Plan Review Details - Permit 15120534
Plan Review Stops For Permit 15120534
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2016-02-12 Cont ID  
Sent By cthroop Date 2016-02-12 Time 13:44 Rev Time 0.00
Received By cthroop Date 2016-02-12 Time 13:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2016-01-13 Cont ID  
Sent By cthroop Date 2016-01-13 Time 14:44 Rev Time 0.00
Received By cthroop Date 2016-01-13 Time 14:44 Sent To  
Notes
2016-01-13 14:59:30CHRISTOPHER S. THROOP, C.B.O.
 BLDG. PLANS EXAMINER ? PX3169
 (561) 805-6718
 [email protected]
  
 PROVIDE SOIL REPORT
 R401.4 SOIL TESTS.
 WHERE QUANTIFIABLE DATA CREATED BY ACCEPTED SOIL
 SCIENCE METHODOLOGIES INDICATE EXPANSIVE, COMPRESSIBLE,
 SHIFTING OR OTHER QUESTIONABLE SOIL CHARACTERISTICS ARE
 LIKELY TO BE PRESENT, THE BUILDING OFFICIAL SHALL
 DETERMINE WHETHER TO REQUIRE A SOIL TEST TO DETERMINE
 THE SOIL?S CHARACTERISTICS AT A PARTICULAR LOCATION.
 THIS TEST SHALL BE DONE BY AN APPROVED AGENCY USING AN
 APPROVED METHOD.
  
 PROVIDE TRUSS TIE DOWN DETAIL FOR GARAGE TRUSSES. REF.
 DETAIL 6, PG. 6.6.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2016-02-11 Cont ID  
Sent By vperez Date 2016-02-11 Time 14:06 Rev Time 0.00
Received By vperez Date 2016-02-11 Time 14:06 Sent To  
Notes
2016-02-11 14:06:56SENT TO S. KENNEDY 2/11

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2016-01-06 Cont ID  
Sent By albarran Date 2016-01-06 Time 15:43 Rev Time 0.00
Received By albarran Date 2016-01-06 Time 10:10 Sent To  
Notes
2016-01-06 15:44:14THE PLANS FOR THE ABOVE MENTIONED REVISION HAS BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE), FIRE CODES AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1. NEC 300.5(B). YOUR NOTES INDICATE THHN CONDUCTOR
 INSULATION UON. PLEASE BE AWARE THAT THE INTERIOR OF
 ANY UNDERGROUND RACEWAY IS CONSIDERED A WET LOCATION
 THUS THWN IS REQUIRED.
 2. NEC 406.9(B), RECEPTACLES OUTDOORS OR EXPOSED TO THE
 WEATHER SHALL BE LISTED WEATHER-RESISTANT ?WR?.
 3. REVISE NOTE 9 TO REFLECT THE CURRENT/APPLICABLE
 CODE. NEC 2011 AND ARTICLE 406.12 ADDRESSES THE
 TAMPER-RESISTANT RECEPTACLES.
 4. THE WORD ?ROMEX? AS USED IN YOUR NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE; REFER TO CABLE TYPES ?NM?, ?NMC? OR ?NMS?.
 5. NEC 422.15 CENTRAL VACUUM OUTLETS. ALL CENTRAL
 VACUUM OUTLET ASSEMBLIES SHALL COMPLY AS INDICATED
 HEREIN.
 6. NEC 210.12, ARC-FAULT CIRCUIT PROTECTION SHALL BE
 INSTALLED AS INDICATED.
 7. NEC 314.27(A) LUMINAIRE OUTLETS. BOXES USED AT
 LUMINAIRE OR LAMPHOLDER OUTLETS IN A CEILING SHALL BE
 REQUIRED TO SUPPORT A LUMINAIRE WEIGHING A MINIMUM OF
 50 LB. ADD THIS TO THE NOTES ON CEILING BOXES ON PAGE.
 8. NEC 314.27(D) PADDLE FANS. BOXES USED FOR THE SOLE
 SUPPORT OF CEILING FANS SHALL BE MARKED BY THE
 MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND INDICATE
 THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED TO SUPPORT
 PADDLE FANS HEAVIER THAN 70 LBS.
 9. NEC 410.110 & FBC-E C402.4.8 RECESSED LIGHTING.
 RECESSED LIGHTING INSTALLED IN THE BUILDING THERMAL
 ENVELOPE SHALL BE IC RATED AND BE SEALED TO LIMIT AIR
 LEAKAGE BETWEEN CONDITIONED & UNCONDITIONED SPACES.
 10. NEC 250.94 BONDING FOR OTHER SYSTEMS. THE
 INTER-SYSTEM BONDING TERMINAL PRESCRIBED SHALL BE
 INSTALLED.
 11. NEC 210.52 (A)(2) WALL SPACE. ANY WALL SPACE 2 FT.
 OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. THIS
 INCLUDES THE WALL ADJACENT TO THE REAR DOOR.
 12. NEC 210.52(C)(3) PENINSULAR COUNTERTOP SPACES. AT
 LEAST ONE RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH
 PENINSULAR COUNTERTOP.
 13. NEC 210.8 GROUND FAULT CIRCUIT-INTERRUPTER
 PROTECTION. GFI REQUIRED FOR THE OUTLET ADJACENT TO THE
 SINK IN THE LAUNDRY ROOM & THE OUTLET IN THE MASTER
 BEDROOM IF LESS THAN 6FT. FROM SINK.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2016-01-08 Cont ID  
Sent By dkittred Date 2016-01-08 Time 14:58 Rev Time 0.00
Received By dkittred Date 2016-01-08 Time 14:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2016-02-25 Cont ID  
Sent By ccole Date 2016-02-25 Time 08:24 Rev Time 0.00
Received By ccole Date 2016-02-24 Time 15:15 Sent To  
Notes
2016-02-24 15:15:10RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2016-02-12 Cont ID  
Sent By ccole Date 2016-02-12 Time 15:21 Rev Time 0.00
Received By ccole Date 2016-02-09 Time 09:25 Sent To  
Notes
2016-02-10 09:29:06R21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2016-01-22 Cont ID  
Sent By ccole Date 2016-01-22 Time 07:43 Rev Time 0.00
Received By ccole Date 2015-12-15 Time 10:18 Sent To  
Notes
2015-12-16 10:20:50R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2016-02-12 Cont ID  
Sent By cthroop Date 2016-02-12 Time 13:43 Rev Time 0.00
Received By cthroop Date 2016-02-12 Time 13:43 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2016-01-21 Cont ID  
Sent By skennedy Date 2016-01-21 Time 16:05 Rev Time 0.00
Received By skennedy Date 2016-01-21 Time 16:05 Sent To  
Notes
2016-01-21 16:06:43PLANS REQUIRE REVIEW BY THE PBC IMPACT FEE OFFICE. CALL
 233-5025. UPON APPROVAL, YOU MAY CHECK OUT ONE PLAN AND
 TAKE TO THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED
 WITH A COPY OF RECEIPT AS APPLICABLE.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2016-02-25 Cont ID  
Sent By ccole Date 2016-02-25 Time 08:23 Rev Time 0.00
Received By ccole Date 2016-02-25 Time 08:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2016-02-12 Cont ID  
Sent By ccole Date 2016-02-12 Time 15:22 Rev Time 0.00
Received By ccole Date 2016-02-12 Time 15:22 Sent To  
Notes
2016-02-12 15:50:452ND REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120534
 2/12/16
  
 1) AS STATED IN THE LETTER FROM MR. HUMBERTO DIAZ
 R403.6.1 EQUIPMENT SIZING.
 "HEATING AND COOLING EQUIPMENT SHALL BE SIZED IN
 ACCORDANCE WITH ACCA MANUAL S BASED ON THE EQUIPMENT
 LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED HEATING AND COOLING CALCULATION
 METHODOLOGIES, BASED ON BUILDING LOADS FOR THE
 DIRECTIONAL ORIENTATION OF THE BUILDING. THE
 MANUFACTURER AND MODEL NUMBER OF THE OUTDOOR AND INDOOR
 UNITS (IF SPLIT SYSTEM) SHALL BE SUBMITTED ALONG WITH
 THE SENSIBLE AND TOTAL COOLING CAPACITIES AT THE DESIGN
 CONDITIONS DESCRIBED IN SECTION R302.1. THIS CODE DOES
 NOT ALLOW DESIGNER SAFETY FACTORS, PROVISIONS FOR
 FUTURE EXPANSION OR OTHER FACTORS WHICH AFFECT
 EQUIPMENT SIZING. SYSTEM SIZING CALCULATIONS SHALL NOT
 INCLUDE LOADS CREATED BY LOCAL INTERMITTENT MECHANICAL
 VENTILATION SUCH AS STANDARD KITCHEN AND BATHROOM
 EXHAUST SYSTEMS." THE SUBMITTED REVISED CALCULATION
 DOES NOT PROVIDE LOADS BASED ON THE DIRECTIONAL
 ORIENTATION OF THE BUILDING, DOES NOT IDENTIFY THE
 PROJECT, PROJECT ADDRESS,MANUFACTURER AND MODEL NUMBER
 OF THE EQUIPMENT, AND THE PERSON WHO PREPARED THE
 CALDCULATION. THE LETTER STATES THAT THE CALCULATION
 METHOD USED IS THE CARRIER HAP SOFTWARE PROGRAM HOWEVER
 THAT TITLE DOES NOT APPEAR ANYWHERE ON THE DOCUMENT. AS
 PREVIOULSY REQUESTED, PLEASE PROVIDE MANUAL J
 CALCULATIONS USING AN APPROVED SOFTWARE PROGRAM.
 2) THE AC CLOSET SIZE IS NOT IN COMPLIANCE WITH SECTION
 M1305.1.1 WHICH REQUIRES THE ENCLOSING SPACE TO BE AT
 LEAST 12 IN. WIDER THAN THE WIDTH OF THE AIR HANDLER.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2016-01-22 Cont ID  
Sent By albarran Date 2016-01-06 Time 15:54 Rev Time 0.00
Received By ccole Date 2016-01-22 Time 07:07 Sent To  
Notes
2016-01-22 07:35:331ST REVIEW: FBC 2014 MECHANICAL
 PERMIT #15120534
 1/22/16
  
 1) THE AC SYSTEM SIZING CALCULATION WAS NOT PERFORMED
 USING AN APPROVED CALCULATION METHODOLOGY AS REQUIRED
 PER SECTION R4-03.6 FBC-14 ENERGY CONSERVATION. THE
 SOFTWARE PROGRAM FROM HVAC COMPUTER SYSTEMS LTD. DOES
 NOT HAVE ACCA APRROVAL OR ANY OTHER AGENCY APPROVAL.
 2) ENERGY COMPLIANCE FORM R405-2014: IT APPEARS THAT
 MR. HUMBERTO DIAZ, WHO WAS THE PREPARER OF THE
 DOCUMENT, HAS ALSIO PRINTED THE NAMES OF THE OWNERS ON
 THE LINE WHERE THE OWNERS HAVE TO SIGN. PLEASE PROVIDE
 AN ORIGINAL SIGNATURE FROM THE OWNERS OR THE DOCUMENT.
 3) ENERGY FORM R405-2014: THE DATA LISTED FOR THE DOORS
 ON THE DOCUMENT DOES NOT MATCH THE PLAN WHICH SHOWS
 ONLY TWO SOLID DOORS- ONE ON THE NORTH SIDE AND ONE ON
 THE WEST SIDE. THE REMAINDER OF THE DOORS ARE SLIDING
 GLASS TYPES- PLEASE CORRECT.
 4) SHEET M.1: SUFFICIENT SPACE MUST BE [PROVIDED FPOR
 THE AIR HANDLER IN THE CLOSET. PLEASE REFER TO
 M1305.1.1 FURNACES AND AIR HANDLERS FBC-14 RESIDENTIAL
 AND SHOW COMPLIANCE ON THE PLAN:
 FURNACES AND AIR HANDLERS WITHIN COMPARTMENTS OR
 ALCOVES SHALL HAVE A MINIMUM WORKING SPACE CLEARANCE OF
 3 INCHES (76 MM) ALONG THE SIDES, BACK AND TOP WITH A
 TOTAL WIDTH OF THE ENCLOSING SPACE BEING AT LEAST 12
 INCHES (305 MM) WIDER THAN THE FURNACE OR AIR HANDLER.
 FURNACES HAVING A FIREBOX OPEN TO THE ATMOSPHERE SHALL
 HAVE AT LEAST A 6-INCH (152 MM) WORKING SPACE ALONG THE
 FRONT COMBUSTION CHAMBER SIDE. COMBUSTION AIR OPENINGS
 AT THE REAR OR SIDE OF THE COMPARTMENT SHALL COMPLY
 WITH THE REQUIREMENTS OF CHAPTER 17.
 5) M.1: KEY NOTES ARE PROVIDED HOWEVER THEIR RELATIVE
 LOCATIONS ON THE PLAN ARE NOT SHOWN.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-12-20 Cont ID  
Sent By tklarge Date 2015-12-20 Time 11:35 Rev Time 0.00
Received By tklarge Date 2015-12-20 Time 11:23 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2016-01-13 Cont ID  
Sent By cthroop Date 2016-01-13 Time 14:44 Rev Time 0.00
Received By cthroop Date 2016-01-13 Time 14:44 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2016-02-11 Cont ID  
Sent By dkittred Date 2016-02-11 Time 11:00 Rev Time 0.00
Received By dkittred Date 2016-02-11 Time 10:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2016-01-08 Cont ID  
Sent By dkittred Date 2016-01-08 Time 14:53 Rev Time 0.00
Received By dkittred Date 2016-01-08 Time 13:22 Sent To  
Notes
2016-02-11 10:46:162/11/16 - SEPARATE LANDSCAPE PERMIT SUBMITTED FOR
 REVIEW (16020287), DK
2016-01-14 14:06:541/14/16 - SEPARATE DRIVEWAY PERMIT SUBMITTED FOR REVIEW
 (16010262), DK
  
2016-01-08 14:53:51PLANNING AND ZONING COMMENTS: ***FAILED***
  
 1/8/16
  
 1. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV MUST BE SUBMITTED FOR NEW CONSTRUCTION.
 (NOTE: ZLDR SEC. 94-442(B)(2)A. ? FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING, OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 )
  
 GENERAL COMMENT:
  
 A. SEPARATE PERMIT REQUIRED FOR DRIVEWAY. WHEN
 SUBMITTING FOR DRIVEWAY PERMIT PLEASE INCLUDE AN
 EASEMENT CONSENT FORM FROM FPL AS THE DRIVEWAY IS
 PROPOSED WITHIN AN FPL EASEMENT. STANDARD EASEMENT
 CONSENT FORM CAN BE FOUND AT THE FOLLOWING LINK: HTTP:/
 /WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/2013/0
 9/EASEMENT-CONSENT-FORM.PDF
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  