Plan Review Details - Permit 15120734
Plan Review Stops For Permit 15120734
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-01-06 Cont ID  
Sent By hmoser Date 2016-01-06 Time 08:36 Rev Time 0.00
Received By hmoser Date 2015-12-30 Time 16:58 Sent To M
Notes
2016-01-05 10:18:33GAVE TO H MOSER ON 1/5/16.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-29 Cont ID  
Sent By rmcdouga Date 2015-12-29 Time 17:54 Rev Time 0.00
Received By rmcdouga Date 2015-12-22 Time 13:26 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2016-01-06 Cont ID  
Sent By hmoser Date 2016-01-06 Time 08:36 Rev Time 0.00
Received By hmoser Date 2016-01-06 Time 08:25 Sent To  
Notes
2016-01-06 08:36:11PLAN PASS ONLY ONE SET OF PLANS SUBMITTED. GAVE PLAN TO
 SANDY W. TO COPY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-12-29 Cont ID  
Sent By rmcdouga Date 2015-12-29 Time 17:54 Rev Time 0.00
Received By rmcdouga Date 2015-12-29 Time 17:44 Sent To  
Notes
2015-12-29 18:34:03MECHANICAL MASTER PERMIT #15030292 WAS NEVER ISSUED. IF
 THESE ARE AS BUILT DRAWINGS, THE WORK WAS DONE WITHOUT
 PERMITS. SEE COMMENTS FROM REVIEW FOR MASTER.
  
 THE PLANS THAT WERE SUBMITTED ARE NOT CLEAR. THERE IS
 NO EQUIPMENT SCHEDULE. THE CFMS ARE NOT SHOWN. LOCATION
 OF AIR HANDLE IS NOT CLEAR. LOCATION OF CONDENSING UNIT
 IS NOT SHOWN. DISCONNECTS ARE NOT SHOWN. EQUIPMENT
 ANCHORING IS NOT SHOWN. SUBMIT COMPLETE SCALED DRAWINGS
 AND EQUIPMENT SIZING CALCULATIONS AS A RESUBMITTAL TO
 THE MASTER PERMIT #15030292. FBC 107.3.5.3