALL
 BE TESTED BY AN AGENCY AND MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701 OR SUCH MATERIALS
 SHALL BE NONCOMBUSTIBLE. REPORTS OF TEST RESULTS SHALL
 BE PREPARED IN ACCORDANCE WITH NFPA 701 AND FURNISHED
 TO THE BUILDING OFFICIAL UPON REQUEST.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-09 Cont ID  
Sent By jwitmer Date 2016-01-09 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2016-01-08 Time 14:28 Sent To  
Notes
2016-01-09 08:00:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120750
 ADD: 811A BELVEDERE RD.
 CONT: TBD
 TEL: 305-710-7178
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRI., JAN. 08/2016
 ACTION: DENIED
  
 1) SHEET A0.10 UNDER THE BUILDING CODE SUMMARY;
  
 1A) DISCREPANCY IN PLANS THE TOTAL PROJECT AREA IS
 STATED IN THE PLANS 1682 SQ. FT. THE BUILDING SCALE
 INDICATES 1/8 INCH / FOOT THE TOTAL OVERALL SQUARE FEET
 IS OVER 6580 SQUARE FEET. GOOGLE SHOWS FOR LEASE SIGNS
 WITH 1800 =/- SQUARE FEET. PLEASE CORRECT THE
 DISCREPANCIES IN THE PLAN. 107.2.1.3.
  
 1B) THE BUILDING CODE SUMMARY LIST THIS ALTERATION AS A
 LEVEL 3, A LEVEL 3 ALTERATION PER THE 2014 FBC-EXISTING
 BUILDING CODE 505.1 SCOPE. LEVEL 3 ALTERATIONS APPLY
 WHERE THE WORK AREA EXCEEDS 50 PERCENT OF THE AGGREGATE
 AREA OF THE BUILDING. PLEASE PROVIDE WHERE 50 % OF THE
 FLOOR AREA IS BEING ALTERED? THIS BUILDING APPEARS TO
 BE A PARTIAL CHANGE OF OCCUPANCY AND WOULD NEED TO
 COMPLY WITH 2014 FBC-EXISTING BLDG. CODE 1001.3.1
 PARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. WHERE A
 PORTION OF AN EXISTING BUILDING IS CHANGED TO A NEW
 OCCUPANCY CLASSIFICATION, SECTION 1012 SHALL APPLY.
  
 1C) PLEASE BREAK DOWN THE AREAS OF OCCUPANCY BY SQUARE
 FOOTAGE AND OCCUPANT LOADS FOR EACH USE AREA. THE PLANS
 INDICATE A BUSINESS OCCUPANCY OF 1682/100= 17 OCCUPANTS
 . THE OFFICE/ WORKROOM IS ONLY 462 SQ. FT. OR A
 OCCUPANT LOAD OF 5. FOR BOTH THE A1 THEATER AND THE A3
 PLACE OF WORSHIP THE OCCUPANT LOAD IS FIGURED AT 15
 SQUARE FEET PER OCCUPANT (NET) PER FBC-B TABLE
 1004.1.2. PLEASE PROVIDE THE TOTAL SQUARE FOOTAGE OF
 THE BUILDING AND OCCUPANT LOAD.
  
 1D) PLEASE SHOW THE MEANS OF EGRESS PATH NOT AS A
 SINGLE LINE BUT THE WIDTH OF THE MEANS OF EGRESS AND
 OCCUPANT LOADS. THIS SQUARE FOOTAGE CAN BE DELETED FROM
 THE TOTAL SQUARE FOOTAGE AS WELL AS THE RESTROOMS AND
 WALLS (NET) SEE CHAPTER 2 DEFINITIONS.
  
 1E) PLEASE PROVIDE ADDITIONAL DETAIL AS TO THE USAGE OF
 THE OFFICE / WORK ROOM. PLEASE DEFINE WHAT ACTIVITIES
 WILL BE TAKING PLACE IN THE WORK ROOM. THE SECOND MEANS
 OF EGRESS IS THROUGH THE WORK ROOM.
 COMPLIANCE WITH THE 2914 FBC-B 1014.2 EGRESS THROUGH
 INTERVENING SPACES WILL NEED TO BE PROVIDED AS TO THE
 ALLOWABLE USAGE OF THE ROOM, AND A DEMARCATED PATH
 CLEAR OF FURNITURE AND OR OBSTACLES.
  
 2) SHEET A0.10 SHOWS WHAT APPEARS TO BE A CURTAIN HUNG
 ACROSS WHAT APPEARS TO BE A PRE-FUNCTION AREA AND THE
 MAIN ASSEMBLY OCCUPANCY. PLEASE SHOW COMPLIANCE WITH
 2014 FBC-B 1008.1 MEANS OF EGRESS DOORS SHALL BE
 READILY DISTINGUISHABLE FROM THE ADJACENT CONSTRUCTION
 AND FINISHES SUCH THAT THE DOORS ARE EASILY
 RECOGNIZABLE AS DOORS. MIRRORS OR SIMILAR REFLECTING
 MATERIALS SHALL NOT BE USED ON MEANS OF EGRESS DOORS.
 MEANS OF EGRESS DOORS SHALL NOT BE CONCEALED BY
 CURTAINS, DRAPES, DECORATIONS OR SIMILAR MATERIALS.
  
 3) SHEET A0.10 LIST THE FRONT AREA OF THE THEATER AS A
 LOBBY. IS THIS AREA TO BE CONSIDERED A PRE-FUNCTION
 AREA WHERE PERSONS ARE ADMITTED TO THE BUILDING AT
 TIMES WHEN SEATS ARE NOT AVAILABLE, SUCH PERSONS SHALL
 BE ALLOWED TO WAIT IN A LOBBY OR SIMILAR SPACE,
 PROVIDED SUCH LOBBY OR SIMILAR SPACE SHALL NOT ENCROACH
 UPON THE REQUIRED CLEAR WIDTH OF THE MEANS OF EGRESS.
 SUCH FOYER, IF NOT DIRECTLY CONNECTED TO A PUBLIC
 STREET BY ALL THE MAIN ENTRANCES OR EXITS, SHALL HAVE A
 STRAIGHT AND UNOBSTRUCTED CORRIDOR OR PATH OF TRAVEL TO
 EVERY SUCH MAIN ENTRANCE OR EXIT. 1028.3.
  
 4) THE PLANS FAIL TO PROVIDE AN ACCESSIBLE CIRCULATION
 PATH, ACCESSIBLE SEATING AND COMPANION SEATING. 2014
 FBC-ACCESSIBILITY CODE:
  
 206.2.6 PERFORMANCE AREAS. WHERE A CIRCULATION PATH
 DIRECTLY CONNECTS A PERFORMANCE AREA TO AN ASSEMBLY
 SEATING AREA, AN ACCESSIBLE ROUTE SHALL DIRECTLY
 CONNECT THE ASSEMBLY SEATING AREA WITH THE PERFORMANCE
 AREA. AN ACCESSIBLE ROUTE SHALL BE PROVIDED FROM
 PERFORMANCE AREAS TO ANCILLARY AREAS OR FACILITIES USED
 BY PERFORMERS UNLESS EXEMPTED BY 206.2.3 EXCEPTIONS 1
 THROUGH 7.
  
 802.2 LINES OF SIGHT. LINES OF SIGHT TO THE SCREEN,
 PERFORMANCE AREA, OR PLAYING FIELD FOR SPECTATORS IN
 WHEELCHAIR SPACES SHALL COMPLY WITH 802.2.
  
 802.3 COMPANION SEATS. COMPANION SEATS SHALL COMPLY
 WITH 802.3.
  
 802.3.1 ALIGNMENT. IN ROW SEATING, COMPANION SEATS
 SHALL BE LOCATED TO PROVIDE SHOULDER ALIGNMENT WITH
 ADJACENT WHEELCHAIR SPACES. THE SHOULDER ALIGNMENT
 POINT OF THE WHEELCHAIR SPACE SHALL BE MEASURED 36
 INCHES (915 MM) FROM THE FRONT OF THE WHEELCHAIR SPACE.
 THE FLOOR SURFACE OF THE COMPANION SEAT SHALL BE AT THE
 SAME ELEVATION AS THE FLOOR SURFACE OF THE WHEELCHAIR
 SPACE.
  
 802.3.2 TYPE. COMPANION SEATS SHALL BE EQUIVALENT IN
 SIZE, QUALITY, COMFORT, AND AMENITIES TO THE SEATING IN
 THE IMMEDIATE AREA. COMPANION SEATS SHALL BE PERMITTED
 TO BE MOVABLE.
  
 802.4 DESIGNATED AISLE SEATS. DESIGNATED AISLE SEATS
 SHALL COMPLY WITH 802.4.
  
 5) SHEET M2.01:
  
 5A) THIS SHEET SHOWS A NEW ROOF TOP A/C CONDENSER ON A
 NEW ROOF TOP A/C STAND. PLEASE SHOW COMPLIANCE WITH
 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31(G) PRE-ENGINEERED A/C STANDS
  
 PLEASE ALSO REVIEW TABLE 1509.6.5 FBC-B CLEARANCES
 BELOW RAISED ROOF MOUNTED MECHANICAL UNITS.
  
 5B) 107.3.4.1 THOSE PRODUCTS WHICH ARE REGULATED BY DCA
 RULE 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 5C) PLEASE PROVIDE THE WIND DESIGN IN COMPLIANCE WITH:
 2014 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 5C) 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND
 SPEED, VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 5C)2. RISK CATEGORY.
  
 5C)3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED.
  
 5C)4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 5C)5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
  
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5D) PLEASE PROVIDE WHAT ADDITIONAL TYPE OF
 REINFORCEMENT OF THE ROOF FRAMING SYSTEM (MAIN WIND
 FORCE RESISTING SYSTEM) MWFRS WILL THE ENGINEERED A/C
 STAND ANCHOR TOO? FBC-B 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 5E) PLEASE ALSO PROVIDE THE METHOD OF ATTACHMENT OF THE
 A/C CONDENSER TO THE ROOF TOP STAND. FBC-B 1609.6.4.4.1
 COMPONENTS & CLADDING.
  
 5F) NONE OF THE PLANS PROVIDE A SECTION THROUGH THE
 EXTERIOR WALL INDICATING IF THERE IS A PARAPET WALL
 LOCATED NEXT TO THE A/C ROOF TOP CONDENSER. PLEASE SHOW
 COMPLIANCE WITH :
 2014 FBC- 1013.6 MECHANICAL EQUIPMENT. GUARDS SHALL BE
 PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH
 OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A SPHERE 21 INCHES (533
 MM) IN DIAMETER. THE GUARD SHALL EXTEND NOT LESS THAN
 30 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT.
  
 6) IMPACT FEES: BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY.
 THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-03-24 Cont ID  
Sent By mvaldes Date 2016-03-24 Time 09:04 Rev Time 0.00
Received By mvaldes Date 2016-03-24 Time 09:04 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-02-08 Cont ID  
Sent By mvaldes Date 2016-02-08 Time 15:43 Rev Time 0.00
Received By mvaldes Date 2016-02-08 Time 15:43 Sent To  
Notes
2016-02-08 15:44:49JOB PERMIT NUMBER: 15120750
 JOB ADDRESS: 811 A BELVEDERE RD
 WEST PALM BEACH
 DATE: FEB 8 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1 NEC 406.9(B) RECEPTACLES IN WET LOCATIONS. 15 AND 20
 AMPERE, 125 AND 250 VOLT RECEPTACLES INSTALLED IN A WET
 LOCATION SHALL HAVE AN ENCLOSURE THAT IS WEATHERPROOF
 WHETHER OR NOT THE ATTACHMENT PLUG CAP IS INSERTED. ALL
 15 AND 20 AMPERE, 125 AND 250 VOLT NONLOCKING
 RECEPTACLES SHALL BE LISTED WEATHER-RESISTANT TYPE
 ?WR?. THIS APPLIES TO THE CU UNIT UP ON THE ROOF.
 2 NEC 210.8 GFCI PROTECTION ??. (B) OTHER THAN DWELLING
 UNITS. AS FAR AS THE STAGE PERFORMANCE AREA RECEPTACLES
 WERE PORTABLE LIGHTING EQUIPMENT ARE TO BE USED.
 3 NO LIGHTING CONTROLS IN OFFICE AREA PLEASE SEE FBC-E
 C405 AS A REFERENCE
 4 FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & UNCONDITIONED SPACES.
 5 GENERAL NOTES STATE THAT A FIXTURE MOUNTING DETAIL
 SHALL BE FOUND IN ARCHITECTURAL ELEVATION? COULDN'T
 FIND !
 6 NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED
 7 PROVIDE ARC FLASH AND AVAILABLE FAULT CURRENT FIELD
 LABELING NEC 110.16 / 110.24
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD
 INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE
 OR ACTION TO SAME. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS FOR COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6713
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2016-03-29 Cont ID  
Sent By pleduc Date 2016-03-29 Time   Rev Time 0.00
Received By pleduc Date 2016-03-29 Time 15:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-12-31 Cont ID  
Sent By pleduc Date 2015-12-31 Time   Rev Time 0.00
Received By pleduc Date 2015-12-31 Time 09:48 Sent To  
Notes
2015-12-31 10:31:35THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1. SHEET A0.10 - THE OCCUPANCY LOAD CALCULATIONS ARE
 INCORRECT. THE OFFICE AREA CAN BE CALCULATED AS
 BUSINESS; HOWEVER, THE STAGE, VIEWING AND FRONT AREA
 SHALL BE CALCULATED AS ASSEMBLY, WHICH EXCEEDS THE
 INDICATED OCCUPANCY LOAD.
  
 2. SHEET A3.00 - THERE IS NO INDICATION OF DOOR
 HARDWARE OR LOCKING/LATCHING MECHANISMS. THE OCCUPANCY
 LOAD CALCULATIONS SHALL REQUIRE PANIC HARDWARE AND
 LOCKING/LATCHING ON ALL EXIT DOORS PER NFPA 101,
 CHAPTER 7, MEANS OF EGRESS.
  
 3. SHEET A1.01 - A CURTAIN WALL IS INDICATED TOWARDS
 THE FRONT OF THE OCCUPANCY. THIS CURTAIN IS NOT
 APPROVED AND CANNOT IMPEDE THE EXIT TRAVEL PATH AND
 MEANS OF EGRESS. AN EXIT SPACE SHALL BE CLEARLY
 INDICATED AND BE ILLUMINATED BY AN EXXIT SIGN. THE
 CURTAIN WALL SHALL BE FLAME RETARDENT AND MEET ALL THE
 REQUIREMENTS OF FLAME SPREAD AND SMOKE PROPAGATION PER
 NFPA 101.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-05-10 Cont ID  
Sent By ccole Date 2016-05-10 Time 07:41 Rev Time 0.00
Received By ccole Date 2016-05-06 Time 11:28 Sent To  
Notes
2016-05-09 11:28:27RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-04-07 Cont ID  
Sent By gjohnson Date 2016-04-07 Time 12:34 Rev Time 0.00
Received By gjohnson Date 2016-03-18 Time 09:59 Sent To  
Notes
2016-03-21 10:00:21B29

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-02-08 Cont ID  
Sent By cpuell Date 2016-02-08 Time 17:20 Rev Time 0.00
Received By cpuell Date 2015-12-22 Time 07:34 Sent To  
Notes
2015-12-23 07:35:10B01

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2016-04-01 Cont ID  
Sent By jwitmer Date 2016-04-01 Time 14:46 Rev Time 0.00
Received By jwitmer Date 2016-04-01 Time 14:45 Sent To  
Notes
2016-04-01 14:45:54 
 IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-09 Cont ID  
Sent By jwitmer Date 2016-01-09 Time 08:00 Rev Time 0.00
Received By jwitmer Date 2016-01-09 Time 08:00 Sent To  
Notes
2016-01-09 08:00:52IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-05-10 Cont ID  
Sent By ccole Date 2016-05-10 Time 07:41 Rev Time 0.00
Received By ccole Date 2016-05-10 Time 07:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-03-25 Cont ID  
Sent By ccole Date 2016-03-25 Time 10:00 Rev Time 0.00
Received By ccole Date 2016-03-25 Time 09:52 Sent To  
Notes
2016-03-25 10:27:192ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120750
 3/25/16
  
 1) THE AC SYSTEM AT 57, 340 BTUH MAXIMUM COOLING
 CAPACITY IS UNDERSIZED PER THE SUBMITTED CALCULATIONS
 WHICH INDICATE A HEAT LOAD OF APPROXIMATELY 63,700
 BTUH. ADDITIONALLY, THE CALCULATION IS BASED ON 568
 CFMS OF OUTSIDE VENTILATION AIR, HOWEVER THE
 VENTILATION CALCULATION ON SHEET M3.01 IS REQUIRING 790
 CFMS OF O/A FOR OCCUPANTS. PLEASE NOTE THAT INDUSTRY
 STANDARDS TYPICALLY SET O/A CFMS FOR SYSTEMS AT
 APPROXIMATELY 15- 20% OF SYSTEM CFM CAPACITY DEPENDING
 ON THE OCCUPANT LOADS. PLEASE REVISE THE CALCULATIONS
 AND SYSTEM SELECTION ACCORDINGLY.
 2) M2.01: THE 24"X24" RETURN GRILL IS UNDERSIZED FOR
 1900 CFMS. A MINIMUM OF 950 SQ. IN. OF FREE AIR RETURN
 IS REQUIRED.
 3) THE CU STAND ANCHORING DETAIL TO THE ROOF STRUCTURE
 ON M4.01 IS IN CONFLICT WITH THE DETAIL ON SHEET A4.10-
 PLEASE CORRECT.
 4) THE $30,000 JOB VALUE FOR 1600 SQ.FT. OF COMMERCIAL
 BUILDOUT. PLEASE PROVIDE AN ACCURATE JOB VALUE IN
 ACCORDANCE WITH SECTION 109.3 WPPB AMENDMENTS TO THE
 FBC-10 BUILDING CODE: PERMIT VALUATION. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST
 PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS
 SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By ccole Date 2015-12-29 Time 12:49 Rev Time 0.00
Received By ccole Date 2015-12-29 Time 12:41 Sent To  
Notes
2015-12-29 13:17:311ST REVIEW 2014 MECHANICAL
 PERMIT #15120750
 12/29/15
  
 1) PROVIDE AC COOLING AND HEATING LOAD CALCULATIONS IN
 COMPLIANCE WITH SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
 2) THE OUTSIDE AIR CALCULATIONS ARE NOT IN COMPLIANCE
 WITH ASHRAE 62.1 OR TABLE 403.3 FBC-14 MECHANICAL. THE
 OCCUPANT DENSITY IS CALCULATED AT 150 PER 1000 SF. FOR
 THE AUDITORIUM AREA WHICH COMPRISES APPROXIMATELY 752
 SF. USING A SCALE RULER (PLAN DOES NOT PROVIDE
 DIMENSIONS). I AM CALCULATING 112 PEOPLE AT 5 CFM'S
 EACH= 564 + 45 CFM'S FOR A TOTAL OF 609 CFRMS. THIS
 AMOUNT MUST BE ADDED TO THE O/A CFM'S REQUIRED FOR THE
 BACK OFFICE/WORK, AND THE FOYER AREAS.
 3) M2.1: PROVIDE THE DIMENSIONS OF THE RETURN AIR GRILL
 AT THE AC CLOSET- SEE SECTION 601.5.
 4) M2.1: THE TRANSFER DUCT IS UNDERSIZED PER SECTION
 601.5
 5) M2.1: THE AC CLOSET IS CONSIDERED A PLENUM CHAMBER
 PER SECTION C403.2.7.2 FBC-14 ENERGY CONSERVATION.
 PLEASE INDICATE THE TYPE OF DOOR TO BE INSTALLED AT THE
 CLOSET- REFER TO SECTION 602 FBC-14 MECHANCIAL.
 6) M4.01: PROVIDE THE CURRENT WIND LOAD DESIGN CRITERIA
 AND WIND SPEED FOR INSTALLATION OF THE AC ROOF STAND-
 SEE SECTION 301.15 FBC-14 MECHANICAL. SUBMIT TWO COPIES
 OF THE ROOF STAND NOA REVIEWED AND APPROVED BY THE
 E.O.R.
 7) M2.01: UNLESS A MINIMUM 42" HIGH PARAPET WALL IS
 EXISTING ABOVE THE ROOF, GUARDS MUST BE INSTALLED IN
 ACCORDANCE WITH SECTION 304.11 FBC-14 MECHANICAL.
 8) DUCT SMOKE DETECTORS ARE REQUIRED IN THE RETURN AIR
 SYSTEMS OF AC SYSTEMS WITH A DESIGN CAPACITY GREATER
 THAN 2000 CFM. IF THE CARRIER SYSTEM CAN PRODUCE MORE
 THAN 2000 CFMS IT MUST BE IN COMPLIANCE. PLEASE PROVIDE
 A CUT SHEET FROM THE MANUFACTURER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2016-04-07 Cont ID  
Sent By gjohnson Date 2016-04-07 Time 12:24 Rev Time 0.00
Received By gjohnson Date 2016-04-07 Time 12:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2016-01-06 Cont ID  
Sent By gjohnson Date 2016-01-06 Time 13:27 Rev Time 0.00
Received By gjohnson Date 2016-01-06 Time 13:27 Sent To  
Notes
2016-01-06 13:51:251ST REVIEW: FBC 2014
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  
 PLUMBING COMMENTS
  
 1.PROVIDE PLUMBING RISER DIAGRAM WATER AND SANITARY PER
 WPB AMEND TO FBC SEC107.3.5.1.3(13)
 2. YOUR PRIMARY OCCUPANCY IS ASSEMBLY A1 NOT BUSINESS
 PER FBC 303.2
 3. YOUR OCCUPANT LOAD SHALL BE CALCULATED BY USING THE
 DIFFERENT AREAS PRESCRIBED IN FBC TABLE 1004 .2.1
 ASSEMBLY FIXED SEAT ,ASSEMBLY WITHOUT FIXED SEATS
 STANDING ROOM 5 NET ,STAGES AND PLATFORMS 15 NET AND
 BUSINESS
 ALL THESE AREAS MUST BE CALCULATED SEPARATELY.
 4. A DRINKING FOUNTAIN COMPILING WITH FBC PL SEC410.2
 IS REQUIRED PER FBC PL TABLE 403.1
 5. A SERVICE SINK IS REQUIRED PER FBC PL TABLE 403.1