Plan Review Details - Permit 15120685
Plan Review Stops For Permit 15120685
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2016-02-03 Cont ID  
Sent By jwitmer Date 2016-02-03 Time   Rev Time 0.00
Received By jwitmer Date 2016-02-03 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2016-02-02 Cont ID  
Sent By jwitmer Date 2016-02-02 Time 11:14 Rev Time 0.00
Received By jwitmer Date 2016-02-02 Time 11:14 Sent To  
Notes
2016-02-02 11:14:42BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120685
 ADD: 2000 PRESIDENTIAL WAY # 1906
 CONT: AMENGUAL ELEC.
 TEL: 954-410-6364
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 2ND REVIEW
 DATE: TUES. FEB. 02/2016
 ACTION: DENIED
  
 1) COMPLIED., BUILDING TYPE IS A 1-A.
  
 2) 2ND REQUEST. THE COVERSHEET A-0.01 INDICATES NEW
 TILE FLOORS THROUGH OUT THE APARTMENT. PLEASE PROVIDE
 TEST REPORTS NOT THE MANUFACTURERS SPEC. SHOWING
 COMPLIANCE WITH:
  
 2A) 2ND REQUEST. FBC-B 2014 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) 2ND REQUEST. FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) 2ND REQUEST. FLAME SPREAD- FBC-B 2014 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-12-30 Cont ID  
Sent By   Date 2015-12-30 Time 06:59 Rev Time 0.00
Received By jwitmer Date 2015-12-30 Time 06:44 Sent To  
Notes
2015-12-30 06:56:29BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15120685
 ADD: 2000 PRESIDENTIAL WAY # 1906
 CONT: AMENGUAL ELEC.
 TEL: 954-410-6364
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
  
 1ST REVIEW
 DATE: WED. DEC. 30/2015
 ACTION: DENIED
  
 1) THE COVERSHEET A-0.01 INDICATES THE BUILDING TYPE AS
 A II-A. PLEASE REVIEW THE 2014 FBC-B TABLE 503 FOR A R2
 II-A IS ONLY ALLOWED 4 STORIES. THIS BUILDING IS 20
 PLUS STORIES, BUILDING TYPE IS A 1-A.
  
 2) THE COVERSHEET A-0.01 INDICATES NEW TILE FLOORS
 THROUGH OUT THE APARTMENT. PLEASE PROVIDE TEST REPORTS
 SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2016-01-22 Cont ID  
Sent By dharvey Date 2016-01-22 Time 14:11 Rev Time 0.00
Received By dharvey Date 2016-01-22 Time 13:41 Sent To I
Notes
2016-01-22 14:13:11PLANS INDICATE LEVEL 1 ALTERATION. ONLY REPLACEMENT OF
 DEVICES IS INDICATED WITH NO CHANGE TO LAYOUT OR FLOOR
 PLAN. IF WALSS ARE MOVED, REMOVED OR OTHERWISE
 IMPACTED, CHANGES TO RECEPTACLES, INCLUDING ARC FAULT,
 GFCI AND RECEPTACLE SPACING MAY BE REQUIRED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-03 Cont ID  
Sent By jwitmer Date 2016-02-03 Time   Rev Time 0.00
Received By jwitmer Date 2016-02-03 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-02 Cont ID  
Sent By jwitmer Date 2016-02-02 Time 11:14 Rev Time 0.00
Received By jwitmer Date 2016-01-29 Time 10:25 Sent To  
Notes
2016-02-01 10:26:11JWITMER'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-22 Cont ID  
Sent By dharvey Date 2016-01-22 Time 14:13 Rev Time 0.00
Received By dharvey Date 2015-12-21 Time 13:08 Sent To  
Notes
2015-12-21 13:08:55B11

Review Stop P PLUMBING
Rev No 1 Status P Date 2016-01-04 Cont ID  
Sent By gjohnson Date 2016-01-04 Time 14:27 Rev Time 0.00
Received By gjohnson Date 2016-01-04 Time 14:26 Sent To  
Notes
***NONE***