Plan Review Details - Permit 15120507
Plan Review Stops For Permit 15120507
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-12-21 Cont ID  
Sent By mvaldes Date 2015-12-21 Time 08:51 Rev Time 0.00
Received By mvaldes Date 2015-12-21 Time 08:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-12-16 Cont ID  
Sent By mvaldes Date 2015-12-16 Time 16:27 Rev Time 0.00
Received By mvaldes Date 2015-12-16 Time 16:27 Sent To  
Notes
2015-12-16 16:31:061ST REVIEW: FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 516-805-6700
 [email protected]
 ALTERNATE CONTACT
 MIKE ALBARRAN
 561-805-6746
 [email protected]
  
  
 PROVIDE LOAD CALCS
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL
 BE PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS.
 SUCH A
 DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE
 BUILDING
 OR OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED
 LOAD BEFORE APPLYING DEMAND FACTORS, THE DEMAND FACTORS
 USED, THE CALCULATED LOAD AFTER APPLYING DEMAND
 FACTORS,
 AND THE SIZE AND TYPE OF CONDUCTORS TO BE USED.
  
 SPOKE TO FPL ENGINEER HE STATED ONLY 1 SERVICE DROP AT
 LOT.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-12-21 Cont ID  
Sent By lmarchan Date 2015-12-21 Time 09:53 Rev Time 0.00
Received By lmarchan Date 2015-12-18 Time 14:00 Sent To  
Notes
2015-12-18 14:00:54RESUB ROUTED TO MVALDES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-12-17 Cont ID  
Sent By lmarchan Date 2015-12-17 Time 13:31 Rev Time 0.00
Received By lmarchan Date 2015-12-15 Time 15:07 Sent To  
Notes
2015-12-15 15:07:27ELECTRICAL INBOX