Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
3 |
Status |
P |
Date |
2015-12-29 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-29 |
Time |
15:05 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-29 |
Time |
15:05 |
Sent To |
|
|
Notes |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
2 |
Status |
F |
Date |
2015-12-23 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-23 |
Time |
07:36 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-23 |
Time |
07:36 |
Sent To |
|
|
Notes |
2015-12-23 07:42:00 | 1ST REVIEW 2010 MECHANICAL | | REVISION PERMIT #15120322 | | 12/23/15 | | | | 1) THE REVISED AC LAYOUT PLAN SHOWS THE AMOUNT OF CFM'S | | DISTRIBUTED WILL EXCEED THE CAPACAITIES OF THE TWO- | | 5TON SYSTEMS. AC-1- 2515 CFMS, AC-2- 2690 CFMS. PER | | TELEPHONE CONVERSATION WITH DAVID R. JONES P.E. ON | | 12/22/15, THE LAYOUT IS INCORRECT AND WILL BE REVISED. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
Review Stop |
M |
MECHANICAL (A/C) |
Rev No |
1 |
Status |
F |
Date |
2015-12-14 |
|
|
Cont ID |
|
Sent By |
ccole |
Date |
2015-12-14 |
Time |
11:52 |
Rev Time |
0.00 |
Received By |
ccole |
Date |
2015-12-14 |
Time |
11:52 |
Sent To |
|
|
Notes |
2015-12-14 11:58:48 | 1ST REVIEW 2014 MECHANICAL | | REVISION #15120322 | | 12/14/15 | | | | 1) THE PRINT ON THE REVISED LAYOUT PLAN IS UPSIDE DOWN: | | PLEASE REVISE IN ACCORDANCE WITH SECTION 107.2 WPB | | AMENDMENTS TO THE FBC-14 BUILDING CODE. | | 2) SHOW THE CONDENSATE PIPING RUNS AND DISCHARGE | | LOCATIONS. | | 3) SHOW THE REFRIGERANT PIPE RUNS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | | | |
|
|
|